Professional Documents
Culture Documents
Catalog Chapter-1A - 15Sep2011Blue - Revision2 PDF
Catalog Chapter-1A - 15Sep2011Blue - Revision2 PDF
25
YE
F
CE
EX
CE
LL EN
ENGINEERING
DATA
www.airmasteremirates.com
1.0 index
ENGINEERING DATA
ISO 9001 CERTIFIED COMPANY
INDEX
SECTION TOPIC PAGE
1.1 Introduction 3
1.2 Glossary of terms and definitions 3
1.3 Performance factors 4
1.4 Air jets and jet temperature 9
1.5 Selection of supply outlets 13
1.6 Sound 15
1.7 Noise Vs Air terminal devices 21
1.8 Air flow measurement 24
1.9 Material construction 27
1.10 Powder coating 28
1.11 Expansion and contraction of linear bar grilles
and registers 29
1.12 Weight of duct material 30
1.13 Unit conversions 31
1.14 References 32
Cover Page Photo: Air Master Emirates have successfully installed substantial number of products at the Burj Khalifa, the tallest
building in the world. We are proud of being chosen as a supply partner for this prestigious project.
In the modern HVAC system, the wrongly chosen air Free area:
outlets leads to failure of the entire HVAC system. The Total minimum area of the opening in air outlet through
considerations while doing a perfect and competitive which air can pass.
selection of air outlet are occupant comfort, energy
conservation, air quality and the cost. It is the foremost Effective area (Ak) Or area factor:
purpose of this Air Distribution Engineering section. The calculated area of an outlet based on the average
The details provided in this section are referred from measured velocity between the fins.
ASHRAE Handbooks and Standards.
Terminal velocity:
The point at which the discharged air from an outlet
decreases to a given speed, generally accepted as
1.2 GLOSSARY OF TERMS AND 0.25 m/sec.
DEFINITIONS
Envelope:
The outer boundary of the air stream moving at a
Grille: perceptible velocity (Ex: 0.50 m/sec envelope).
A louvered covering for an opening through which air
passes (generally installed in a side wall). Stratified zone:
A region in which room air velocity is less than
Return: 0.075 m/sec (15 FPM).
An outlet for return or exhaust air.
Stratification boundary:
Damper: The boundary between room air currents moving faster
A device used to control the volume of air passing than 0.075 m/sec (15 FPM) and stratified zone.
through an outlet or inlet.
Primary air:
Register: The air coming directly from the outlet.
A grille which is equipped with a damper and control
valve and directs air in a non-spreading pattern. Secondary air:
The room air which is picked up and carried along by
Diffuser: the primary air.
A circular, square or rectangular outlet discharging
supply air in a spreading pattern (generally installed in Total air:
a ceiling). Mixture of primary and secondary air.
Table 2 gives information about the effects of local air velocities on the preferred indoor air temperature and the
thermal comfort of occupants.
Characteristic length (L) in meters: The ratio of throw to characteristic length Tv/L is re-
Characteristic length is either the horizontal distance lated to the ADPI of various supply outlets and has
from the surface of the outlet to the nearest vertical op- been used as a parameter in space diffusion design.
posite wall or the horizontal distance from the surface As per Air Diffusion Council, throw can be measured
of the outlet to the mid plane between two outlets in the only when the temperature differentials i.e. difference
direction of air flow or distance to the closest intersec- between supply air and room air temperature cannot
tion of air jets. exceed ± 2º C.
60 2.5 86 80 <3.8
Light Troffer Diffusers 40 1.0 92 90 <3.0
20 1.0 95 90 <4.5
Conversion formulae:
1. BTU/Hr Sq. Ft. = 0.317 W/Sq.-Mt.
2. (ºF-32) × 5/9 = ºC.
