Professional Documents
Culture Documents
Bunner Control
Bunner Control
Bunner Control
B 2010.12.28 Deleted the description of “flame detectors are Wang Xue Zeng Qingmiao Zhang Cuixi
supplied by customer” on page 2 Section 1
A 2010.02.22 FOR REFERENCE Wang Xue Zeng Qingmiao Zhang Cuixi
VIETNAM MACHINERY
INSTALLATIONCORPPORATION (LILAMA)
FICHTNER GmbH & Co. KG
PROJECT TITLE
BOILER ISLAND
CONTRACT No.
180609 / LILAMA-BWBC
DRAWING TITLE
GUIDE SPECIFICATIONS
BURNER CONTROLS
SCALE REV
DOCUMENT No. VA1-BWBC-00100-M-M1A-PHL-0002
B
BOILER INSTRUCTION
B&WB-2028/17.4-M BOILER
50-G14900-0
2010-12-28
PAGE 1 OF 17
INDEX
SECTION SUBJECT PAGE
1 SCOPE 2
2 FUEL-AIR EQUIPMENT 2
3 GENERAL REQUIREMENTS 3
4 OPERATING MODES 3
5 OPERATOR INTERFACE 4
6 FURNACE PURGE AND BOILER MONITOR 4
7 START/STOP SEQUENCES 6
8 OIL LIGHTER CONTROL 7
9 PRIMARY AIR FLOW CONTROL 10
10 SECONDARY AIR FLOW CONTROL 11
11 BURNER LINE SWING VALVE AND SLIDE 12
PLATE GATES ON BURNER VENT AIR PIPE
CONTROL
12 PULVERIZER CONTROL 12
13 FEEDER CQNTROL 13
14 FLAME MONITORING 13
15 COMBUSTION CONTROL INTERFACE 14
SECTION 1:SCOPE
Each boiler is equipped with direct firing system, six (6) ball pulverizers. And each pulverizer
supplies PC for four burners. Each boiler is equipped with twenty four (24) concentrated HALF-
PAX EI-XCL burners, which are located on boiler front arch and rear arch (each arch is arranged
by twelve burners). Each burner is equipped with a set of lighter (oil burner) locating inside the
secondary air sleeve, and each lighter is with pneumatic operated retractable device, which can be
remote controlled. Also each burner is equipped with coal flame detector and oil flame detector.
Boiler windbox consists of burner secondary air (over arch air) windbox and staging air (blew
arch air) windbox, both winboxes are non compartmented (open windbox). Each burner is
associated with a staging air pipe and a vent air nozzle, and each staging air pipe is split into two
staging air nozzles.
From the pulverizer , the pulverized coal is carried by primary or transport air through the coal
pipes to the burners. The PC-air flow enters furnace in two streams after concentrated, one of
them which contains 85%~90% PC and 50% PA enters furnace for igniting and burning through
burner nozzles, the other stream which contains 10%~15% PC and 50% PA enters furnace
through Vent Air nozzles. The primary air flow is measured and controlled on an individual
burner basis, with the primary air temperature being regulated by the mixing of hot and tempering
air flows.
Each pulverizer supplies four dual register burners, and each boiler is equipped with six (6) ball
pulverizers. And Coal line swing valves are located in each burner line to shut-off fuel flow to the
furnace, slide plate gates are located in vent air pipeline to shut-off vent air flow to the furnace.
The dual register burneris a limited turbulence controlled diffusion flame type designed to limit
the amount of air mixed with the fuel at the burner to that required to obtain stable ignition at the
burner throat.The remainder of the combustion air is introduced to the periphery of the burner
where it mixes with the fuel.The dual register burner,as its name implies,has two air
registers which are manually adjusted during initial firing to obtain desired fuel and air mixing in
the primary ignition zone.
Each concentrated dual register burner is equipped with a steam atomizing oil lighter. The
pneumatic operated retractors for the lighters are remotely operated drives.
lighter.The retractors for the lighters are the only remotely operated drives provided on the dual
register burner.
