Dear Sir,
With reference to above, we are pleased to place this order on you for supply of following
materials as per the price and terms and conditions indicated below:
Order value (in words): Rupees Twenty Eight Lakh Fifty Seven Thousand Nine
Hundred Twelve and Paisa Fifty Only.
1|Page
Make: Prabhu Switchgear Pvt. Ltd; Model: FLP-TX-01
Material Code : 13040522
02. Price: Prices are on FOR destination basis and shall remain FIRM till delivery.
However, the order prices shall not be considered as LPP for future
procurement.
04. Sales Tax (VAT): Shall be payable at actual on submission of documentary evidence
within the original delivery period. Current rate of VAT is indicated under scope of
supply. Any increase/decrease in VAT within the original delivery period shall be
paid at actual on submission of documentary evidence. Increase in the rate of VAT
during extended delivery period shall have to be borne by supplier.
05. Packing and Forwarding charges: Shall be paid at actuals as indicated under scope
of supply.
06. Freight charges: Shall be paid at actuals limited to the amount indicated under scope
of supply.
07. Insurance charges: Shall be paid at actuals as indicated under scope of supply. Safe
delivery of the consignment to consignee will be your responsibility.
08. Other charges: Shall be paid at actuals as indicated under scope of supply.
09. CENVAT: ECL shall avail CENVAT credit for the goods/services to be supplied
against this order for which proper invoice as per CE rules to be submitted by
supplier.
10. Input Tax credit (ITC): ECL shall avail ITC as per the VAT rules in case of supplies
where VAT is applicable. The supplier shall submit the Tax Invoice along with the
supplies wherever VAT is applicable.
11. Delivery schedule: Supply should be completed within 180 days from the issue of
purchase order. Early delivery shall be acceptable. Delivery conditions shall be as per
“Standard Terms & Conditions of purchase order-domestic supply”.
2|Page
14. E-payment: e-payment shall be made through NEFT/RTGS as per bank details of the
supplier given below. Terms of Payment shall be as per “Standard Terms &
Conditions of purchase order-domestic supply”.
Sl Key indicator for e-payment e-payment details of supplier
1 Name of the Payee Prabhu Switchgear Pvt. Ltd.
2 Bank A/c No. of Payee 27342560000153
3 Name of the bank with Branch name HDFC BANK LTD
and code BRANCH LAKE AVENUE,
CODE NO: 2734
4 IT PAN of Payee AACCP9241P
5 Indian Financial Service Code (IFSC) HDFC0002734
15. Security Deposit (SD): Security Deposit @ 10% of landed value of the order
amounting to Rs 2,85,792.00 (Rupees Two Lakh Eighty Five Thousand Seven
Hundred Ninety Two Only) shall be submitted by the supplier valid for minimum
period of 27 months from date of order as per format enclosed with NIT. However
for increase in landed value of order, if any, due to increase in rates of taxes and
duties within original delivery period, value of SD shall be enhanced suitably to cover
10% of the incremental order value. Further details are as per “Standard Terms &
Conditions of purchase order-domestic supply”.Exempted-supplier is DGS&D
Regd/Ancillary/Govt/PSU.
16. Performance Bank Guarantee (PBG): PBG @ 10% of landed value of the order
amounting to Rs 2,85,792.00 (Rupees Two Lakh Eighty Five Thousand Seven
Hundred Ninety Two Only) shall be submitted by the supplier valid for minimum
period of 27 months from date of order as per format enclosed with NIT. However for
increase in landed value of order, if any, due to increase in rates of taxes and duties
within original delivery period, value of PBG shall be enhanced suitably to cover 10%
of the incremental order value. Further details are as per “Standard Terms &
Conditions of purchase order-domestic supply”.
3|Page
18. The “Standard Terms & Conditions of purchase order-domestic supply” attached at
annexure-1 shall be an integral part of this Purchase Order and supply of goods
against this order shall be guided by the same.
19. Technical specification: Supply of goods against this order shall be in strict
compliance to the technical specifications enclosed at annex-2.
20. Pre Contract Integrity Pact: The Integrity Pact duly signed and stamped by
authorized representatives of the supplier and purchaser is enclosed at annexure-6. In
terms of section-6 of the Integrity Pact, the Independent External Monitor(IEM)
nominated for this tender shall be,
1. Shri J. N. Mishra, IAS (Retd.), 2/77, Vijay Khand, Gomti Nagar, Lucknow-226010, E
mail : jnmishra77@yahoo.co.in, M-09452775435/08009007744.
