6000TM

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 40

Document: MAN-6000 Series

Data: 04/99
Part No. 276-947

i
TABLE OF CONTENTS
1. SYSTEM OVERVIEW................................................................................................................................................................................................. 1
1.1. Scope of this Document................................................................................................................................................................................... 1
1.2. General Description.......................................................................................................................................................................................... 1
1.3. Information Displays......................................................................................................................................................................................... 1
2. FUNCTIONAL DESCRIPTION 6000 SERIES CONTROL SYSTEMS........................................................................................................................ 3
2.1 System Overview............................................................................................................................................................................................. 3
2.2 Generating set Parameter Displays.................................................................................................................................................................. 3
2.3 Control Features............................................................................................................................................................................................... 3
2.4 Control Functions............................................................................................................................................................................................. 4
2.5. Protective Features.......................................................................................................................................................................................... 5
2.6 Standard Auxilliary Equipment......................................................................................................................................................................... 5
2.7 Standard Options............................................................................................................................................................................................. 5
2.8. Communications Options................................................................................................................................................................................. 6
2.9 Hardware.......................................................................................................................................................................................................... 6
3. CONFIGURATION - OUTLINE OF SETPOINTS........................................................................................................................................................ 9
3.1 Configuration Menu.......................................................................................................................................................................................... 9
3.2 Shutdowns, Alarms........................................................................................................................................................................................ 10
3.3 Engine Control................................................................................................................................................................................................ 13
3.4 Synchroscope................................................................................................................................................................................................ 13
3.5 Real Load Control........................................................................................................................................................................................... 14
3.6 Reactive Load Control.................................................................................................................................................................................... 15
3.7 Process Control.............................................................................................................................................................................................. 16
3.8 Calibration...................................................................................................................................................................................................... 16
3.9 NetComm Dropouts........................................................................................................................................................................................ 18
3.10 6100 - Single Generating set, Automatic Mains Failure.................................................................................................................................. 18
4. RUN / GENERATING SET MANUAL RUN.............................................................................................................................................................. 19
4.1 Functional Description.................................................................................................................................................................................... 19
4.2. Prime Power Variant - Normal Switch Positions............................................................................................................................................. 19
4.3. AMF Variant - Normal Switch Positions.......................................................................................................................................................... 20
5. 6300 - AUTOMATIC SYNCHRONISING OF ONE GENERATING SET WITH MAINS............................................................................................. 21
5.1 Functional Description.................................................................................................................................................................................... 21
5.2. Base Load Operation...................................................................................................................................................................................... 21
5.3. Base Load Variant - Normal Switch Positions................................................................................................................................................ 21
5.4. Peak Shaving Operation................................................................................................................................................................................. 22
5.5. Peak Shaving Variant - Normal Switch Positions........................................................................................................................................... 22
5.6. Soft Transfer Variant - Normal operation:....................................................................................................................................................... 23
5.7. Soft Transfer Variant - Normal Switch Positions............................................................................................................................................. 23
6. AUTOMATIC SYNCHRONISING OF MULTIPLE GENERATING SETS WITH MAINS............................................................................................ 24
6.1. Functional Description.................................................................................................................................................................................... 24
6.2. Base Load Operation...................................................................................................................................................................................... 24
6.3. Base Load Variant - Normal Switch Positions................................................................................................................................................ 25
6.4 Peak Shaving Operation................................................................................................................................................................................. 25
6.5 Peak Shaving Variant - Normal Switch Positions........................................................................................................................................... 25
6.6 Soft Transfer Variant - Normal operation:....................................................................................................................................................... 26
6.7 Soft Transfer Variant - Normal Switch Positions............................................................................................................................................. 26
7. ALARM / EVENT INDICATION AND LOGGING....................................................................................................................................................... 27
8. REMOTE CONTROL AND MONITORING VIA A PC:.............................................................................................................................................. 27
8.1 System Outline................................................................................................................................................................................................ 28
8.2 Functional Description..................................................................................................................................................................................... 28
8.3 Hardware Specifications.................................................................................................................................................................................. 28
8.4 Equipment Supplied With Each Option:........................................................................................................................................................... 29
9. INITIAL STARTUP AND COMMISSIONING............................................................................................................................................................. 29
9.1 Test Procedure for Single Generating set Systems......................................................................................................................................... 29
10. TROUBLESHOOTING.............................................................................................................................................................................................. 32
10.1 Control Hardware and I/O................................................................................................................................................................................ 32
10.2 Engine Control / Sensing Parameters.............................................................................................................................................................. 32
10.3 Synchronisation............................................................................................................................................................................................... 33
10.4 Breaker Close / Open Control.......................................................................................................................................................................... 33
10.5 Real Load Control............................................................................................................................................................................................ 34
10.6 Reactive Load Control..................................................................................................................................................................................... 34
10.7 Sequencing...................................................................................................................................................................................................... 35
10.8 Mains / Bus Sensing........................................................................................................................................................................................ 35
10.9 Communications.............................................................................................................................................................................................. 35
11. DEFINITION OF TERMS........................................................................................................................................................................................... 36

ii
iii
1. System Overview

1.1. Scope of this Document


This document is intended for use by any suitably qualified
person wishing to obtain technical information regarding the
configuration and setup of any of FG Wilson’s range of 6000
series control systems. It may also be used reference
document for those in the Sales, Engineering and Product
Support departments within FG Wilson. The information
contained herein is sufficiently detailed as to give the reader
insight into the operating modes of the 6000 Series Control
System and is designed to replace the Woodward GCP-1
manual for any of the FG Wilson range.
1.2. General Description
The 6000 Series Control System employs the 6000 Controller
as its core in addition to some ancillary components to realise
the range of 6000 Series Control Panels offered. Depending on
the requirements of the installation, the 6000 Series Control
System may be configured to operate in one of several modes:
6100, 6200 or 6300. It may also be configured to operate in the
6400 mode in conjunction with an external master control
section.
The control panel provides a means of starting and stopping the
generating set, monitoring its operation and output, and
automatically shutting down the set in the event of a critical
condition arising such as low oil pressure or high engine coolant Figure 1: Diagram of Typical Control Panels
temperature. 10. “STATUS PAD”:
Figure 1 shows typical diagrams of the 6000 Series Control A pad to move cursor into the status screen.
Panel. Addition of optional equipment will add items to the panel 11. VOLTS RAISE / LOWER SWITCH:
so the panel fitted on the generating set may be slightly different A switch to manually control the generator voltage
from the one shown. The following descriptions explain the (optional in 6100 Mode).
function of each item on both the panel and controller and each
display screen menu on the panels: 12. SPEED RAISE / LOWER SWITCH:
1. ALARM LAMP: This switch manually controls the engine speed (optional
in 6100 Mode).
Fault lamp that illuminates to indicate that the protective
circuitry has sensed a fault condition. The lamp flashes 13. EMERGENCY STOP PUSHBUTTON:
on an ALARM condition and lights continuously on a A red lock-down pushbutton that immediately shuts down
SHUTDOWN condition. The specific nature of the fault is the generating set and will inhibit start until the pushbutton
detailed in the ALARM / EVENT LOG menu on the has been released by turning it clockwise.
STATUS screen. 14. CONTROL SWITCH:
2. ALARM RESET: A four position switch that provides a means of controlling
By pressing this pad the audible alarm is reset. Specific the generating set mode and function.
faults are reset by pressing the ALARM RESET pad when Position "1" - Off
in the ALARM / EVENT LOG menu on the STATUS Generating set is stopped and automatic starting is
screen. disabled.
3. ESC: Press this pad to exit from any menu. Position "2" - Auto
4. COMMIT: This is the normal position for automatic start up.
Use this pad to enter any menu or amended settings Position “3” - Test
(subject to security clearance). Depending on exact configuration the generating set starts
5. “UP PAD”: and runs off load.
A pad to step upwards through the menu items or to Position “4” - Run
increase numerical values of parameters (subject to Depending on exact configuration the generating set starts
security clearance). and runs on load.
6. “DOWN PAD”: 15. AUDIBLE ALARM:
A pad to step downwards through the menu items or to Buzzer that sounds on sensing of a fault condition
decrease numerical values of parameters (subject to depending on fault handling description.
security clearance). 16. BREAKER / CONTACTOR CLOSED:
7. “LEFT PAD”: Light to indicate generator breaker / contactor closed.
A pad to move cursor to the left on numerical parameters 1.3. Information Displays
(subject to security clearance).
8. “RIGHT PAD”: The 6000 Series Control Panel has two 4 line alphanumeric
LCD displays. The lines of information displayed on these
A pad to move cursor to the right on numerical parameters screens is split into two sections. All four lines of the upper
(subject to security clearance). display and the top two lines of the lower display make up the
9. “TUNEABLE PAD”: first section, outlined on the front panel in blue. The bottom two
A pad to move cursor into the tuneable screen. lines of the lower display make up the second section, outlined
on the front panel in white. The white section is the tunables
section where all tuning of setpoints is carried out. The blue
section is used to display all status information.
All information on the status of the generating set is subgrouped
into the various display screens listed below:

iii
• Control Overview - 3 x Phase kVar

• Engine Overview - 3 x Phase kVA

• Generator Overview #1 A B C
V 221 220 220
• Generator Phases A 250 248 251
• Synchroscope KW 58.2 58.2 58.2