MAIN DUCT FPM M/sec FPM M/sec FPM M/sec FPM M/sec FPM M/sec FPM M/sec
Rectangular Duct 1000 5.0 2200 11.18 3000 15.2 1800 9.15 2500 12.7 3500 17.78
Round Duct 1200 6.0 2400 12.2 4000 20.33 2100 10.67 3200 16.26 6500 33.0
BRANCH DUCT FPM M/Sec FPM M/Sec FPM M/Sec FPM M/Sec FPM M/Sec FPM M/Sec
Rectangular Duct 500 2.5 1600 8.13 2500 12.70 800 4.1 2000 10.16 3000 15.25
Round Duct 600 3.0 2000 10.16 3000 15.25 1000 5.1 2500 12.7 4000 20.33
An Air Jet is an air stream that discharges from an outlet with a significantly higher velocity than that of the surrounding
air, and moves along its central axis until its terminal velocity reduces to a value that equal or approximately equals
the velocity of the ambient air. Because of the turbulence of air particles, air jets tend to spread. They also rise or fall
depending on the buoyancy of the air stream. The outer boundary of an air jet moving at a perceptible velocity such
as 0.75 ,0.5 and 0.25 m/sec is called envelope.
In general, air jets can be classified as free or confined, isothermal or non-isothermal and axial or radial.
D0 Vx
Vy
2 = 22o
Surface of Boundary
the outlet
Core zone:
In the core zone, the central axis velocity remains un-
changed. This zone extends about 4D 0. (D 0 indicates the
diameter or the circular equivalent of supply outlet in me-
ter from the surface of the outlet. Fig. 5: Non isothermal jet.
Transition zone:
In the transition zone, the central axis velocity decreases
inversely with the square root of the distance from the
surface of the outlet. This zone extends about 8D 0.
If the jet is round, the velocity (V) at any point in the jet at standard air conditions is given by Schlichtung as
2 2 2
V = (7.41 × V0 × √A0 ) /d ( 1 + 57.5 R /d )
The equation shows that jet centerline velocity decreases inversely with distance from the source. One can define a
jet radius in several ways e.g. it could be the distance from the center line at which the velocity is 1% of the centerline
velocity. The jet radius increases with distance from the source. Cool air should not have a velocity of more than 45 to
50 fpm (0.25 m/sec) in occupied rooms for good comfort.
In the absence of manufacturer’s data during preliminary design the throw can be estimated from the dimensional
equation.
T = (K × VC) / Aeff
x W
s= ax =0.22
0.5Ar
1.0
0.5
0
0.1 0.2 0.3
ax
x=
0.5Ar
Sound Pressure Level: The human ear is more sensitive to high frequency than
Sound pressure level is the sound level a person hears low frequency.
from a source of sound at the given point of observa-
tion. This will be affected by distance from the source The design material used to attenuate sound depends
and acoustical environment of a room. This sound level on the frequency.
is the value of the ratio of the measured sound level to
the reference sound level. This value i.e. sound pres- The audible frequency range includes frequencies from
sure level is expressed in decibels by this equation. 20 to 20000 cycles per second. In order to simplify
measuring techniques this vast frequency range has
Lp = 10 Log10 (p/0.002)2 = 20 Log10 (p/0.002) been subdivided into eight separate frequency ranges
called octaves. The frequency of the upper limit of each
Where ‘p’ is sound pressure in microbars. Sound pres- band is twice that of the lowest frequency in each oc-
sure level is not used to rate the sound level by a given tave band. The preferred octave bands are 31.5 Hz, 63
source because sound pressure varies with distance Hz, 125 Hz, 250 Hz, 500 Hz, 1 kHz, 2 kHz, 4 kHz, 8 kHz
from the source and acoustical environment. and 16 kHz. The end bands (31.5 Hz and 16 kHz) are
rarely used.
Sound Power Level:
Sound power level is used to rate the sound output of
a sound source. The sound output of a given sound
source is a constant. Sound power level will not vary or
have any effect due to acoustical changes in a room.