2. Sri Rakesh Jaruhar, Sector-B/9,Flat No.6457, Vasant Kunj, New Delhi -110070, e
mail : rakeshjaruhar@hotmail.com
21. Contact Person of supplier: Mr. Anand Kumar Agarwala (DIRECTOR) Mobile no.
9831180847; Email: prabhuswitchgear@hotmail.com.
22. Please quote Purchase Order No. & Date in future correspondences.
Yours faithfully,
For and on behalf of Eastern Coalfields Limited
Enclosures
1. Annexure–1 : Standard Terms & Conditions of purchase order-domestic
2. Annexure–2 : Technical specifications & TPS
Copy to:
1. CVO/ GM(E&M)/HOD/GM(Fin.)IC – ECL HQ.
2. DY.GM(MM), Depot Officer, Sodepur Central Stores, ECL.
3. Sr. Manager, Finance(Bills), ECL, Sanctoria.
4. Progress Cell, ECL (HQ) – This is covered against IC No. 51511095 dated 24.08.15.
BC has been provided vide B.C No: CB/EM/P&M/16-17/37 dt. 24.05.16 for Rs
30,12,065.63/=. F.C No: Chief Manager(F)/Lighting Transformer/16-17/31 dt.
25.05.16 for Rs 30,12,065.63/= (Rupees Thirty Lakh Twelve Thousand Sixty Five
and Paisa Sixty Three) Only.
5. GM (MM) – CIL/BCCL/CCL/WCL/SECL/NCL/MCL/NEC.
6. Asstt. Commissioner, Commercial Taxes, Central Section, 14, Beliaghata Road,
Kolkata
Indent details
Sl no Indent no & date Area Indentor
1 KKC/AGENT/2013/ 169(A) dated 22/23.10.13 Kajora GM, Kajora area
2 NIT/14-15/NK/03 dated 09.10.14 Kunustoria GM, Kunustoria area
3 GM/SA/E&M/14/38 dated 16.05.14 Sripur GM, Sripur area
4|Page
Annexure-1
Standard Terms & Conditions of purchase order-domestic
01. Delivery terms: Except under specific instructions delivery to stores is restricted up
to 3.00 p.m. on all working days except Saturdays. Supply will be made on FOR destination
basis at the consignee store/stores. Supplier shall be wholly responsible for any loss &
damage in transit. Safe arrival of the consignment upto the destination stores shall be the
responsibility of the supplier.
The supplier while dispatching materials by road has to ensure compliance of the provisions
of “Carriage by Road Act’ 2007” and ensure that transportation of goods is done through
registered common carrier only. Way Bill, if required, may be obtained from consignee for
which a request may be sent to them indicating following details –
I. TIN/VAT No.
II. CST No.
III. Full address with pin code
IV. PAN No.
6|Page
c) The PBG should be submitted before delivery of first consignment and shall remain valid
upto three months beyond warranty period.
d) The Performance Bank Guarantee shall be released after expiry of warranty period and
receipt of no claim certificate from the user and on receipt of request letter from supplier.
9|Page
suppliers shall in no event exceed the lowest price at which suppliers sell the stores or offer to
sell the stores of identical description to any customer during the tenure of the supply order.
If any time during the said period, the suppliers reduce the sale price, sell or offers to sell
such stores to any other customer at a price lower than the ordered price, they shall forthwith
notify such reduction of sale or offer to sell to us to enable us to amend the rates of the order.
15. Guarantee/Warranty
The supplier shall give a warranty of satisfactory performance of the unit offered by them for a
period of 12 months from the date of commissioning or 18 months from the date of receipt and
acceptance by ECL. The supplier shall be responsible for any defects that they develop under
the conditions provided for by the contract and under proper use, arising from faulty materials,
design or workmanship and shall remedy such defects at his own cost when called upon to do
so. If it becomes necessary for the supplier to replace on renew any defective portion of the
goods, such replacement or renewal should be made by the supplier without any extra cost to
ECL on door delivery basis.
18. Technical support and service: In addition to normal after sales service, the supplier
will render technical support and service to ensure proper usage, maintenance and
satisfactory performance of the items supplied.
Special Note: Any other item(s) not specified above, but required for the completeness of
the Main Ventilation Fan, its erection, commissioning and smooth operation is (are) also
included in the scope of supply.
