AREA WISE DESIGN PHILOSOPHY

TYPE OF
Area FLOOR LIGHT No. of zones Floor Scheme STRATEGIES Field Devices Occupancy
(Receiver devices (QSMs) are
not counted here

Please note that apart from the various below details all the areas can be controlled and monitored from the LMS GUI software. Also, the time limits of the sensors can be set from area to area based on client requi
the coverage, if required. Further, high end trim can be done at any %, 80% is indiacted just as a case.

* OCCUPANCY
Lights automatically turn on to 80% (or
* DAYLIGHT HARVESTING
All typical floors and any depending upon lux level reqd) when
AS PER DRAWINGS *TIMECLOCK BASED/*SCHEDULING OCCUPANCY SENSOR, DAYLIGHT
Typical open office area non typical floors open DALI DIMMABLE the user enters the Area and turns off 5
*HIGH END SENSORS
office areas minutes (or any minute more than 1)
TRIMMING *FAVORITE
after the area has been vacated.
SCENE SELECTION

All typical floors and


non typical floors open Since corridor has no
Corridors office areas. Main Swithcing AS PER DRAWINGS lights, the work station - - -
Corridors which are lights will provide enough
parallel to the facade lighting for this area
are only considered.

Wash rooms NOT IN SCOPE

* OCCUPANCY Lights automatically turn on when the


DALI DIMMABLE *TIMECLOCK user enters the room and turns off 15
Meeting rooms (> 4 pax) , AS PER DRAWINGS
All floors + Motrised BASED SCHEDULING Occ sensor, keypads minutes after the room has been
Conference rooms etc.
shades *HIGH END TRIMMING vacated. Various permutaion can be
*FAVORITE SCENE SELECTION worked out with BMS integartion.

AS PER DRAWINGS *TIMECLOCK BASED


Standard Rooms All floors DALI DIMMABLE -
SCHEDULING
*HIGH END TRIMMING
Elevator Lobby NOT IN SCOPE

* OCCUPANCY * DAYLIGHT
Lights automatically turn on to 80% when
HARVESTING
RECEPTION, INTERVIEW All floors DALI DIMMABLE AS PER DRAWINGS OCCUPANCY SENSOR, DAYLIGHT the user enters the area and turns off 5
*TIMECLOCK BASED
ROOMS SENSORS minutes after the room has been
SCHEDULING
vacated.
*HIGH END TRIMMING
HY

Dimming/Switching Daylighting Control Time Clock

set from area to area based on client requirement. (minimum 1 min.). Apart from this sensor masking would be done to limit

Based on occupancy, Up lights at


The user can manually intervene
workstation will be controlled by As per office timing light control can be
selection, from on /off manual
Dimmed lights are controlled in this area daylight sensor for target lux level and preset, - Scheduling can be decided by
dimmingl and one favorite scene can
down lights will be turned on by user client.
be set from software
for additional light level requirement

- NA - -

By manual intervention various scenes


As per the kind of occupation and type of
Dimmed lights are controlled in this area NA can be selected such as PPT, Movie,
meeting, pedefines scenes can be set.
Meeting etc. with 4-5 buttons keypad

- NA - -

Dimmed lights are controlled in this area NA - As per office timing light control can be
preset