• Alarm/Event Log Kvar 20.0 19.0 22.0


• I/O Status Kva 60.6 60.6 60.6

• Sequencing - Slip Frequency


Control Overview Screen Layout - Phase Angle Difference
- Unit Number - Voltage Differential
- Engine Status - Mains/Bus PT Selection
- Mains/Bus Volts Status - Dead Bus (Yes/No)
- Generator Output Status - Synchroniser Status
- Mode of Operation - Generator Voltage (A: )
- Control Status - Mains/Bus Voltage (U: )
- List of All Available Units SLIP PHASE VOLTS
**** **** ****
- Network Priorities of All Units on the Network MAINS/BUS: MAINS
UNIT 1 ALARMS 0 DEAD BUS: NO
ENGINE: OFF
MAINS ~ GEN - (Synchroniser status) IN SYNC
AUTO OFF A: 381 U: 380
Alarm/Event Log Screen Layout
UNIT NO: 1 2 3
PRTY: 1 2 3 - Number of Unacknowledged Faults
Engine Overview Screen Layout - Listing of up to Eight Most Recent Faults
- Engine Coolant Temperature UNACK FAULTS : 0
Faults Listing:
- Engine Oil Pressure OVERSPEED
- Battery Voltage 26-9 13:01

- Time LOW OIL PRESSURE


28-9 11:59 1.5
- Date
- Engine RPM I/O Status Screen Layout
- Generating set kW-Hrs - Status of Discrete Inputs 1-12 (‘*’ Denotes Active I/P)
- Generating set Run Time - Status of Discrete Output 1-12 (‘*’ Denotes Active O/P)
H2O OIL BATT - Volts Bias Output
67C 4.0B 27.9V
TIME DATE RPM - Speed Bias Output
12:00 26 09 1500
DI: 1 2 3 4 5 6 7 8 9 0 1 2
* * *
KW-HRS RUN TIME
DO: 1 2 3 4 5 6 7 8 9 0 1 2
831 25
* * *
Generator Overview Screen Layout
Volts Bias : 0
- 3 x Phase/Phase Volts Speed Bias : 0
- 3 x Phase Currents Sequencing Screen Layout
- Generator Power Factor - List of All Available Units
- Generator kW - List of All Running Units
- Load Status - Network Priorities of All Units on the Network
#1 A B C
V 381 379 380 - Unit Number of the Designated Master
A 250 248 251 - Address of Next Unit to be Sequenced On
Hz 50.0 kW 174.6
- Address of Next Unit to be Sequenced Off
PF 1.00 LAGGING
Generator Phases Screen Layout
0.96 (Load Control status) UNIT 1 2 3
- 3 x Phase/Neutral Volts OPER X X
PRTY 1 2 3
- 3 x Phase Currents MASTER UNIT 1
- 3 x Phase kW
NEXT ON: 3
NEXT OFF: 2
iii
Automatic Mains Failure Control (handled externally in 6100 and
6200 Modes)
2. Functional Description 6000 Series Control Systems Alternator Output / Load Control
2.1 System Overview Import/Export Control (6300 Mode only)
The 6000 Series control system incorporates a microprocessor Automatic Proportional Real and Reactive Load Sharing (6200
based complete load control and engine management system and 6400 Modes)
and carries out all the functions necessary for engine control,
synchronising, real (kW) control, reactive (kVAR) control and Automatic Soft Load Ramping Facility (6200, 6300 and 6400
automatic generator sequencing. Protection is provided by the Modes)
control system against various fault conditions. VAR or Power Factor Load Control in Mains Parallel Operation
To simplify the variations in control capability the most common (6300 and 6400 Modes)
operating modes have been designated as follows:- Externally Adjustable VAR/PF Reference
6100 - Automatic mains failure (no paralleling). Externally Adjustable Baseload/Process reference
6200 - Automatic synchronising of multiple generating sets (up Soft Load Ramping
to 8 sets).
Soft load Transfer and Re-transfer Control (6300 and 6400
6300 - Automatic synchronising of one generating set with Modes)
mains (baseload, peak lopping and soft transfer).
Manual Voltage Control Facility (depends on configuration)
6400 - Automatic synchronising of multiple generating sets (up
to eight) with the mains (baseload and peak lopping). Manual Frequency Control Capability (depends on
configuration)
2.2 Generating Set Parameter Displays
Synchronising
AC Voltage Phase/Phase and Phase/Neutral
Automatic Phase Match Synchronisation
AC Phase Current
3-Mode operation (Run, Permissive and Check)
Output Frequency
Automatic Voltage Matching
Power Factor (Cos Phi)
Dead Bus Closing
Total and Per Phase kW
Synch Timer
Per Phase kVAr
Reclose Attempt Timer
Total and Per Phase kVA
Manual Synchronisation Capability (depends on configuration)
Total kWh to Date
Mains Sensing
% Voltage Difference between Bus and Generator (Single
Phase/Neutral) Over / Under Voltage
Bus/Generator Phase Angle Difference Over / Under Frequency
Bus/Generator Frequency Slip Load Surge Detection
Generator Run Time Programmable Loss of Mains Detection
Engine Coolant Temperature Loss of Mains Action Delay Timer
Engine Lube Oil Pressure Programmable Mains Stable Delay
DC Voltage Sequencing (6200 and 6400 Modes)
Single Phase/Neutral AC Bus Voltage Each unit in the system has an assigned priority
Generator AC Voltage within limits indication Master (Highest Priority Unit) sequences units on / off line as
Bus AC Voltage within limits indication required

2.3 Control Features Higher priority units are sequenced on in order of priority;
sequenced off in reverse of priority
Engine Control
‘Max System Load’ and ‘Min System Load’ setpoints determine
OFF/AUTO/TEST/RUN Control Switch percentage system load at which units are sequenced on or off
line
Emergency Stop Pushbutton (Latching)
Programmable sequence on and off delays
Multiple Attempt Crank Timer
Separate programmable time delay for overload (> 100%)
Multiple Crank Repeat Setpoint system load levels
Crank Repeat Timer
Crank Fail Alarm/Shutdown
Crank Cutout (RPM based)
Programmable Pre-Glow Timer 2.4 Control Functions
Automatic Cooldown Timer Engine Cranking
Remote Starting capability (method employed depends on The GCP-1 Control is designed to automatically control the
application) cranking functions of the engine generator set. In order to
safely control engine cranking the GCP-1 uses the following

iii
setpoints, as found in the Engine Control tuning menu of the 2. Voltage Matching during Synchronization across the
software: generator or mains breaker Reactive load sharing between
multiple units on an isolated bus
 Preglow Time
3. Reactive load control while in parallel with the mains.
 Crank Time
The generator voltage, or reactive load (depending on the
 Crank Cutout operation) is adjusted by injecting a voltage bias signal to the
 Crank Delay Automatic Voltage Regulator. The GCP-1 can be set for +/- 1
VDC, +/- 3 VDC, and +/- 9VDC outputs. The span of the output
 Crank Repeats is selected by a dip switch located on the back of the GCP-1, as
Starting Sequence: SW-2, which is near the J5 connector. Here is a table showing
the dip switch settings, and resulting voltage bias output ranges
Upon receiving a start command the following events occur: for those settings:
1. The Preglow Output Energizes for the given preglow time Dip Switches Voltage Bias Output Range
delay, and remains energized through the crank cycle.
ON
2. After the preglow time expires, the Fuel Solenoid output
energizes. SW2-5 +/- 1 VDC