19. Inspection
GM(E&M)/HOD or his authorized representative shall have the right to inspect and/or to test
the goods to confirm their conformity with the contract and in case any inspected/tested
10 | P a g e
goods fail to perform to the specifications, the purchaser may reject them and the supplier
shall either replace the rejected goods / make alterations necessary to meet the specifications
free of cost to the purchaser. The stores will be inspected at final destination. However, ECL
reserves the right to inspect the goods at supplier’s premises before dispatch by himself or a
nominated agency like CMPDIL, RITES etc. Manufacturers standard test certificates
indicating conformation to the specifications of the order should be submitted in advance.
20. Verification & endorsement during inspection
Wherever there is necessity to obtain certificates from DGMS, BIS and Manufacturers’ Test
and Guarantee certificate etc as per the terms of the purchase order, the inspecting authority
has to verify the relevant documents and the same should be recorded in the inspection note.
The materials shall be received and SRVs will be prepared only on compliance of the said
condition.
21. Terms and conditions of Notice Inviting Tender(NIT) shall be an integral part of this
Purchase Order.
22. Any terms and conditions not specifically mentioned in the order, shall be governed by
the General Terms & Conditions of Supply of Stores” as mentioned in Enclosure 6 of the
tender documents. Further, any terms and conditions not specifically mentioned anywhere in
the “General Terms & Conditions of Supply of Stores”, shall be governed by the provisions
of the Purchase Manual which is available in the web-site of Coal India Limited namely –
www.coalindia.in.
23. Jurisdiction: Any dispute arising out of this contract shall come under the sole
jurisdiction of Court at Asansol, West Bengal.
xxxxxxxxx
11 | P a g e
Annexure-2
Technical Section & TPS
A. Technical Section
Sl Features
A Adjustable Wheel and Axle Assembly to suit 24" track Gauge.
Compact Design to suit low gallery height.
Three separate compartments for H.T. Circuit Breaker, Transformer and L.T Distribution
Chamber. Each compartment should be individually and combined certified flameproof for
Gas Group-I (Methane) by the DGMS, Dhanbad.
All cable entries and outlets are of FLP plug and socket type preferably interchangeable and
to suit PVCDWA Mining Cable.
All CTs and PTs are resin cast.
The Earth Leakage Relay shall be neutral CT operated with test and reset facility properly
pad locked.
Insulating materials used must be non hygroscopic in chamber..
Must have inspection cover for Tap changing Gear.
Drain Sump for periodical drainage of breathed in condensed Vapour.
B H.T. CIRCUIT BREAKER: 3.3 KV, 75 MVA rupturing capacity FLP horizontal draw
out Vertical/Horizontal Isolation flange mounted Vacuum Circuit Breaker having the
following safety features:
CT operated Magnetic Overload Protection with Dashpot type time lag arrangement having
setting range 75% to 150% of the full load current.
Restricted neutral CT operated E/L Relay, 50 to 750 mA with setting range having
Test/Reset and visual indication facility.
FLP Plug and Socket type incoming cable connector suitable for PVCDWA cable provision
for through-going connector suitably blanked.
CT operated Ammeter, suitably scaled, housed on a flameproof chamber.
PT operated voltmeter, suitably sealed, housed in flameproof chamber..
Proper interlocking arrangement.
C TRANSFORMER: FLP Air cooled, Copper Wound Transformer having the following
details:-
Rating : 315 KVA
Connection : Delta / Star
Vector Group : DY 11
Voltage Ratio : 3.3 KV /550V with tapping ± 2.5%, ± 5%, ± 7.5%
D L.V.DISTRIBUTION CHAMBER:The distribution chamber shall divide the secondary
into two distinct feeders. The following should be provided:-.
CT Chamber for each Feeder, housed in a flameproof Chamber.
Earth Leakage Protection for each Feeder for restricted Neutral System.
CT operated O/L Relay for each Feeder: The O/L Trip and Secondary Leakage Trip shall
actuate the HT VCB for tripping purpose.
Fail safe arrangement with suitable rating resistance to be provided for restricted neutral
earthing so that leakage current must be restricted within 750 mA.
E DIMENSION: Overall Width :- 1.1 Mtr (Approx)
Overall height : 1.6 Mtr (Approx)
F NOTE:- There should be provision for neutral of the transformer to be grounded through a
12 | P a g e
proper rating resistance so that in case of earth fault, leakage current should be restricted to
750 mA as per CEAR 2010 in 550 V side. The whole system should have fall safe
arrangement, so that if the resistance break due to any reason, fall safe relay will trip the
primary Breaker of the Transwitch Unit.