All of the burners supplied by a given pulverizer are enclosed in a separate windbox
compartmentwith the secondary air flow to each windbox compartment being individually
measured and controlled by dampers located at the inlet to the compartment.This allows the fuel
and air flow to each pulverizer group to be independently controlled, which is desirable from an
ignition and slagging standpoint.This also assists in the light-off of a cold unit,since the fuel-
air ratio at the burners being fired can be controlled independently of the continuous purge air
flow being admitted through idle compartments.
PAGE 3 OF 17
The burner control system shall incorporate a continuous purge of the furnace to insure that the
boiler is free of any accumulation of combustibles for light-off and that the boiler will remain so
during operation.The burner control system shall also supervise the operation of the fuel-air
equipment associated with the pulverizer.It shall accept operator commands and if the required
permissives are met,perform the required operation. Equipment shall be continuously
monitored and any over deviation shall be alarmed while the system either corrects the deviation
or shuts down equipment as necessary to avoid hazardous furnace conditions or equipment
damage.
The system shall monitor the operation of the fuel equipment and if the equipment fails to
respond to commands from the burner control system,the equipment tripped status shall be set.
Indications shall be provided to allow the operator to determine the equipment level which
initiated a trip of fuel equipment. Tripped equipment shall be successfully shutdown before reset
of the trip is permitted. The status of the fuel-air equipment shall be displayed to the operator at
all times.
The burner control system shall interface with a master fuel trip system.It also shall interface
with the analog fuel control system to position and monitor devices for start-up and shutdown
which are normally modulated during on-line operation. The burner control system shall be
designed to operate reliably and to minimize the number of false trips which occur in order to
establish operator confidence in this system, such that the system will be maintained in service
and available to respond if hazardous conditions develop.
The term pulverizer group as used in this guide specification refers to the pulverizer, its
associated primary air systems, feeder, swing valves and burners(contains coal nozzle, vent air
nozzle and staging air nozzle). For control purposes, burners(contains coal nozzle, vent air nozzle
and staging air nozzle) associated with the pulverizer shall be divided as equally as possible into
two burner groups. Ball pulverizer is adopted in this project, half mill is associated with two
burners which are in a same burner group, the two burner groups associated with one pulverizer
are diagonally opposed, which are located separately on front arch and rear arch and are
symmetrical about the furnace centre line .
In the manual sequence control mode, the operator has the responsibility for initiating each step
in the start and stop sequences at the proper time and for positioning the modulating devices
controlled by the analog fuel and air control system.This system shall monitor the operator’s
progress and inhibit him from departing from the proper operating sequences.The manual
control mode does not include sequence timing functions other than for lighter and furnace purge
functions.The manual mode of control includes the basic supervisory interlocks,trips and
monitoring functions including proper positioning of functions controlled by the analog system.
In the automatic sequence control mode,the burner control system shall automatically place the
pulverizer group in service,or remove it from service on a single operator initiation to start or
stop that pulverizer group.In the automatic mode,start/stop sequences,including timing
between the steps,are superimposed over the manual mode. As such,all of the interlocking
and tripping functions that are part of the manual mode shall also be an integral part of the
automatic mode. A system with automatic sequence control shall,be capable of being
transferred between the automatic and manual modes at any time.
PAGE 4 OF 17
The furnace purge control shall incorporate a continuous purge of the furnace to insure that the
boiler is free of any accumulation of combustibles for light-off and that the boiler will remain so
during operation.
Prior to light-off, the air and gas passages of the boiler shall be purged of any combustible that
may have accumulated.This purging shall be accomplished by maintaining a minimum of 30
percent air flow through all windboxes with all sources of fuel to the furnace shut-off for at least
five minutes. Purge permissives shall include,but are not limited to:
1. All swing valves closed.
2. All pulverizers stopped.
3. All feeders stopped.
4. All primary air control dampers closed.
5. All lighter valves closed.
6. Lighter header trip valves closed.
7. All secondary air heaters running.
8. At least one FD and ID fan running.
9. No primary air fans running.
10. Purge air flow established through all windboxes.
11. Boiler air flow greater than 30 percent.
PAGE 5 OF 17
Accumulation of purge credit shall start automatically when the purge permissives are
established. Once the purge is complete, a continuous purge with greater than 30 percent boiler
airflow must be maintained. The boiler airflow shall be monitored, and the start of any additional
fuel equipment shall be blocked until air flow has been restored.