3. 200 ms after the Fuel Solenoid output energizes, the SW2-4, SW2-1 +/- 3 VDC
Crank output energizes.
SW2-4, SW2-3 , +/- 9 VDC
At this point, the engine should be cranking at a certain RPM, SW2-2
and receiving fuel. Typically a start would occur in these
Select the proper voltage range input as recommended by the
conditions. To check if a start does occur, the GCP-1 monitors
AVR manufacturer.
the magnetic pickup from the engine. If the magnetic pickup
input indicates that the engine is operating above the Crank Generator Voltage can be manually controlled from the Voltage
Cutout speed, the GCP-1 will remove the Crank and Preglow Raise and Voltage Lower Discrete inputs to the GCP-1. The
outputs, leaving the fuel solenoid energized. The engine state in rate of change for manual voltage adjustment is set in the
the control overview menu changes from “OFF” to “RUN”. Reactive Load Control tuning menu, at the Voltage Ramp Time
setpoint. The voltage ramp time is the amount of time it will take
If for some reason the engine does not reach the crank cutout
for the GCP-1 to send a 0 to 100%, or 0 to -100% voltage bias
RPM level, the GCP-1 will crank the engine for the Crank Time.
signal to the AVR.
If the engine fails to rise above the crank cutout level in this
time, the GCP-1 will remove the Crank output signal, wait for the When operating in the TEST mode, manual voltage
Crank Delay, and if allowed by the number of Crank Repeats, adjustment is only allowed through the voltage raise and
will crank the engine again. This sequence will continue until the lower inputs. This allows testing of the Voltage Bias output,
number of crank repeats is depleted, or until the engine speed and generator voltage levels prior to operation with load on
rises above the crank cutout RPM setting, whichever comes the generator.
first. If the number of crank repeats is depleted, the GCP-1 will
When operating in Isoch mode, the GCP-1 does not allow
activate the Crank Fail Alarm Output based on this Alarm
manual adjustment of the voltage, unless the Load Control
setpoint’s configuration.
setpoint in the Configuration tuning menu is set for
NOTE: “Droop”, or the VAR/PF Control Setpoint in the Reactive
Load Control tuning menu is set to “Disabled”. Using either
• The preglow output may stay energized between crank of these settings implies that a manual voltage control will
attempts if the preglow time is greater than the sum of the be used, and no automatic reactive load control functions
Crank Time and Crank Delay timers.
are active.
WARNING:
NOTE:

! Set Crank Repeats to zero when starting the engine for • It is highly recommended that the automatic reactive load
the first time with the GCP-1. This will prevent starter control in the GCP-1 be used for proper power conditioning
and ring gear damage to the engine if the MPU input to throughout the generator(s) load range. This is achieved by
the control should be faulty. Monitor Engine Overview setting the Load Control setpoint in the Configuration tuning
Status menu on the first start and confirm the RPM menu to Normal, or Soft Transfer (depending on the
readout during cranking. After a successful start is application), and the VAR/PF Control setpoint in the
made, the crank repeats may be set to the appropriate Reactive Load Control tuning menu to VAR or PF control
value for the application. (depending on the application). For more details on these
functions see the Real Load Control and Reactive Load
Control sections of this manual.
The percent level of the voltage bias output can be monitored in
the I/O Display status screen of the GCP-1. This is a useful
point to monitor during initial start of the unit. By issuing Voltage
Raise and Lower inputs to the control while operating in the Test
Generator Voltage Control Mode, confirmation of proper generator voltage levels at various
The GCP-1 has the ability to control the voltage of the generator voltage bias points can easily be made. Typically the generator
set. This ability is used to control four separate operations which voltage should change no more than +/- 10% for a +/- 100%
require generator voltage adjustment : voltage bias output from the GCP-1.
1. Manual voltage adjustment All other modes of generator set operation rely upon the
Reactive Load Control functions of the GCP-1. See the

iii
information in the “Reactive Load Control” section of the manual Per-Phase Overvoltage Shutdown
for more details on voltage and reactive load control.
Per-Phase Undervoltage Shutdown
Generator Real Load Control Overfrequency Shutdown
The GCP-1 Control has four core modes of generator load Underfrequency Shutdown/Alarm
control operation. These four modes are:
Alternator Loss of Excitation Alarm
 Droop
Load Surge Detection (while in Mains Parallel)
 Isochronous Load Sharing System Protection / Alarms
 Base Load Fail to Synchronise Alarm
 Process Control Mains Bus Overvoltage Alarm (Single Phase/Neutral)
The specific mode of generator control that the unit is in at any Mains Bus Undervoltage Alarm (Single Phase/Neutral)
given time can be monitored on the Control Overview Menu.
Mains Bus Overfrequency Alarm (Single Phase/Neutral)
A detailed description of each of these load control modes, and Mains Bus Underfrequency Alarm (Single Phase/Neutral)
the various operating states that will put the GCP-1 into each
respective load control operation can be found in section 3.5 of Up to 3 Spare Fault Channels
this manual. 2.6 Standard Auxilliary Equipment

Generator Reactive Load Control PBC5: 5A Battery Charger (fitted to all 6000 series systems)

When a small generator is paralleled with a Mains, the 2.7 Standard Options
synchronizer voltage matching function adjusts the generator PBC5: 5A Battery Charger (Standard on all Systems)
voltage to match that of the Mains. Voltage variations that may
occur in the Mains system after paralleling can cause large PSB3: 5A Battery Charger With Boost
changes in reactive current in the generator. The VAR/Power PBL5: 5A Battery Charger Low Voltage (Standard on all low
Factor Control provides closed loop control of either VARs or voltage Systems)
power factor when operating in parallel with another power
WH: Water Heater Contactor
system when that system can accept the reactive load.
WHL: Water Heater Contactor Low Voltage
Voltage adjustment, however, can only affect reactive power
when another system is available to accept the reactive load. FP2: DC Fuel Pump Controls
So the VAR/Power Factor control functions are automatically FP3: AC Fuel Pump Controls
switched to Power Factor sharing when either single or multiple
PML1: Oil Temperature Gauge
units are operating in isochronous load sharing mode on an
isolated bus. PPE1: Earth Leakage (not available on 6200)

The 6000 series controller is capable of operating in 3 modes of PPE2: Earth Fault
reactive load control:- WS1: Low Coolant Level (Standard on CV12 / Dorman)

 VAr Control FS1: Low Fuel Level Shutdown


 Power Factor Control FS2: Low Fuel Level Alarm
 VAr Sharing
LS1: High Lube Oil Temp
The Reactive Load Control function may also be disabled if
desired. This mode is used as standard in 6100 and 6200 Crank Attempt Counter
systems. PSB: Emergency Stop Button With Security Key

A more detailed description of each of the above operating PAT1: Terminals For Customer Supplied Remote Emergency
modes can be found in section 3.5 of this manual. Stop
PAC1: Set of Volt Free Contacts For Common Alarm
2.5. Protective Features
PRM1: Electronic Mains Sensing Unit (Phase Failure Unit)
Engine Protection
PSB2: Canopy Mounted Emergency Stop
High Coolant Temperature Pre-Alarm
AH1: Anti-Condensation Heater With Control Panel Mounted
High Coolant Temperature Shutdown
Auto control System and Contactor
Low Oil Pressure Pre-Alarm
FV1: DC Tank Base Mounted Solenoid Valve (For Use With
Low Oil Pressure Shutdown FS3 or FS4)

Overspeed Shutdown FS3: 2 x Tank Mounted Fuel Level Switches (High and Low)

Fail to Start Shutdown FS4: 4 x Tank Mounted Fuel Level Switches (High, Extra High,
Low, Extra Low)
Emergency Stop Operated
E1: Electronic Governor (Standard on 6200 and 6300 Systems)
Battery Overvoltage Alarm
WC1: Low Coolant Temperature Switch
Battery Undervoltage Alarm
2.8. Communications Options
Alternator Protection
PC1: Remote Monitoring (Hardwired)
Reverse Power Shutdown
PC2: Remote Monitoring and Control (Hardwired)

iii
TEL1: Remote Monitoring (Dial Up Link)
9 Mains Breaker Trip
TEL2: Remote Monitoring and Control (Dial Up Link)
10 Generator Breaker Trip
TEL3: Remote Monitoring and Control With Fault Alert Callback
(Dial Up Link) 11 Audible Alarm Relay

MOD1: Remote Monitoring and Control Utilising a ModBus The identification numbers associated with the discrete inputs
Communications Network and outputs are used in the I/O status screen of the GCP–1.
2.9 Hardware
AC Inputs
Discrete Inputs and Outputs
The GCP–1 receives AC inputs from the
The discrete inputs and outputs of the GCP–1 control are used
to interface external commands to specific control actions and generator, bus, mains and engine. They are as
operations, and to control external devices. follows:
The Discrete inputs are designed to be tied back into a switch Loc. Description Signal Burden
common on the GCP–1 when closed. Each switch input will sink
5 mA of current at 12 VDC when closed. J5-19 Generator PT phase A Line AC Voltage
Below is a list of the discrete inputs available to the GCP–1 J5-23 Generator PT phase A Neutral AC Voltage
control.
J5-18 Generator PT phase B Line AC Voltage
ID Description
J5-22 Generator PT phase B Neutral AC Voltage
Number
J5-17 Generator PT phase C Line AC Voltage
1 Mode Control Input #1 (Auto)
J5-21 Generator PT phase C Neutral AC Voltage
2 Mode Control Input #2 (Test)
J5-9 Generator CT phase A Current AC Current .067
3 Mode Control Input #3 (Run with Load) ohms
4 Volts Bias Raise J5-5 Generator CT phase B Current AC Current .067
ohms
5 Volts Bias Lower
J5-1 Generator CT Phase C Current AC Current .067
6 Speed Bias Raise ohms