Lw = 10 Log10 (W/10-12)
DBA scale: each frequency band. Beranek and Kosten have carried
The response of the ear to sound is non-linear. At low out experiments with office workers and home dwell-
frequencies it is less sensitive; which is why, for in- ers using broad-band noise sources. They produced
stance, the low frequency body vibrations cannot be the well known Noise Criteria (NC) and Noise Rating
heard. The ear’s response varies with loudness (phon) (NR) curves. NR curves gives a slightly more stringent
and frequency (Hertz). requirement than the NC curves in the higher frequen-
cies. For all practical purposes, NR and NC curves may
When sound levels are measured, the variation in the be regarded as mutually interchangeable.
sensitivity of the ear is to be taken into account by in-
corporating weighting networks in the meter. These are However, for sound control problems where the noise
termed as A, B and C. The response of the human ear level in certain octave bands is especially important,
to a sound level can be approximated by direct mea- design based on octave band sound levels is neces-
surement or by a combination of octave band sound sary. NC curves provide this information. NC curves
pressure measurement and mathematical calculation plot octave band frequencies versus sound level in
of the loudness level. The “A - scale noise level” is a decibels. NC curves are numbered and have increas-
direct measurement estimate of the human ear’s re- ing NC numbers as the allowable magnitude of the
sponse, which denoted as dBA. Two other methods of sound spectrum increases. Areas such as a concert
“loudness level” determinations of human ear response hall will have a low NC number and factories a relatively
use the units of sone and phone for the total loudness high NC number.
and loudness level respectively. These methods use a
combination of sound pressure level measurement and The following table (Table No: 8) is recommended noise
an equation to calculate loudness response. That is criteria for different functions. Also, the following graph
why most used weighted scale is dBA, the measuring (Fig. No: 8) is Noise Criteria Curves defining the design
of which corresponds to the 40 phon loudness level. criteria in terms of the maximum permissible sound
pressure level for each frequency band.
NC and NR curves:
Noise criterion curves are a method of using octave
bands for assessing the background noise level for an-
noyance and speech intelligibility in a given environment
and are attempts to express equal human tolerance in
Fig. 8: Frequency spectrum: Noise criteria curves defining the design criteria in terms of the maximum sound pressure level for
each frequency band.
Table 8: Range of design goals for air conditioning system sound control
A-Sound Level decibels NC Level decibels
Type of area Low Medium High Low Medium High
RESIDENCES:
Private homes (rural and suburban) 25 30 35 20 25 30
Private homes (urban) 30 35 40 25 30 35
Apartment houses 2 and 3 family units 35 40 45 30 35 40
HOTELS:
Individual hotel rooms and suits 35 40 45 30 35 40
Hall rooms, banquet rooms 35 40 45 30 35 40
Halls, corridors and lobbies 40 45 50 35 40 45
Garages 45 50 55 40 45 50
Kitchens and laundries 45 50 55 40 45 50
HOSPITALS AND CLINICS:
Private rooms 30 35 40 25 30 35
Operating rooms and wards 35 40 45 30 35 40
Laboratories, halls, corridors, lobbies 40 45 50 35 40 45
and toilets 40 45 50 35 40 45
wash rooms and toilets. 45 50 55 40 45 50
OFFICES:
Board rooms 25 30 35 20 25 30
Conference rooms 30 35 40 25 30 35
Executive office 35 40 45 30 35 40
Supervisor office, reception room 35 40 50 30 35 45
General open office, drafting rooms 40 45 55 35 40 50
Halls and corridors 40 50 55 35 45 55
Tabulation and computation 45 55 65 40 50 60
AUDITORIUMS AND MUSIC HALLS:
Consent and opera halls 25 30 35 20 22 25
Studios for sound reproduction 25 30 35 20 22 25
Legitimate theatres, multi propose halls 30 35 40 25 27 30
Movie theatres, TV audience studios 35 40 45 30 32 35
Semi-outdoor amphi theatres 35 40 45 30 32 35
Lecture halls, planetariums 35 40 45 30 32 35
Lobbies 40 45 50 35 40 45
CHURCHES AND SCHOOLS:
Sanctuaries 25 30 35 20 25 30
Libraries 35 40 45 30 35 40
Schools and classrooms 35 40 45 30 35 40
Laboratories 40 45 50 35 40 45