A continuous purge of one minute with greater than 30 percent air flow shall occur after the
start of any feeder, the trip of any burner group, the trip of any pulverizer,the trip of any lighter
before the feeder has been running for greater than 20 seconds,or the occurrence of a pulverizer
group emergency trip, before any additional fuel equipment may be started.
Completion of the furnace purge shall allow reset of the master fuel trip. A furnace purge shall
be required on a master fuel trip,no FD fans operating, or when all lighters and pulverizers are
stopped or tripped after main fuel firing has been initiated. Furnace purge required shall trip the
master fuel trip, the lighter oil header trip valve and all fuel equipment in the pulverizer groups.
The boiler monitor shall prevent starting any fuel equipment if the furnace firing permissives
are not met.The furnace firing permissives shall include,but are not limited to:
1. Master fuel trip and oil fuel trip not present.
2. Continuous purge requirements met.
3. All pulverizer group equipment trips reset.
4. Lighter header valve open.
5. Lighter header pressure greater than minimum and less than maximum.
6. Flame detector cooling air adequate.
7. Lighter atomizing medium greater than minimum.
The furnace purge control insert shall provide indications to the operator of the status of the
purge and firing permissives and the progress of the furnace purge. These shall include, but are
not limited to:
1. Purge required.
2. Purge in progress.
3. Purge complete.
4. Status of each individual purge permissive.
5. Status of each individual firing permissive.
6. Purge time count down.
7. Purge failure and the cause first-out.
A boiler first-out annunciator shall be included to indicate to the operator the initiating
cause of a boiler trip. Points to be included in the first-out display shall include, but are not
limited to:
1. Master fuel trip.
2. Turbine trip.
3. FD fan trip.
4. ID fan trip.
PAGE 6 OF 17
The burner control system shall start and stop the pulverizer group following fixed
sequences.The system shall be capable of transferring between the start-up and shutdown
sequences at any time.
The recommended start-up sequence is:
1. Establish burner air flow (burner cylindrical sliding damper) at light-off through the
manipulation of the analog air flow control subloop.
2. Start lighters.
3. Start primary air flow.
a. For common PA fan release analog system to open control damper slowly
b. For individual PA fans start PA fan and time delay release of analog system to open
control damper slowly.
4. Open burner line swing valves and slide plate gate on vent air pipe to establish primary
air flow through the burner lines.
5. Hold to allow primary air flow to stabilize at its light—off value(approximately 10
seconds).
6. Start pulverizer(follow the start sequence as pulverizer vendor required).
7. Hold for pulverizer to come up to speed(approximately 10 seconds).
8. Start feeder (as required by pulverizer and feeder vendor).
9. Release pulverizer outlet fuel—air temperature control to automatic.
10. Hold for initial flame stabilization period (approximately 3 minutes).
11. Release secondary air flow control to automatic (release control damper located on
general duct of both burner secondary air and staging air to automatic, set burner
cylindrical sliding damper at “firing”, staging air control damper full open).
12. Release pulverizer demand to automatic control.
13. Hold for final flame stabilization period (approximately 5 minutes).
14. Stop lighters after stable combustion has been established and secondary air temperature
is above 200℃.
PAGE 7 OF 17 7 FOR 21
Each burner is equipped with a Class 1 lighter. The lighters associated with a pulverizer
group are divided into two lighter groups corresponding to the two burner groups. Each lighter
group will be controlled with a separate electro-pneumatic lighter control package. All of the
lighters associated with a pulverizer group shall normally be started or stopped at the same time.
However, each lighter group shall be independently monitored and tripped. Provisions shall be
included to allow sequential starting of the lighter groups to reduce lighter header pressure upsets
and to allow restarting of a tripped lighter group without having to shutdown an operating group.