7 Speed Bias Lower J5-10 Generator CT Neutral AC Current

8 Generator Circuit Breaker / Contactor J5-20 Mains/Bus PT phase A Line AC Voltage


Auxiliary J5-24 Mains/Bus PT phase A Neutral AC Voltage
9 Mains Circuit Breaker / Contactor Auxiliary J1-2 +Magnetic Pickup AC Freq.
10 Mode Control Input #4 (Process) J1-1 -Magnetic Pickup AC Freq.
11 High Engine Temperature Shutdown Contact DC Inputs and Outputs

Location Description Signal I/O


12 Low Oil Pressure Shutdown Contact
J5-12 + power supply 9-15 VDC (12V unit) Isolated
13 Emergency Stop Input
J5-8 - power supply 18-32 VDC (24V unit) Input
14 - 16 Spare Fault Channels 1 – 3 J5-2 + process signal 4-20 mA or 1-5 VDC 6 Watt
Below is a list of the discrete outputs available. All discrete J5-6 - process signal typical
outputs consist of double-pole relays rated at 10A at 120VAC, J1-17 + speed bias +/- 3 VDC Isolated
8A at 277VAC resistive. J1-13 - speed bias Output
J5-3 + voltage bias +/- 1, 3, or 9 VDC Isolated
J5-7 - voltage bias Output

Communication Ports
2 x serial communications ports are provided on the 6000 series
controller (1 x RS-485 and 1 x RS-422). Details of connections and
uses are given below.
ID Description
Number
Location Description Signal
1 Mains Breaker / Contactor Close
J8-2 - RS-485 communication line Intercontrol comms
2 Generator Breaker / Contactor Close
J8-1 + RS-485 communication line Intercontrol comms
3 Engine Preglow
J8-4 + 5VDC Isolated Supply
4 Fuel Control Solenoid
J8-5 - 5VDC Isolated Supply
5 Engine Crank
J8-3 + RXD RS-422 communication line Remote communications
6 Visual Alarm Relay
J8-6 - RXD RS-422 communication line Remote communications
7 Local Bus PT Connect
J8-8 + TXD RS-422 communication line Remote communications
8 Mains Bus PT Disconnect

iii
J8-9 - TXD RS-422 communication line Remote communications

Switch # Description Normal


Status
SW1-1 Not used N/A
SW1-2 Not used N/A
SW1-3 Not used N/A
SW1-4 Not used N/A
SW1-5 Oil pressure shunt resistor (100 ohms when on) OFF
SW1-6 Oil pressure shunt resistor (100 ohms when on) OFF
SW1-7 Water temp shunt resistor (100 ohms when on) ON
SW1-8 Water temp shunt resistor (100 ohms when on) ON
SW2-1 Voltage bias output scaling (ON for +/- 3VDC, OFF
OFF for others)
SW2-2 Voltage bias output scaling (ON for +/- 9VDC, OFF
OFF for others)
SW2-3 Voltage bias output scaling (ON for +/- 9VDC, OFF
OFF for others)
SW2-4 Voltage bias output scaling (OFF for +/- 1VDC, OFF
ON for others)
SW2-5 Voltage bias output scaling (ON for +/- 1VDC, ON
OFF for others)
SW2-6 Not used N/A
SW2-7 Not used N/A
SW2-8 Process input type selection ON
ON = 4-20 mA input, OFF = 1-5 VDC input (4-20
mA)
SW3-1 RS-422 Termination RxD+ ON
(end of
line
units)
SW3-2 RS-422 +5VDC pull-up ON
(end of
line
units)
SW3-3 RS-422 Termination RxD- ON
(end of
line
units)
SW3-4 RS-485 +5 VDC pull-up ON
(end of
line
units)
SW3-5 Not used N/A
SW3-6 Not used N/A
SW3-7 RS-485 Termination - ON
(end of
line
units)
SW3-8 RS-485 Termination + ON
(end of
line
units)

iii
Explanation of Dip Switches

J1 J2 EXPLANATION OF
SWITCHES
SW-1
8 water temp shunt resistor (100 ohms) when ON
7 water temp shunt resistor (100 ohms) when ON
6 oil pressure shunt resistor (100 ohms) when ON
5 oil pressure shunt resistor (100 ohms) when ON
4 not used
3 not used
2 not used
1 not used
on off
8
7
CONTRAST
6 ADJ. SW-2
5
4
3
8 process I/E: ON = 4-20 mA @250 ohms; OFF = 1-5 VDC @ 30Kohms
7 not used.
2
1 J5 6 not used. +/- 1 +/- 3 +/- 9
SW-1 5 voltage bias output
4 voltage VDC VDC VDC
scaling bias output
3 voltage
scaling bias output SW2-5 SW2-4 ON SW2-4 ON
2 voltage bias output
scaling ON SW2-1 ON SW2-3 ON
1 voltage bias output scaling
scaling SW2-2 ON

8 RS-485 Termination +
7 RS-485 Termination -
on
8
off 6 not used.
7 5 not used.
6 4 RS-485 +5VDC pull up.
5
4
3 RS-422 Termination RxD -
3 2 RS-422+5VDC pull up.
2 1 RS-422 Termination RxD +
J8 on
8
off
1

7 SW-2
6
5
4
3
2
1

SW-3

Connector Wiring Diagram


W
iringDiagramforGCP-1
Connector Connector Connector
J5 J1 J2

+ 12 - + 17 9
Speedbiasoutput Mainsbreakerclose(DO1) n.o.
12Vdcor24Vdc - 13 18
- 8 n.c.
- 1 27
Shieldtermination 4 MPUspeedinput
+ 2 8
+ 20 n.o.
Mains/BusAphasePT GeneratorBreakerClose(DO2)
+
- 24 5 17
Coolanttemperaturesensor n.c.
- 6 26
+ 19
GeneratorAphasePT Oilpressuresensor
- 23 + 9 7
EnginePreglow(DO3) n.o.
Auto/m
anual(DI1) 16
+ 18 16
n.c.
GeneratorBphasePT Testengine(DI2)
- 22 10 25
Runwithload(DI3) 34
+ 17 11
Voltageraise(DI4) FuelSolenoid(DO4) n.o.
GeneratorCphasePT 35
- 21 12
n.c.
Voltagelower(DI5) 36
GeneratorAphaseCT + 9 24
Speedraise(DI6)
GeneratorBphaseCT + 5 19 6
EngineCrank(DO5) n.o.
Speedlower(DI7) 15
GeneratorCphaseCT + 1 20
GeneratorCBaux(DI8) n.c.
CTNeutral - 10 15 24
MainsCBaux(DI9) 22 31
+ 2 n.o.
Processim port/export ProcessI/E(DI10) VisualAlarm(DO6)
(4-20m A/1-5Vdc) - 6 18 32
n.c.
Fault1(DI11) 33
+ 3 14
Voltagebiasoutput Fault2(DI12)
7 23 5
- n.o.
Fault1(DI11) LocalBusPTConnect(DO7)
8 13
NoConnect 11 n.c.
Fault2(DI12)
7 23
NoConnect 13
Fault1(DI11) 4
NoConnect 14 4
n.o.
Fault2(DI12)
3 14
NoConnect 15 MainsPTDisconnect(DO8) n.c.
21 22
NoConnect 16
1
MainsBreakerTrip(DO9) n.o.
10
n.c.
Connector 3
J8
2
+ 1 n.o.
RS-485Network GeneratorBreakerTrip(DO10)
- 2 11
ConnectorJ5is24-pinmaleTrimTriotype n.c.
(maleconnectoronPCboard) Shieldterm
ination 7 12

+ 3 28
ConnectorJ1is24-pinfem aleTrimTriotype RS-422RxD AudibleAlarm(DO11) n.o.
(femaleconnectoronPCboard) - 6 29
n.c.
+ 8 30
ConnectorJ2is36-pinfem aleTrimTriotype RS-422TxD
(femaleconnectoronPCboard) - 9 NoConnect 19