Recreation halls 40 45 55 35 40 50
Corridors and halls 40 50 55 35 45 50
Kitchens 45 50 55 40 45 50
PUBLIC BUILDINGS:
Public libraries, museums, court rooms 35 40 45 30 35 40
Post offices, general banking areas 40 45 45 30 35 40
Lobbies 40 45 50 35 40 45
Washrooms and toilets 45 50 55 40 45 50
RESTAURANTS, CAFETERIAS, LOUNGES:
Restaurants 40 45 50 35 40 45
Cocktail lounges 40 50 55 35 45 50
Night clubs 40 45 55 35 40 45
Cafeterias 45 50 55 40 45 50
RETAIL STORES:
Clothing stores 40 45 50 35 40 45
Department stores (upper floors) 40 45 50 35 40 45
Department stores (main floors) 45 50 55 40 45 50
Small retail stores 45 50 55 40 45 50
Supermarkets 45 50 55 40 45 50
Table 8 (cont.): Range of design goals for air conditioning system sound control
A-Sound Level decibels NC Level decibels
Type of area
Low Medium High Low Medium High
MANUFACTURING AREAS:
Foreman’s office 45 50 55 40 45 50
Assembly lines - light machinery 50 60 70 45 60 70
Foundries - heavy machinery 60 70 80 55 63 75
Sound design:
• Sound engineering and design can minimize the • Designing systems to operate at low static pressure
sound contribution of air terminals to an occupied will reduce the generated sound level. This will also
space. provide more energy efficient operation and allow
the central fan to be downsized.
• Wherever possible, terminals should be located
over areas less sensitive to noise. This includes • Sharp edges and transitions in ducting should
corridors, copy rooms, storage rooms, etc. Quiet be minimized to reduce turbulent air flow and its
air terminals facilitate the location of terminals over resulting sound contribution.
unoccupied space. With quiet terminals larger zones
are possible resulting in fewer terminals. This also
reduces first cost and increase energy efficiency.
1 LIVE Churches, swimming baths, factories, operating theaters, large canteens and gymnasiums
2 MEDIUM LIVE School rooms, lecture theatres, art galleries and public houses
3 AVERAGE Standard offices, libraries, hospital wards (rooms with no special acoustic treatment)
4 MEDIUM DEAD Restaurants, offices and board rooms with absorbent ceiling and floor covering hotel bedrooms
5 DEAD Radio and T.V. studios, audio metric rooms
Distance: Directivity:
As the measuring station moves away from the ATD, The Lp perceived at the measuring station will depend
the perceived Lp will drop. In the open air and anechoic on the positioning of the ATD in the room. Room correc-
rooms, the rate of fall is 6dB for each doubling of dis- tion charts are based on ATD positions at
tance. This is known as the inverse square law.
Junction of two surfaces - fig. A., Table 10.
Flush with one surface - fig. B., Table 11.
Table 10 (fig A): Room corrections for diffuser mounted at the junction with two surfaces
Table 11 (Fig. A): Room corrections for diffuser mounted flush with one surface
Number of ATDs:
If the number of ATDs in a room is doubled, the perceived will increase by 3dB. A second doubling will result in a
further increase of 3 db. The relation between number of ATDs and dB addition is given in table12.
The preceding phenomena can be described in mathematical terms enabling calculations of the resultant sound
pressure level as a function of frequency. A more convenient method is by the use of the room correctioncharts,
tables 10 and 11.
Example:
For a room of size 12×6×4 meters high is supplied with 1.32 m3/sec of air (2800 CFM). 4 slot diffuser is mounted in
the center of the room across 6 meter dimension. Diffuser is 8 meters long. Find noise correction factor for a throw
of 2 meters.
Assuming the room with no special acoustic treatment (choose rating 3, average room from table 9).
With table 11, enter at 288 m3/sec vertically upto rating line 3, then horizontally along the curve upto the intersection
of 2 meter distances. Then horizontally to read -6 dB.
POSSIBLE NOISE PROBLEMS AND Cost implications of remedial action should the noise
SOLUTIONS: problem occur with an ATD clearly emphasize the im-
portance of total consideration at design stage to cor-
If a noise level problem occur at commissioning stage,
rect selection.
it is recommended that the following basic procedures
employed to determine if the ATD (air terminal device)
is responsible.