The burner control shall provide a start lighter group command upon which the electro-
pneumatic control package will:
PAGE 8 OF 17
The following outputs from the electro-pneumatic control package are available for use by
the burner control system:
1. Lighters inserted.
2. Purge valve open.
3. Lighter oils valves open.
A lighter group shall be tripped if
1. Boiler tripped.
2. Pulverizer group emergency trip initiated by operator.
3. Lighter fails to start when commanded.
4. Lighter oil valve not open after trial for ignition.
5. Lighter flame not detected after trial for ignition.
Lighter group trip sequence is shown in Figure 3.
Maintained lighter selection on a pulverizer group basis shall be provided for any system
which includes automatic sequence control. This capability shall allow the operator to start or
stop the lighters any time firing is permitted in the boiler, provided the automatic sequence does
not require the lighters in service at that time. If the lighter is in service, selection of maintained
lighters shall prevent shutdown of the lighters by the automatic sequence control.
Indications shall be provided to the operator on the status of the lighters.These shall
include,but are not limited to:
1. Lighters ready to start.
2. Lighters maintained.
3. Lighter group successfully lit.
4. Lighter group successfully shutdown.
5. Lighter group tripped.
6. Lighter group cleaning.
7. Lighter group trouble due to unsuccessful shutdown or shutdown without cleaning.
PAGE 10 OF 17
With common primary air fans, the burner control shall provide commands to open or close
the pulverizer group primary air flow control damper. This damper is normally controlled by the
combustion control system. With individual primary air fans, the burner control system will start
and stop these fans.
Permissives to start the primary air flow on a pulverizer group shall include the following:
1. Furnace firing permissives met.
2. At least one primary air fan and one primary air heater(s) running.
3. Cold air damper open and hot air damper closed.
4. At least one lighter group started.
5. Pulverizer seal air differential pressure above minimum.
Primary air flow shall be stopped if the boiler is tripped. The primary air flow shall be tripped
if flame monitoring is not in service and both lighter groups are not in service, primary air flow is
less than minimum, or the pulverizer group is tripped.
Minimum primary air flow is dependent on the specific P.C. system or contract. System
requirements include sufficient burner line and pulverizer throat velocities. Specific contract
requirements are determined by component design and the pulverizer/burner line. To protect
against fires and explosions,It is suggested that a 20 second, time-delayed trip occur for
primary air flows lower than 10% below the minimum, and an instantaneous trip occur for
primary air flows lower than 15%below the minimum.
The hot and cold primary air control dampers are normally controlled by the combustion
control system to maintain pulverizer outlet coal-air temperature. The burner control system shall
provide commands to open and close the hot and cold air damper. The hot air damper shall be
closed and the cold air damper opened whenever the feeder is not operating.
Indications provided to the operator on the status of the primary air flow control shall
include:
1. Primary air flow started.
2. Primary air flow stopped.
3. Primary air flow tripped.
4. Primary air flow low.
5. Hot air damper closed and cold air damper open.
6. Pulverizer temperature control released to automatic.
PAGE 11 OF 17
Secondary air flow control shall normally be the responsibility of the combustion control
system. The burner control system shall provide outputs to the combustion control system to
establish the air flows required for furnace purge and pulverizer start-up and shutdown. During
operation at lower loads the burner control system shall avoid calling for operating burner air
flows which could reduce total boiler air flow below its minimum value. On a master fuel
trip,the burner control system shall avoid any conflict with the normal analog control of
secondary air flow.
Indications provided to the operator on the status of the secondary air flow control shall
include:
1. Secondary air flow control released to automatic (control damper on general duct of
burner secondary air and staging air control damper).
2. Secondary air flow at light-off (set burner cylindrical sliding damper at “light-off”,
staging air control damper at “firing”).
3. Secondary air flow released to cooling (burner cylindrical sliding damper and staging air
control damper).
PAGE 12 OF 17
SECTION 11 : BURNER LINE SWING VALVE AND SLIDE PLATE GATE ON VENT
AIR PIPE
The burners associated with a pulverizer group shall be divided into two burner groups. Each
burner is equipped with a swing valve and a slide plate gate on vent air pipe. Normally, it is not
recommended or should be avoided that only one end of the mill is operating. All of the swing
valves associated with a pulvenzer group and the slide plate gates on vent air pipe of relevant
burners shall normally be opened or closed at the same time. When the pulverizer is only with
one end operating, the swing valves and slide plate gate on vent air pipe in each burner group
shall be opened or closed at the same time. Provision shall be included to allow reopening of
swing valves and slide plate gate on vent air pipe on a tripped burner group if light-off conditions
are established.
