UNIVERSIDAD NACIONAL DE COLOMBIA - SEDE MANIZALES

MÁQUINAS ELÉCTRICAS II LISTA 4 – MAQUINAS ROTATIVAS - INTRO

1 The rotor of a six-pole synchronous generator is rotating at a mechanical speed of 1200 r/min.
a) Express this mechanical speed in radians per second.
b) What is the frequency of the generated voltage in hertz and in radians per second?
c) What mechanical speed in revolutions per minute would be required to generate voltage at a frequency of
50 Hz?

2 The simple loop rotating in a uniform magnetic field shown in Figure has the following characteristics: B=
0,5 T to the right r =0,1m l = 0,5 m  = 103 rad/s
a) Calculate the voltage etot(t) induced in this rotating loop.
b) Suppose that a 5Ω resistor is connected as a load across the terminals of the loop. Calculate the current that
would flow through the resistor.
c) Calculate the magnitude and direction of the induced torque on the loop for the conditions in b).
d) Calculate the electric power being generated by the loop for the conditions in b).
e) Calculate the mechanical power being consumed by the loop for the conditions in b. How does this number
compare to the amount of electric power being generated by the loop?

3 A three-phase Y-connected ac machine is initially operating under balanced three-phase conditions


when one of the phase windings becomes open-circuited. Because there is no neutral connection on
the winding, this requires that the currents in the remaining two windings become equal and opposite.
Under this condition, calculate the relative magnitudes of the resultant positive- and negative-traveling
mmf waves.

4 What is the effect on the rotating mmf and flux waves of a three-phase winding produced by balanced-
three-phase currents if two of the phase connections are interchanges?

5 In a balanced two-phase machine, the two windings are displaced 90 electrical degrees in space, and the
currents in the two windings are phase-displaced 90 electrical degrees in time. For such a machine, carry out
the process leading to an equation for the rotating mmf wave.
MÁQUINAS ELÉCTRICAS II – TRANSFORMADOR MONOFÁSICO 2

6 A three-phase, four-pole winding is installed in 12 slots on a stator. There are 40 turns of wire in each slot
of the windings. All coils in each phase are connected in series, and the three phases are connected in delta.
The flux per pole in the machine is 0,060 Wb, and the speed of rotation of the magnetic field is 1800 r/min.
a) What is the frequency of the voltage produced in this winding?
b) What are the resulting phase and terminal voltages of this stator?

7 A six-pole, 60-Hz synchronous machine has a rotor winding with a total of 138 series turns and a winding
factor kr= 0,935. The rotor length is 1,97 m, the rotor radius is 58 cm, and the air-gap length = 3,15 cm.
a) What is the rated operating speed in r/min?
b) Calculate the rotor-winding current required to achieve a peak fundamental air-gap flux density of 1,23 T.
c) Calculate the corresponding flux per pole.
d) Assume that a phase winding of the synchronous machine consists of one full-pitch, 11-turn coil per pole
pair, with the coils connected in series to form the phase winding. If the machine is operating at rated speed
and under the operating conditions of literal b), calculate the rms generated voltage per phase.
e) Assume that the synchronous machine has a three-phase winding with 45 series turns per phase and a
winding factor kw= 0,928. For the flux condition of literal b) and rated speed calculate the rms-generated voltage
per phase.

8 A two-pole, 60-Hz, three-phase, laboratory-size synchronous generator has a rotor radius of 5,71
cm, a rotor length of 18,0 cm, and an air-gap length of 0,25 mm. The rotor field winding consists of
264 turns with a winding factor of kr = 0,95. The Y-connected armature winding consists of 45 turns
per phase with a winding factor kw = 0,93.
a) Calculate the flux per pole and peak fundamental air-gap flux density which will result in an open-
circuit, 60-Hz armature voltage of 120 V rms/phase (line-to-neutral).
b) Calculate the dc field current required to achieve the operating condition of part (a).
c) Calculate the peak value of the field-winding to armature-phase-winding mutual inductance.

9 A four-pole, 60-Hz synchronous generator has a rotor length of 5,2 m, diameter of 1,24 m, and air-gap
length of 5,9 cm. The rotor winding consists of a series connection of 63 turns per pole with a winding factor
of kr = 0,91. The peak value of the fundamental air-gap flux density is limited to 1,1 T and the rotor
winding current to 2700 A. Calculate the maximum torque (N.m) and power output (MW) which can be supplied
by this machine.