NoConnect 4 NoConnect 20
ConnectorJ8is9-pinm aleTrimTriotype
(maleconnectoronPCboard) NoConnect 5 NoConnect 21

1
3. Configuration - Outline of Setpoints value is out of range, and the engine will not operate until the #
symbol is cleared by entering the correct values.
3.1 Configuration Menu
CT Ratio (numeric : 5)
Security Code - 4 Levels of Access
Scales sensed CT input for Amperage as seen at generator
• Operator: Access to Alarm Log and Network
Priority Used for Load Sensing Algorithm (KVA,KW,KVAR,PF)
• Supervisor: Allows access to Network Address and PT Ratio (numeric : 1)
Time Set in addition to above access.
Scales sensed PT input to Voltage Levels as measured at the
• Technician: Allows access to all setpoints except
Generator
engine run time and calibration
• Factory: Allows access to all setpoints Used in Load Sensing Algorithm (KVA, KW, KVAR, PF)

Network Address (1 to 8) Used for Voltage Matching

Unique Address for Each Unit in the System Voltage Input (Wye L-N, Delta L-L)

Maximum of 8 units on network Set for sensing/transformer used between generator and Gen
Part 6000.
Network Priority
Defines which calculations will be used for kW, KVA, KVAR,
Unique Priority for Each Unit in the System etc.
Lowest Active Priority is considered Master Wye (Star) Generator or Transformer Connection
Maximum of 8 units on network 4 Wire - volts measured Line to Neutral
Delta Generator or Transformer Connection
Sequencing effective from lowest to highest priority
3 Wire - volts measured Line to Line
“Set All” Function
Voltage Reference (numeric)
When priority is reduced below 1, the value will change to “Set
All”. If the commit key is pressed when this value is on the Operating Voltage of Generator per Generator Spec.
display, the display will change to represent all units in auto on Used for Var/PF Sharing as the Reference that multiple
the network, and their priority. The network priority of any unit generators share reactive load to. This maintains the voltage
can be changed by using the left/right and up/down keys n the reference while in Power Factor Sharing or KVAR Control mode
control. Once changes are made, the changes are committed on an isolated bus.
by pressing the commit key twice.
Load Control Mode
Number of Poles (numeric)
Normal: Standard setting for load control and VAR/PF functions
Determines Speed/Frequency Relationship
Soft Transfer: Standard load control and VAR/PF functions, but
Used for Speed/Frequency Mismatch Alarm/Shutdown unit will issue mains breaker open command while in process
control if process reference is reached, or while in base load
Number of Teeth (numeric) and base load reference is reached.
Determines RPM Scaling Droop: Manual Load and Voltage Control used primarily for
Engine Speed Readouts/Alarms commissioning

System Frequency (50/60 Hz) Process Action (direct, indirect)

Used as a basis for generator waveform analysis Defines action of speed bias when unit is operating in process
control in parallel with the mains.
Defines typical operating frequency of generator Direct action = Unit increases speed bias (fuel) to increase
process 4- 20 ma input
Rated Speed (numeric) Indirect action = Unit decreases speed bias (fuel) to increase
Synchronous Speed of Generator Set process 4-20 ma input.

Used in Speed Calculation to determine “sample” period for Circuit Breaker Control (Breaker, Contactor)
MPU input Defines action of Generator and Mains closure command
Rated kW (numeric) Breaker issues momentary close signal, momentary open signal
Rated kW of Generator independently.

Rated kVA (numeric) Contactor issues continuous close signal. Removes this signal
to open contactor.
Used to determine Rated Current of Generator
Equation: I=KVA/Rated Voltage Breaker Close
Rated kVAr (numeric) Normally Open and de-
energised on mains and
Rated KVAR of Unit generator
Typically .6 x Rated KVA
Breaker Open
NOTE:-
Normally Open and
• Rated KVA must be less than or equal to the Voltage energised on generator
Reference x CT Ratio Primary. Normally Closed and
Rated kW must be less than or equal to the Rated KVA Contactor
de-energised on mains
Close/Open
Rated KVAR must be less than or equal to the Rated KVA
Any Values Falling out side of these ranges will appear on the Normally Open and
screen with a pound sign (#) next to them. This indicates the de-energised on generator

Normally Closed and


2 de-energised on mains
If this time is exceeded a link failure error will be logged.
Modbus Reset (True, False)
Used to reset all static ModBus error messages
Check Mains Breaker (enabled, disabled) 3.2 Shutdowns, Alarms
Used to activate checking of mains c.b. aux. input when Shutdowns and Alarms menu is used to configure the various
enabled safety functions of the Gen Part 6000.
Each alarm setpoint can be set for:
If disabled, unit relies on other units with this setpoint enabled to
broadcast state of mains c.b. aux. contact over network  Disabled: Disables alarm indication and logging.
 Warning: LED on Control Flashes.
Operating Mode
 Visual Alarm: LED Flashes, and Visual Alarm relay
Mains Parallel or No Mains Parallel energises.
Mains Parallel will allow the unit to synchronise to the mains,  Audible Alarm: LED Flashes, Visual and Audible Alarm
and carry load while in parallel with the mains as well. relays energise.

No Parallel will allow the unit to operate with load until the mains  Soft Shutdown: LED Turns On, Visual and Audible
breaker is sensed as being open Alarm relays energise, Fuel Solenoid relay de-
energises. Unit soft unloads and cycles through cool
All units operating in a load sharing system must be set for the down timer when applicable.
same parameter, i.e. mains parallel, or no parallel.  Hard Shutdown: Same as above, but immediately
Number of Units (single, multiple) opens generator breaker and de-energises fuel
solenoid.
Defines whether unit is part of a multiple unit system or not. The following alarms have ‘special’ functions:
If single unit, there is no auto starting, auto sequencing, load or  Mains Voltage High
pf sharing with other units under any circumstances. Unit
 Mains Voltage Low
displays “single unit no sequencing” on sequencing screen.
 Mains Frequency High
If multiple unit, auto starting, auto sequencing, load and var/pf
 Mains Frequency Low
sharing are active between all units in multiple. Unit displays
system-sequencing information on sequencing screen.  Load Surge
Auto Sequencing (enabled, disabled) These alarms cannot be set to ‘Soft Shutdown’ or ‘Hard
Shutdown’ but may be set to the following two extra functions:
Enables or Disables Auto Sequencing for that unit
 Loss Of Mains
Can be used to disable sequencing for a particular unit in a
sequencing system if needed - Triggers an internal Loss of Mains condition
- No alarm indication triggered
RS-422 Protocol (Modbus, Servlink, Upload Setpoints)
 Loss Of Mains With Alarms
Used to select between different types of communication
options as outlined below: - Triggers an internal Loss of Mains condition
- Triggers an audible alarm
 ModBus
Load Surge (numeric %/sec)
Utilises the industry standard ModBus protocol.
More details on ModBus communications Used only in Base Load or Process Control (Mains Parallel
With the 6000 series system can be found in section xxxx Operations)
of this manual.
The controller must be re-booted if this option is selected to Set to trigger at a percent setpoint of total generator load shift
initialise ModBus communications per second while operating in Mains Parallel

 Servlink Instantaneous Trigger

Utilises the Servlink protocol. Load Surge Alarm


This option is used in conjunction with the PC1, PC2, Type of alarm triggered on Load Surge event
TEL1, TEL2 and TEL3 communications options.
The controller must be re-booted if this option is selected to Can be set for Loss of Mains Detection
initialise Servlink communications.
Mains Volts High Limit
 Upload Setpoints
Maximum mains bus voltage for mains to be considered stable
Used for uploading the stored setpoints from the controller
Mains Volts High Alarm
to a storage file on a PC compatible computer.
This option should not be used by any personnel other than Type of alarm triggered on Mains Volts High event
FGW commissioning personnel who have undergone the
appropriate training. Can be set to Loss Of Mains / Loss of Mains with Alarms

Modbus ID (numeric) Mains Volts Low Limit

Used to uniquely identify each controller on a ModBus network Minimum mains bus voltage for mains to be considered stable
Any changes will not take effect until the controller has been re-
booted
Mains Volts Low Alarm
Modbus Timeout (seconds) Type of alarm triggered on Mains Volts Low event
Maximum time delay allowed between successive polls of the Can be set to Loss Of Mains / Loss of Mains with Alarms
slave controller by the master.
This should be set to greater then the polling period of the Mains Frequency High Limit
ModBus master.