A burner group's swing valves and slide plate gates on vent air pipe shall be closed if the boiler
is tripped, primary air flow is stopped or commanded to stop, the burner group is tripped, or
pulverizer group emergency stop is initiated.
Indications shall be provided to the operator on the status of the swing valves and slide plate
gates on vent air pipe. These shall include, but are not limited to:
1. Burner group swing valves and slide plate gates on vent air pipes open.
2. Burner group swing valves and slide plate gates on vent air pipes closed.
3. Burner group tripped.
Swing valve and slide plate gate on vent air pipe trips are shown in Figure 3.
Means shall be provided to disable individual burner line swing valves.
The pulverizer may be started if any swing valve is open, the pulverizer lube oil pump is
running and pulverizer lube oil pressure is greater than minimum. The pulverizer shall be stopped
if the boiler is tripped, the pulverizer group emergency stop is initiated or the primary air flow is
stopped or commanded to stop. The pulverizer will be tripped if all swing valves go closed or the
lube oil pump stops or lube oil pressure goes below minimum.
Indications provided to the operator on pulverizer status shall include:
1. Pulverizer running.
2. Pulverizer stopped.
3. Pulverizer tripped.
4. Pulverizer lube oil pump running.
5. Pulverizer lube oil pressure low.
6. Pulverizer seal air differential pressure low.
7. Other indications required by vendor.
Pulverizer trips are shown in Figure 3.
PAGE 13 OF 17
The feeder may be started if the coal feeder inlet and outlet gates are open, all enabled swing
valves on at least one end open, furnace firing permissives are met, coal is detected at the feeder
inlet , the feeder outlet is not plugged or other requirements from vendor. The feeder shall be
stopped if the boiler is tripped or the pulverizer is stopped or commanded to stop. The feeder
shall be tripped if the feeder outlet is plugged, feeder outlet gate open, either burner group is
tripped or has 2 or more swing valves closed, primary air flow is below minimum for 20 seconds
or feeder inlet gate not closed and no coal detected at the feeder inlet for 2 seconds or no coal
detected on the feeder belt for 20 seconds with the lighters not in service.
Indications provided to the operator on the status of the feeder control shall include:
1. Feeder running.
2. Feeder stopped.
3. Feeder tripped.
4. Feeder inlet gate not open.
5. Feeder outlet gate not open.
6. No coal detected at feeder inlet.
Coal feeder trips are shown in Figure 3.
The burner control system shall minimize the possibility of developing hazardous furnace
conditions by shutting down fuel equipment on loss of ignition. It shall also minimize the number
of false trips which occur.
With a Class 1 lighter on each burner, it is necessary to discriminate between lighter and coal
flames at the burner. Therefore, two flame detectors are required per burner. These two detectors
shall detect respectively the lighter and coal flames at that burner reliably and shall discriminate
between flames at its burner and other burners in the furnace.
The burner control system shall divide the burners served by a pulverizer into two burner
groups with no trip action being taken on a single detector in either burner group showing no
flame, but it should alarm to remind the operator to deal with this. If two detectors in a burner
group show no flame, that burner group and the feeder shall be tripped with the other burner
group (half mill) served by the same pulverizer running (half mill running is not recommended
for long term). On loss of flame detection on two burners in the second burner group,the
pulverizer shall be stopped and fuel flow to the pulverizer group terminated by closing all swing
valves, and the relevant slide plate gates on vent air pipe should be closed too.
Before admitting main fuel to a burner, an ignition source must be present at the burner. The
burner control system shall require flame from the lighters be detected at all burners of at least
one burner group before primary air flow, pulverizer and feeder serving those burners may be
started. Once the feeder is started, the loss of flame on two burners in a group is necessary to trip
the lighters associated with that burner group.