1.8 AIR FLOW MEASUREMENT:
• Shut down in rotation the various plants serving
the space to identify the source that is creating the Instruments for Measurement of Air Flow:
noise. Do not be misled by the possible air imbal- The rotating vane anemometer is usually the most suit-
ance created with in the space, i.e., supply only cre- able instrument available at present to measure air flow
ating noise by air escaping through doors etc. rate at two or more terminals. There are two general
types of this instrument.
• On the noisy system check position of ATD damp-
ers. If the noise level is reduced then damper gen- • The dial-face anemometer which requires the use
erated noise is probably the cause. Solution - con- of a watch. This has the advantage of giving a defi-
sider introducing duct dampers well upstream of the nite value of air velocity based upon the number of
ATD to provide required pressure drop for balanc- revolutions per unit time and is particularly useful
ing. This could involve the use of secondary attenu- for giving accurate comparative valves when mea-
ators downstream of the new damper. suring at terminals where the air velocity pattern is
reasonably uniform and stable.
• If opening and closing the ATD damper does not
result in any significant change of noise level, either • The direct reading anemometer of the electronic
the noise is entering the space through some other type which records the air velocity almost instanta-
path i.e. structure borne vibration, direct transmis- neously. This has a distinct advantage when mea-
sion through walls, ceiling or floor, duct breakout, suring at terminals where there is unstable or non-
etc. or is propagating down the duct from another uniform flow as any instability or random changes of
noise source. velocity are immediately seen and the true mean of
the velocity at a point, and therefore of a number of
• Remove ATD plus associated damper. If the noise points, can be judged. It is also very quick to use.
level reduces then the sources of the problem may Also suitable is the mechanical type of direct read-
well be ATD and damper. But if the noise level in- ing anemometer with vane which rotate but not con-
creases, it is likely that duct borne noise is propagat- tinuously.
ing down the system from some upstream source,
possible main control damper, primary fans, poorly Where a correction chart is supplied with an anemom-
designed duct junctions. However, should investi- eter the correction factors should be applied to the
gation indicate that noise problem is associated measured indicated velocities before comparing these
with the ATD/damper/plenum box combination, then velocities for balancing purpose.
consider remedial measures such as:
AIR FLOW MEASUREMENT FOR DIFFUSERS : • If the anemometer is smaller in diameter than the
• Cones, if adjustable, should be set either all in the width of the annulus then the lower edge of the an-
fully up or in the fully down position. The procedures emometer case should be placed at the outer rim of
of measurement will be same for both supply and the smaller cone, the instrument being held at the
extract diffusers. same angle as described above.
• Measurement can be made with a hood and ane- • The ‘indicated velocity’ is the average value of the
mometer for the diffusers of same type and size and spot measurement. The ‘indicated velocity’ at the
designed to deliver equal rates of air flow. hood outlet is measured.
• Anemometer is held or fixed in the center of the • The ‘design velocity’ is calculated by dividing the
hood outlet while the hood inlet must completely en- design volumetric rate of air flow for the diffuser by
close the diffuser. the gross area of the diffuser discharge.
• The ‘indicated velocity’ at the hood outlet is mea- • Before adopting this method the repeatability of
sured. The ‘design velocity’ is calculated by dividing readings should always be checked by compar-
the design volumetric rate of air flow for the diffuser ing the results obtained by anemometer at a typical
by the hood outlet area. terminal with pitot-static tube readings taken in the
duct serving the terminal.
• Express ‘indicated velocity’ as a percentage of ‘de-
sign velocity’ to give the required ‘indicated percent- • Note that identical results by anemometer and pi-
age of design air flow’. tot-static tube traverse are neither necessary nor to
be expected, but a strict and constant relationship
• Always apply ‘hood factors’ which shall be derived between the results is essential. Express ‘ indicated
by pilot measurement for the appropriate range of velocity’ as a percentage of ‘design velocity’ to give
air flow rates and the indicated percentageof air the required ‘indicated percentage of design air
flow must be corrected by the relevant factor. flow’.