3
Minimum mains bus frequency for mains to be considered If frequency is below Low Limit, generator is not considered
stable stable, and is unfit for breaker closure.
Mains Frequency High Alarm The controller will not allow speed biasing which will cause the
generator output frequency to go below this level even if the
Type of alarm triggered on Mains Frequency High event alarm is disabled.
Can be set to Loss Of Mains / Loss of Mains with Alarms Generator Frequency Low Alarm
Mains Frequency Low Limit Type of alarm triggered on a Generator Frequency Low event
Maximum mains bus frequency for mains to be considered Speed / Frequency Mismatch
stable
Compares generator frequency to engine RPM and alarms on
Mains Frequency Low Alarm difference
Type of Alarm triggered on Mains Frequency Low event Used to indicate loss of MPU, or Loss of Generator Field
Can be set to Loss Of Mains / Loss of Mains with Alarms Voltage

Loss of Mains (LOM) Action Delay Overspeed

Sets Time Delay for LOM Action to begin once Loss of Mains is Set for overspeed limit of engine
detected. Typically set for Hard Shutdown for safety
Typically Delay time From LOM to engine start command Typically Set for 10% above Rated Speed of engine
Voltage Range Alarm Overspeed Alarm
Type of alarm triggered once voltage bias signal to AVR Type of alarm triggered on a overspeed event
reaches +/- 100%
Overcurrent Level
Generator Volts High Limit
3 Phase Sensing
Sets maximum allowable generator voltage level
Set for Per Phase Overcurrent
Triggered of any individual phase
Over Current Detection begins when current exceeds rated
If voltage is above High Limit, generator is not considered current as determined by Voltage Reference and Rated KVA
stable, and is unfit for breaker closure. values in Configuration menu: (KVA/Voltage Ref)/3.
The controller will not allow voltage biasing which will cause the Uses Inverse Time Function as basis for overcurrent detection.
generator voltage to go above this level even if the alarm is This allows different levels of overcurrent based on time span.
disabled.
Per Phase
Generator Volts High Alarm amps Overcurrent Inverse Time Function
Overcurrent Trip Zone
Type of alarm triggered on a Generator Volts High event
overcurrent level
Generator Volts Low Limit
Sets minimum allowable generator voltage level 100% rated current
Triggered of any individual phase time
overcurrent
If voltage is below Low Limit, generator is not considered stable, delay
and is unfit for breaker closure.
The controller will not allow voltage biasing which will cause the Over Current Level
generator voltage to go below this level even if the alarm is
High Current, Short Duration
disabled.
Generator Volts Low Alarm amps
Overcurrent Trip Zone
Type of alarm triggered on a Generator Volts Low event overcurrent level
Voltage Alarm Delay
Delay between detecting a Generator Voltage High or Low
condition and activating the configured alarm time
overcurrent
Generator Frequency High Limit delay

Sets maximum allowable generator output frequency Overcurrent Level


If frequency is above High Limit, generator is not considered
Notice area of over current is the same
stable, and is unfit for breaker closure.
The controller will not allow speed biasing which will cause the
generator output frequency to go above this level even if the
alarm is disabled.
amps Overcurrent Trip Zone
overcurrent level
Generator Frequency High Alarm
Type of alarm triggered on a Generator Frequency High event
Generator Frequency Low Limit overcurrent time
delay
Sets minimum allowable generator output frequency
Overcurrent Delay

4
Setpoint used in conjunction with the Overcurrent Level setpoint Active when generator is stable
to determine tripping time on an overcurrent condition
Sensed in Bar
Overcurrent Alarm
Approaching Low Oil Pressure Alarm
Type of alarm triggered on an Overcurrent event
Type of alarm triggered on an Approaching Low Oil Pressure
Reverse Power event
Reverse Power Condition begins when sensed kW on generator Approaching High H2O Temp
goes negative. Reverse Power
Sets the trigger point for the Approaching High H2O Temp pre-
Trip levels depend upon amplitude and duration of reverse alarm
power condition.
Uses Engine mounted temperature sensor
Reverse Power Delay
Active when generator is stable
Reverse Power also uses an inverse time function.
Sensed in ºC
Reverse Power
Approaching High H2O Temp Alarm
Minimum Reverse Power
Minimum reverse power level which can trigger a reverse power Type of alarm triggered on an Approaching High H2O Temp
alarm. Reverse power levels below this setpoint will never event
cause a reverse power alarm condition, regardless of duration.
See diagram above. Low H2O Temperature

Reverse Power Alarm Sets the trigger point for the Low H2O Temp alarm

Type of alarm triggered on a reverse power event. Uses Engine mounted temperature sensor

Loss of Excitation (LOE) Active when generator is stable


Set as a percentage of total KVAR load on the generator that Sensed in ºC
can be applied as a block reactive load to the unit. If control
senses changes in KVAR loads instantly applied greater than Low H2O Temperature Alarm
this value the LOE alarm triggers. Type of alarm triggered on an Approaching High H2O Temp
event
Used to indicate loss of field excitation to the generator
High Engine Temperature
Loss of Excitation (LOE) Alarm
Sets the type of alarm activated upon the application of the
Type of alarm triggered on an LOE event.
external High Engine Temperature volt-free signal.
Battery Voltage High Limit
Normally set to ‘Soft Shutdown’
Maximum permissible DC voltage supply to 6000 control
Set to ‘Hard Shutdown if combined with an external Low Coolant
Can be used to detect faulty charging circuit Level sensor
Battery Voltage High Alarm Only activated 15 seconds after the engine has reached the
Type of alarm triggered on a Battery Voltage High event crank cut-out speed

Battery Voltage Low Limit High Engine Temperature Timer

Minimum permissible DC voltage supply to 6000 control Additional delay between the application of the external High
Engine Temperature volt-free signal and the activation of the
Used to detect weak battery/failed charger configured alarm type
Automatically Disabled during engine cranking Not active when engine not running
Battery Voltage Low Alarm Low Oil Pressure
Type of alarm triggered on a Battery Voltage Low event Sets the type of alarm activated upon the application of the
High Oil Pressure Limit external Low Oil Pressure volt-free signal.

Sets the trigger point for the High Oil Pressure Alarm Normally set to ‘Hard Shutdown’

Uses Engine mounted pressure sensor Only activated 15 seconds after the engine has reached the
crank cut-out speed
Active when generator is stable
Low Oil Pressure Timer
Sensed in Bar
Additional delay between the application of the external High
High Oil Pressure Alarm Engine Temperature volt-free signal and the activation of the
Type of alarm triggered on a High Oil Pressure event configured alarm type

Approaching Low Oil Pressure Not active when engine not running

Sets the trigger point for the Approaching Low Oil Pressure pre- Emergency Stop
alarm
Sets the type of alarm activated upon the application of the
Uses Engine mounted pressure sensor external Emergency Stop volt-free signal.

5
Normally set to ‘Hard Shutdown’ Cool down Time

Emergency Stop Timer Time allowed for cool down after coming off-line during a normal
stop sequence
Delay between the application of the external High Engine
Temperature volt-free signal and the activation of the configured Only activated if the generating set load has exceeded the Cool
alarm type down Limit

Always activated Cool down Limit

Spare Fault #1 kVA setpoint at which, when exceeded will cause the engine will
execute a cool down during a stop sequence
Sets the type of alarm activated upon the application of the
external Spare Fault #1 volt-free signal. Engine Run Time

Normally set to ‘Disabled’ Hours of run time on the engine

Spare Fault #1 Timer Increments in hours

Delay between the application of the external volt-free signal Retained in EE memory - retains value after power loss
and the activation of the configured alarm type
May be re-set or pre-programmed by anyone with level 3
Always activated security access

Spare Fault #2 MW Hours


Sets the type of alarm activated upon the application of the MW hours supplied by the generating set
external Spare Fault #2 volt-free signal.
increments in 0.1 MW hour steps
Normally set to ‘Disabled’
Retained in EE memory
Spare Fault #2 Timer
May be re-set or pre-programmed by anyone with level 3
Delay between the application of the external volt-free signal security access
and the activation of the configured alarm type
3.4 Synchroscope
Always activated
Synchroniser Mode
Spare Fault #3
 Permissive
Sets the type of alarm activated upon the application of the
- Acts as a synch check device.
external Spare Fault #3 volt-free signal.
- 6000 will not issue speed or voltage bias commands,
Normally set to ‘Disabled’ but if synchronisation conditions are within spec
(phase and voltage), control will issue a breaker close
Spare Fault #3 Timer command.
Delay between the application of the external volt-free signal  Check
and the activation of the configured alarm type
- Used for checking synchroniser prior to
Always activated commissioning
- 6000 control actively synchronises generator by
3.3 Engine Control issuing speed and voltage bias commands, but does
Preglow Time not issue breaker closure command

