Paten TED: Ice Rink Defogger (Packaged)
Paten TED: Ice Rink Defogger (Packaged)
TENTED
PA
ELECTRICAL RATINGS
TIMER
with design techniques to maintain optimal DT
1. Direct the air flow along the boards, do not direct air over the surface. 3. Unit should be 15 to 25 feet above ice surface. (Y)
2. Discharge duct equipped with horizontally and vertically adjustable louvers 4. Unit should be at a minimum of 4 feet from nearest obstruction. (X)
supplied by others.
X Y
PIPING DIAGRAM
REFRIGERATION
REFRIGERATIONCYCLE
CYCLE DESUPERHEATER
CONDENSER
HOT GAS
SOLENOID
RECEIVER
CHECK
VALVE
EVAPORATOR SUCTION LINE
HEAT EXCHANGER
ACCUMULATOR COMPRESSOR
CONDENSER
HOT GAS DEFROST CYCLE
HOT GAS DEFROST CYCLE DESUPERHEATER
CONDENSER HOT GAS
SOLENOID
RECEIVER
CHECK
VALVE
EVAPORATOR SUCTION LINE
HEAT EXCHANGER
ACCUMULATOR COMPRESSOR
PHYSICAL DIMENSIONS
1. Humidistat
2. Running compressor light 13
14 WIDE
3. Toggle switch for emergency 12
HIGH
9. Compressor removal access door
1 2 8
10. Mounting bolts for discharge 3
diffuser 4
7
11. Blower motor & belt access door 10
12. Drain pan access door
6
(Drain 1 1/4 MPT) 9
C
C/
R
13. Air filter access door ANC
5 O
CH EE
P
HO AN D
WIDER C/C
14. Air intake & evaporator coil face ANC
HOR
+ 1 1/
2
The contractor shall furnish and install where shown DEFROST HEAT EXCHANGER shall be included in PIPING shall be copper tube, brazed connections.
on the plan ( ) RefPlus ICE RINK DEFOGGER® each unit to eliminate flood back on defrost cycle. Access fittings for high and low pressure shall be
of the size indicated. located outside the enclosure. Each system shall be
RECEIVER shall be sized to hold the total refriger-
evacuated, dehydrated and charged with operating
Installation shall include mounting platform and ant charge for easy service of the unit. Rotolock
charge of R-22. Each system shall be tested for
discharge diffuser. Each unit shall be factory valves shall be supplied at inlet and outlet to isolate
performance and rating.
assembled and include the following: the refrigerant charge.
CONTROLS shall be located in an accessible,
CASING shall be heavy gauge steel painted white EXPANSION VALVE shall be balanced port type,
prewired, central control panel. Control panel shall
with powder paint. Internal heated drain pan shall specially engineered to operate efficiently at low
include compressor contactor, blower motor starter,
be constructed of stainless steel with 1 1/4 MPT head pressure thus reducing the power consumption
high and low pressure switch, time delay timer,
connection. at low ambient.
defrost control and low ambient thermostat.
UNIT shall be anchored to the platform with integral COILS (Evaporator, Condenser, Subcooler and Additionally, a humidistat shall be supplied and
anchoring rails included in the casing. Desuperheater) shall be constructed of die formed, installed outside the control panel, on the exterior of
collared, self-spacing aluminum plate fin and the unit along with "Compressor running" indicator
AIR FLOW shall be separated from refrigeration
copper tube staggered in direction of air flow and light and "On-Off" for emergency shutdown of the
components for easy servicing of unit while in
mechanically bonded to give metal to metal contact blower and compressor.
operation.
for maximum heat transfer and patented desuper-
PUMP DOWN CYCLE All units to operate on a
COMPRESSOR shall be heavy duty, hermetic, heating of the refrigerant circuitry. All coils shall
pump down cycle for a liquid free starting of the
suction cooled with internal motor protection, be leak pressure tested after welding at 400 psig.
compressor and to minimize refrigerant migration.
liquid slugging protection and centrifugal oil pump
FILTERS shall be 2 inches, throw-away type, in an
for long trouble-free operation. Compressor shall DEFROST SYSTEM shall be of the Demand
accessible filter rack with access door.
have internal suspension system and shall be Defrost type, time actuated and temperature
installed with external rubber vibration absorber CENTRIFUGAL BLOWERS shall be forward terminated. The hot gas defrost cycle shall be
for vibration-free operation. Compressor shall be curved statically and dynamically balanced, designed energized on fixed time intervals if ice is present
supplied with a crankcase heater to prevent for efficient operation and shall have permanently on the evaporator and shall stop when the
refrigerant migration. lubricated ball bearings. Blowers shall operate evaporator is ice free.
constantly to maintain even humidity within the
SUCTION ACCUMULATOR with boil out coil
controlled area.
shall be included in each unit in the refrigerant path
to ensure liquid-free refrigerant at the compressor. BLOWER MOTOR shall be open drip proof, ball
Also improves system efficiency by subcooling the bearing type, permanently lubricated. Overload
liquid. relay shall be provided to protect all current phases.
RefPlus Inc. reserves the right to make any changes in the design or specifications of any product at any time without notice. © Copyright 2003 by RefPlus Inc