• Where the diffusers are large or designed for dis- AIR FLOW MEASUREMENT FOR LINEAR BAR
similar rates of air flow, a small direct reading an- GRILLES AND SLOT DIFFUSERS:
emometer can sometimes be used to take three or The procedures and methods are same as diffuser as
four spot measurement of indicated velocity at equi- detailed above. But the other alternatives are; the an-
spaced distances about the circumference of the emometer and hood combination or the anemometer
annulus between the intermediate and inner cones. alone where the size of diffuser or slot permits.
The following tests/checks are carried out only after Percentage of Cu = 0.03
surfaces of extrusions are treated chemical/mechani- Percentage of Fe = 0.16 - 0.22
cal pre-treatment according to DIN 17611. Percentage of Mg = 0.47 - 0.57
Percentage of Si = 0.39 - 0.47
• Anodic Film Thickness (AFT) of extrusions is Percentage of Ti = 0.02
checked by Eddy Current which is according to Percentage of Zn = 0.025
DIN 50984 & BS 1615. The AFT thickness is in the Percentage of Cr = 0.03
range of class 15 - 18 micron. Percentage of Mn = 0.03
Other Element % = 0.1
• Sealing Assessment tests for anodized products are Aluminium = Remainder
conducted regularly which are “ANO-Test” accord-
ing to DIN 50949 & BS 1615 and “DRY ABSORP- Finish:
TION Test” according BS 1615 & ISO 2143. The standard finish is mill finish or anodized aluminium
finish. Also wide range powder coated colours to RAL
• Periodic Metallic Graphic (microscopic) examina- colour code are available upon request.
tions are conducted to maintain the quality of an-
odic film and the metallurgy of aluminium.
General:
Linear bar grilles and slot diffusers, which are normally installed in ambient conditions, will expand and contract with
the temperature changes in the conditioned area.
Fig 9. shows the variation in length of the grille for temperature difference. From the above fig the variation will be
maximum 1mm per meter length of the grille for a temperature difference of 50°C, both for heating and cooling ap-
plications.
However alignment strips available with linear bar grilles will accommodate this slight clearance.
Area Factor
2 2
AK =Q AK = Area factor, Ft (m )
VK
VK = Face velocity, fpm, (m/s)
LENGTH 1 in = 25.4 mm
1 m = 3.2808 ft
1 ft = 0.3048 mm
AREA 1 in2 = 645.16 mm2
1 m2 = 10.76 ft2
1 ft2 = 0.0929 m2
VOLUME 1 in3 = 16387 mm3
1 cfm = 4.8 × 10-4 m3/sec
1 ft3 = 0.0283 m3
1 m3/sec = 2083.3 cfm
1 UK gallon (liquid) = 4.546 litre
1 cfm = 0.472 L/s
1 US gallon (liquid) = 3.785 litre
DENSITY 3 3
1 lbf/ft (pcf) = 16.018 kg/m
TEMPERATURE o
F = 9/5oC + 32
o
C = 5/9 (oF - 32)
• ASHRAE, ASHRAE Handbook 1988, • Int-Hout D., and Weed J.B., “Throw:
Equipment, ASHRAE Inc., Atlanta, GA, The Air Distribution Quantifier” ASHRAE
1988. Transactions, Part 1,1988.
• ASHRAE Handbook 2008, HVAC systems • Miller Jr., P.L.,“Room air Distribution
and equipments. Systems: A re- evaluation of design data”
ASHRAE Transactions part 2, 1979.
• Hanzawa H., Melikow A.K., and Fanger
P.O., • Miller Jr. P.L.,“Application criteria for the
“Air flow characteristics in the occupied air diffusion performance index (ADP1)”
zone of ventilated spaces”, ASHRAE ASHRAE Transactions part 2, 1976.
transactions, Part I, pp.524-539, 1987.
• Wang S.K., “Air Conditioning Vol 2”, Hong
• Gorton, R.L., and Sassi, M. M., Kong Polytechnic, Hong Kong, 1987.
“Determination of temperature profiles
and loads in a thermally stratified, air • Wang S.K., Kwok K.W., and Watt S.F.,
conditioning system: part I - Model “Characteristics of a space diffusion system
studies”, ASHRAE transactions, Part II , in an indoor sports stadium” ASHRAE
pp.14-32, 1982. Transactions, part 2B, 1985.