Time of preglow allowed prior to engine crank cycle  Run

Maintained through engine cranking - Normal operating mode


- Actively synchronises and issues breaker closure
Resets after every crank attempt command
- Control MUST be in RUN to operate as a dead bus-
Crank Time closing device.
Maximum allowable time for engine cranking - In multiple unit systems 6000 control MUST have
AUTO input active to enable dead bus closing
Crank Cut-out
Synchroniser Gain
Engine RPM level where crank command is cancelled
Sets Gain of synchroniser speed bias output
Crank Delay
Synchroniser Stability
Time between engine crank attempts
Sets Stability of synchroniser speed bias output
Crank Repeats
Both Gain and Stability are used to tune the synchroniser
Number of times the 6000 control will attempt to re-start the dynamic response.
engine. The number of actual cranking attempts = Crank
Voltage Matching
Repeats +1
Enables/Disables Voltage Matching feature of 6000 control
Crank Fail
Enables Voltage Window Setpoint
Type of alarm triggered once the generating set has completed
its full crank sequence and the engine has not yet started. Voltage Window

6
Overall percentage of error allowed between generator and bus, Load Control Gain
or generator and mains
Sets gain response of load control
6000 control will not issue a breaker closure if error is greater
Active in load ramping and base load operations
than voltage window
Load Share Gain
Maximum Phase Window
Sets gain response of proportional load sharing
Maximum allowable phase angle deviation from phase matched
condition. Active in load sharing operations

6000 Control will not issue breaker closure if phase angle Load Stability
between generator and bus, or generator and mains exceeds Sets stability response of load control
this window
Active in load ramping and baseload operations
Dwell Time
Load Derivative
The period of time that the generator must be within the Max.
Phase Window for before the 6000 control will issue a breaker Sets derivative response of load control
closure
Active in load ramping and baseload operations
Longer dwell times will give typically give better stability after the
Load Control Filter
breaker closes
Low pass filter used to attenuate higher frequency transients for
Shorter dwell times reduce amount of time required to better stability
synchronise unit
Active in proportional load sharing, load ramping and baseload
C.B. Hold Time control modes
Time in Seconds that Breaker/Contactor Close output is held
Baseload
after breaker close command is issued
Load Level Generator will automatically ramp to when operating
Close Attempts in Base Load
Number of Close Attempts allowed while synchronising
Unload Trip
Close attempt incremented if breaker does not send back Load Level where Generator Breaker/Contactor open command
continuous CB aux. signal to 6000. will be issued when 6000 control is off loading generator set
Reclose Delay Load Droop
Time in Seconds before 6000 control attempts re- Percentage of kW droop used when 6000 control is operating in
synchronisation after failed closure attempt a droop mode

Synch Reclose Alarm Load Time


Alarm setpoint if number of close attempts is depleted Time in Seconds for generator to load from unload trip level to
base load level. This rate is applied during any automatic
Synch Timeout
loading function, including ramping to load sharing
Sets time allowed for synchronisation in seconds
Unload Time
Begins timing when synchroniser activates
Time in Seconds for generator to unload from base load level to
Active for all gen and mains breaker open and close commands unload trip level. This ramp rate is applied during any automatic
from 6000 control unload functions, including ramping from load sharing

A setting of zero (0) seconds disables synch. time-out - infinite Raise Load Rate
synch time allowed Percent Load per Second ramp rate used when the raise load
Synch Timeout Alarm contact input is used during base load operation.

Sets alarm mode if synch time-out is exceeded Lower Load Rate

Dead Bus Closure Percent per Second Ramp Rate used when the load lower input
is active in base load control operation
Enables/Disables Dead Bus Closing Feature
Fast Xfer Delay
Only active in multiple unit systems. Dead bus closing is always
active in single unit configuration. Time required for a transition in switching from Mains to
Generator operations, and from Generator to Mains operations.
Unit must be within voltage and frequency high/low limits to be This includes transition times between bus and mains sensing.
considered for dead bus closure.
Mains Stable Delay
Dead Bus Closure uses Token Passing Scheme to assure that
only one unit in a networked system will close onto the dead bus Period of time required for the mains to be declared stable
at any given time. before transition from generator(s) to mains.

Multiple unit systems must have Auto switch input to allow dead Generator Stable Delay
bus closing between networked units Period of time generator must be declared stable before
transition from Mains to Generator, as well as dead bus closing
3.5 Real Load Control

7
Load High Limit Master begins sequencing next lowest priority unit off line if
system load is still above Min. Gen. Load setpoint at the end of
Maximum allowed load while operating in Base load or Process
the Max Stop Time Limit.
control modes
3.6 Reactive Load Control
Prevents overload of unit
VAr / PF Mode
High Limit Alarm
Can be set to one of three modes
Sets alarm mode when unit is at or above High Load Limit
 Disabled
Active during all load control operations
- Unit does not PF share, or control PF under any
Load Low Limit
circumstances
Minimum allowed load while operating in Base load or Process - This setting should be used for all 6100 and 6200
control modes systems

Prevents reverse current of unit  VAR Control

Low Limit Alarm - Unit PF shares in isolated bus load sharing mode
- Unit controls KVAR in Base Load and Process Control
Sets Alarm Mode when unit is at or below Low Load Limit Modes
Active during all load control operations  PF Control
Maximum Generator Load - Unit PF shares in isolated bus load sharing mode
% system load on all units with gen breakers closed, and on the - Unit controls PF in Base Load and Process Control
Modes
same network, in Auto,and in Load Sharing or Process control
modes, at which active master unit will begin timing to sequence VAr / PF Gain
next unit on line.
Controls Gain Response of unit in Var/PF control mode
Next Generating set Delay
NOT active in PF sharing mode
Period of time that will pass before master auto sequences an
Voltage Ramp Time
additional generator on line.

Delay is effective only in active master unit Ramp time from 0 to +/-100% voltage bias output

Rated Load Delay Controls response of units in PF sharing modes

Delay when system load exceeds 100%, before master starts Controls ramp time of voltage during synchronisation
next generating set in sequence Controls ramp time of voltage during manual voltage adjust
Maximum Start Time VAr / PF Share Gain
Time allowed by master to see next unit to be sequenced on line Not Active in any modes (reserved for future use)
in an “active” condition, i.e. started and ready to load.

This is determined by a flag, which indicates the unit is ready to


VAr / PF Stability
load, is sent over the network by the unit being sequenced on
by the master. Controls Stability Response of unit in Var/PF control mode

If master does not detect this flag within the Max. Start Time NOT active in PF sharing mode
allowed, it will go to the next lower priority unit and try starting it,
kVAr Reference
or if no other units are available, it will retry the start command
on the same unit. When KVAR control mode is selected, this references the
amount of KVAR the generator will produce while in Base Load
Minimum Generator Load or Process control modes
% of system load at which active master begins timing to
Can be set for generate or absorb levels of KVAR
sequence units off line
KVAR levels limited by Rated KVAR of unit
Master may have to wait until system load is below this level if
unit next in line to be sequenced off will cause the system load PF Reference
to increase above the Max Gen Load setpoint of the Master.
PF level that will be maintained by the generator while in Base
Reduced Load Delay Load or Process control modes.

Time in seconds which the active master waits before Can be set for leading or lagging power factor
sequencing units off line.
Scaled from 0 (unity) to - .5 (.5 leading) to +.5 (.5 lagging)
Delay is effective only on active master unit
PF Deadband
Lowest priority units are sequenced off line first
+/- deadband around PF reference point
Maximum Stop Time
set in PF
Time in seconds allowed by master for slave to sequence off
Active in PF and PF sharing modes
line
Can be used to stabilise units at low loads if needed

8
3.7 Process Control Lower rate
Process Master Uses Process PID to control Rate, in mA/Sec., at which the process reference will change
when the 6000 control receives a lower load contact input while
Gain, Stability, Derivative, Filter, Droop
operating in process control mode
Slaves to the Process Master use Load Control PID Values to
Process High Limit
track master system load reference
Maximum allowable process reference level. Set in mA
Load Gain, Stability, Derivative, and Filter
Effective on active master unit only
Process Gain
Process High Limit Alarm
Sets system gain response while in process control
Sets alarm mode when process High Limit is reached
Effective at active master unit only. Slaves rely on Load Control
dynamic settings to control response to master load reference Process Low Limit

Should be set with maximum number of units operating in Maximum allowable process reference level. Set in mA
process control mode Effective on active master unit only
Process Stability Process Low Limit Alarm
Sets system stability response while in process control
Sets alarm mode when process reference reaches the Low
Effective at active master unit only. Slaves rely on Load Control Limit
dynamic settings to control response to master load reference
Process Low Limit Alarm
Should be set with maximum number of units operating in Sets alarm mode when Process Low Limit is reached
process control mode
3.8 Calibration
Process Derivative
While each unit will be factory calibrated at Woodward prior to
Sets system derivative response while in process control shipment, there are bound to be some inputs/outputs affected
Effective at active master unit only. Slaves rely on Load Control by external wiring and/or interfaces (relays, transformers, etc.)
dynamic settings to control response to master load reference that will require calibration at the site during commissioning.