Time/current characteristics Curve of the Oil Dash Pot Over Load Relay (in both primary
and secondary breaker) along with specification /details of the Oil (Like brand name, grade,
viscosity etc.) to be used with the O/L Relay to be submitted along with the offer and along
with the supply.
Successful tenderer shall have to furnish test Certificate of Time/Current Characteristics of
the O/L Relay along with the supply and to be sure that during testing at Consignee's end,
same result can be obtained.
G Special Note : Any other component, accessories not specifically mentioned in this
specification but required for safe and trouble free operation must be included in the scope
of supply.
B. TPS
S.
Description of Unit of Bidder's value
No Specification Parameter *
Item * Measure
*
DGMS
APPROVED,
FLP
1 TRANSWITCH Offered Quantity No 5
UNIT, 315
KVA, 3.3 KV/
550 V
Duty:-The Transwitch Unit is intended NA AGREED
as a mobile unitized Substation used in
Underground Coal mines & suitable for
frequent shifting which will be having
heavily dust laden and highly humid
atmosphere. The TSU will comprise of
FLP 3.3 KV VCB, FLP 315KVA,
3.3KV/550V, 3 Ph Dry transformer and
FLP 550 V LT Distribution chamber of
suitable rating on secondary side. All the
three units will be coupled directly to
make a single compact unit and shall be
mounted on Wheel & Axle. All the
components will comply with provision
of latest version of statue, regulations &
relevant standards. The system of supply
is restricted neutral system of power
supply as per CEAR 2010
(A)H.T.Circuit Breaker:- The primary NA AGREED
control 3.3 KV VCB shall have rupturing
capacity of 75 MVA
(B)DRY TYPE TRANSFORMER: NA AGREED
FLP Air cooled, Copper Wound
Transformer ,315KVA ,3.3KV/550V,
13 | P a g e
Connection -Delta / Star,Vector Group
- DY 11
(C)L.V.DISTRIBUTION CHAMBER: NA AGREED
The distribution chamber shall divide the
secondary into two distinct feeders.
Arrangement to be provided for Tripping NA AGREED
of HT Breaker due to overload or Earth
Leakage on Secondary side.
Details to be furnished by bidder :- NA AGREED
H.T. CIRCUIT BREAKER: Voltage KV 3.3
Rupturing Capacity MVA 75
NA 100/5 FOR
CT ratio and rating METERING, 60/5
FOR PROTECTION,
PT ratio and rating NA 150VA, 3.3KV/110V
NA OVERLOAD,
EARTH LEAKAGE,
Details of Protection
UNDER VOLTAGE,
ISOLATOR
NA INCOMING BY
MEANS OF FLP
PLUG & SOCKET
Cable Entry THROUGH GOING
SUITABLY
BLANKED
NA THE VCB SHALL
BE FULLY
DRAWOUT TYPE
MOUNTED ON
Isolation and Draw out WHEELS.
NA PUSH BUTTON
ACTUATORS
SHALL BE
PROVIDED ON
FRONT DOOR FOR
PURPOSE OF E.L.
Test/Reset Switch TEST & E.L. RESET
NA The whole unit such as
transitch, vcb and the
l.t. chamber shall be of
flp as per IS/IEC:
FLP Features 60079-1:2007
NA Ammeter, Voltmeter
Provision of Metering provided
NA 1) Door Interlock with
Isolator, Isolator and
Provision of Interlocking VCB
TRANSFORMER: Type NA DRY TYPE
Winding NA COPPER
Cooling NA AIR COOLED
14 | P a g e
Rating NA 315KVA
NA PRMARY: 3.3KV &
Voltage Ratio SECONDARY: 550V
NA DELTA/STAR,
VECTOR GROUP
Connection and Vector Group DYN-11
% Tapping +/- 2.5%,+/-
Tapping 5%, +/-7.5%
Temperature Rise ºC 115
NA The enclosure has
been made as per
IS/IEC: 60079-1:2007
and DGMS Approved
FLP Feature. & BIS Marked
L.V.DISTRIBUTION CHAMBER: NA AGREED
Division into two Feeders NA AGREED
NA 1) Overload (2) Earth
Leakage Relay (3) Fail
Details of Protection Safe Relay
NA 2 sets of 200/5 for
CT Ratio each feeder
NA Ammeter, Voltmeter
Provision of Metering provided
NA 2 outlets through FLP
Cable Entry Plug & Sockets.
Resistance in Ohms for restricted neutral NA 450 Ohms, 250 Watt.
Earthing and fail safe arrangement