PAGE 14 OF 17
A flame detector maintenance mode shall be included to allow work to be done on the flame
detectors without creating nuisance trips or having to completely defeat the protection provided
by the system. In this mode, a burner group shall not be tripped unless all detectors in the group
show no flame. This mode shall be selected by a switch located in the logic cabinets.
Flame monitoring requirements are shown in the trip sequence diagram shown in Figure 3.
Indication of the status of each flame detector shall be provided to the operator.
The burner control system shall interface with the combustion control system to position
devices for start-up and shutdown which are normally modulated during on-line operation. This
interface shall be designed such that the loss of power in one system does not interfere with the
proper operation of the other system.
Signals from the burner control system to the combustion control system shall include, but
are not limited to:
1. Close primary air control damper.
2. Allow secondary air flow (burner cylindrical sliding damper) to burner cooling value.
3. Set secondary air flow (burner cylindrical sliding damper) to light-off value.
4. Close hot air damper and open cold air damper.
5. Set pulverizer demand to light-off value.
Signals from the combustion control system to the burner control system shall include, but
are not limited to:
1. Boiler air flow greater than 30%.
2. Either PA fan running.
3. Unit load greater than 35%.
4. Unit load less than 30%.
5. Unit load greater than 60%.
6. Pulverizer demand at light-off.
7. Primary air control damper closed.
8. Secondary air temperature greater than 200℃.
9. Pulverizer outlet temperature less than 60℃.
10. Secondary air flow at light-off.
11. Secondary air flow at cooling.
12. Primary air flow greater than or equal to light-off.
PAGE 15OF 17
FEEDER RUNNING
SET SECONDARY AIR FLOW SECONDARY AIR FLOW AT LIGHT-OFF START FEEDER
FEEDBACK
DEMAND TO LIGHT-OFF
FEEDBACK
YES
YES FEEDBACK
ALL SWING VALVES AND SLIDE PLATE GATES ON YES
BURNER VENT AIR PIPE IN AT LEAST ONE BURNER
GROUPS OPEN
START SEQUENCE FOR NON COMPARTMENTED
OPEN SWING VALVES FEEDBACK
STOP LIGHTERS WINDBOX
AND SLIDE PLATE PULVERIZED COAL BURNER CONTROL SYSTEM
GATES ON BURNER Figure 1
VENT AIR PIPE
PAGE 16 OF 17
YES YES
PULVERIZER DEMAND AT LIGHT-OFF CLEANING TIME < 1 MINUTE
PULVERIZER OUTLET TEMP. < 60 ℃
PULVERIZER DEMAND TO LIHGT-OFF
HOLD FOR FINAL PULVERIZER COOLING
FEEDBACK
FEEDBACK
YES
HOT AIR DAMPER CLOSED YES
COLD AIR DAMPER OPEN ALL SWING VALVES AND SLIDE PLATE
CLOSE HOT AIR DAMPER AND OPEN
AT COOLING VALUE
TRIP SEQUENCE FOR NON COMPARTMENTED WINDBOS PULVERIZED COAL BURNER CONTROL SYSTEM
PA FLOW < MINIMUM FOR
MASTER FUEL TRIP LIGHTERS NOT IN SERVICE
BOTH BURNER GROUPS 20 SEC
(BY OPERATOR) AND FEEDER STOPPED
TRIPPED
20 SEC
EITHER BURNER GROUP
BOILER
PA FLOW VELOCITY<85% OF TRIPPED
ALL PULVERIZERS TRIP
MINIMUM ALL SWING VALVES
STOPPED OR TRIPPED
O CLOSED
PA FLOW START MEMORIZED TRIP
TRIP PA PULV STOPPED OR
R PULVERIZER
& PA CONTROL DAMPER PA FLOW STOPED OR COMMANDED TO STOP
FLOW
ALL FD FANS CLOSED O
COMMANDED TO STOP
STOPPED O R FEEDER INLET GATE NOT
TO OTHER PA FLOW STOP MEMORIZED
R PULV LUBE OIL PRESSURE CLOSED AND NO COAL AT
MILL & PA CONTROL DAMPER NOT
LOW FOR 3 SEC FEEDER INLET FOR 2 SEC
GROUPS CLOSED
Figure 3