Should be set with maximum number of units operating in The Calibration Menu allows calibration of all the analogue
process control mode inputs to the 6000 control, as well as the speed bias and voltage
bias outputs.

All calibration points in the 6000 control are used to make the
actual value of an input such as generator voltage, read out on
Process Deadband the respective display screen of the 6000 control, the proper
value of the signal being monitored.
+/- deadband around process reference point
Example:
Set in mA
380VAC measured line to line on the generator should read
Process Droop 380VAC in the line to line voltage measurement area of the
6000 control “generator overview” menu.
Introduces negative feedback on the process reference as the
process input increases Any differences between the measured and actual values can
be corrected using the generator PT calibration points in the
Used to add stability to marginally stable processes
calibration menu.
Process Filter
Process In Scale
Low Pass Filter attenuates higher frequency transients on
Actual Input - 4-20 mA, or 1- 5VDC process signal from external
process 4-20 mA input signal
transducer.
The higher the filter is set, the more active the process control
Monitor the Pin (process in) reading in the Load Control Monitor
will be to higher frequency process transients
menu
The lower the filter is set, the less active, and more stable the
Calibrate Process input scale until Pin reads accurately what
process control will be to higher frequency process transients
measured process signal is.
Process Reference
Engine must be in a test or run mode and operating to observe
The reference point, in mA, at which the master will control the the Pin value in the Load Control Monitor menu
process input.
Speed Bias Offset
Also used in Soft Transfer modes to set the level of process at
Factory calibrated for 0VDC offset on +/- 3 VDC range.
which the transfer from mains to generator will occur
All Woodward Speed controls operate with this bias output, so
Raise Rate
no calibration should be required to operate with these controls
Rate, in mA/Sec., at which the process reference will change
when the 6000 control receives a raise load contact input while Calibration may be required for other manufacturer’s speed
operating in process control mode controls.

Voltage Bias Offset

9
Factory set for zero Volts DC. Put 6000 control synchroniser in “check” mode in synchroniser
setup menu.
Dip Switch selectable +/- 1VDC, +/- 3 VDC, +/- 9 VDC range.
Start engine in run/load mode to a live bus (either paralleling to
Some regulators require a positive voltage bias offset because
another generating set, or the Mains).
they cannot receive a negative voltage bias command.
Monitor Synchroscope status menu. Observe and calibrate U:
6000 control will always reset to the voltage bias offset when off
volts reading until measured matches monitored.
line.
Synchroscope Offset
PT Phase A Scale
Calibrates phase angle error detection of 6000 control.
Calibrates PT phase A voltage input
Factory calibrated for zero phase angle error between bus and
Monitor Gen Overview (Volts L-L), or Gen Phases (Volts L-N)
A phase generator inputs
and adjust PT Phase A scale until these values match
measured generator voltage on A phase With synchroniser in “check” mode, and a live bus, monitor the
synchroscope menu of the 6000 control for “phase angle”.
PT Phase B Scale
Monitor Voltage across open gen contactor/breaker or panel
Calibrates PT phase B voltage input
synchroscope for phase angle error between generator and
Monitor Gen Overview (Volts L-L), or Gen Phases (Volts L-N) bus.
and adjust PT Phase B scale until these values match
Adjust synchroscope calibration for lowest voltage across gen
measured generator voltage on A phase
breaker, or 12 o’clock reading on panel mounted synchroscope.
PT Phase C Scale
Battery VCO Gain
Calibrates PT phase C voltage input
Sets slope of battery VCO over operating range
Monitor Gen Overview (Volts L-L), or Gen Phases (Volts L-N)
Analog inputs to VCOs (Voltage Controlled Osc.)
and adjust PT Phase C scale until these values match
measured generator voltage on A phase
Freq.
CT Phase A Scale
(Hz)
Calibrates CT Phase A sensing of 6000 control

Load generator and monitor gen. currents in phase overview


menu.

Measure actual gen. currents with clamp on ammeter, or panel Analog Input
ammeter.

Calibrate phase A CT reading in phase overview. Used for Batt Volts, Water Temp (Ain2) and Oil Pressure (Ain1)
CT Phase B Scale Voltage Controlled Oscillators
Calibrates CT Phase B sensing of 6000 control

Load generator and monitor gen. currents in phase overview Increasing offset
menu.
Freq.
Measure actual gen. currents with clamp on ammeter, or panel
ammeter.
Decreasing offset
Calibrate phase B CT reading in phase overview.

CT Phase C Scale
Analog Input
Calibrates CT Phase C sensing of 6000 control

Load generator and monitor gen. currents in phase overview


menu.

Measure actual gen. currents with clamp on ammeter, or panel


ammeter. Increasing gain

Calibrate phase C CT reading in phase overview.

If CT polarity is reversed, that phase will read negative kW


Decreasing gain
when loaded in the Phase overview menu.

If CTs are on the incorrect phases, then KVAR readings in


phase overview will be off. Battery VCO Offset
Bus PT Scale Sets level, or offset of Battery VCO over operating range
Similar to Gen PT scaling, but this scale is for single phase bus Battery Voltage is a linear increasing type VCO function
PT input to the 6000 control.
Ain1 VCO Gain

10
Oil Pressure sensor input
! If maintenance is to be carried out on the generating set
0-200 ohm sensor on engine is a direct, mostly linear VCO then the battery negative should be disconnected at the
function battery.

Sets slope of oil pressure input to VCO frequency AUTO / Auto Start Position

Ain1 VCO Offset  Generating set awaits an external (Volt Free) start signal
indicating a mains failure from the changeover system.
Sets level, or offset of oil pressure input to VCO frequency Upon receiving this signal the generating set will start and
assume any load on the local bus.
Ain2 VCO Gain
 The generating set will continue supplying the load until the
Sets slope of water temp. input to VCO frequency start signal is removed.
Ain2 VCO Offset  Upon removal of this start signal the generating set will
stop immediately.
Sets level, or offset of VCO frequency to water temperature
slope

Water Temp VCO Sensor without shunt NOTE:

Sensor with shunt


• All load transfer functions and mains failure detection are
handled by an external changeover system.

VCO Any ‘Run-On’ or ‘Cooldown’ timers should be integrated into the


Freq. changeover system. The 6100 control system can be
programmed to perform the cooldown function itself if required
but must be requested prior to build.
TEST / Generating Set Test Position
Water Temperature  If selected the generating set will start and assume any
load on the local bus.
Shunt Resistor Switches 7 and 8 closed on SW-1 of 6000
control NOTE:

3.9 NetComm Dropouts • The 6100 control panel has no control over the load
The number of lost or corrupted network communications transfer and so the generating set can carry out a test
without load by using this switch position only if the
tolerated by the receiving unit.
changeover system used will not cause a load transfer
Excess numbers of NetComm Dropouts on network due to under these conditions.
faulty wiring, improper shielding, or improper setup will result in  If the mains fails while the generating set is running and a
the unit experiencing the dropouts to flash intermittently in the load transfer is initiated by the changeover system the
Sequencing Menu of the 6000 control. Typically set at 5 to 10 generating set will assume the load and run isochronously.
dropouts.
4. RUN / Generating Set Manual Run
Calibrated Unit
 Same as for ‘TEST’ position in this mode since the
When set for true, indicates unit has been factory calibrated. generating set has no control over the load transfer.
Requires level 4 security code to change.
6200 - Multiple Generating set, No Mains Parallel
3.10 6100 - Single Generating set, Automatic Mains Failure
4.1 Functional Description
Functional Description
In this mode of operation an external changeover system must
In this mode of operation an external changeover system must be used in conjunction with the 6000 Control System to handle
be used in conjunction with the 6000 Control System to handle all mains sensing and load transfer functions providing a volt
all mains sensing and load transfer functions providing a volt free start signal. In this mode the generators only parallel with
free start signal. other similarly equipped generating sets (up to a total of 8 sets).
Where there is a group of generating sets each set is given its
Normal Switch Positions own unique identifying number (1-8). There are two main
OFF / Generating Set off operational variants within the 6200 operating mode, i.e. Prime
Power and Automatic Mains Failure (AMF). Depending on the
 If selected while engine is running the generating set will configuration set-up the generating sets may be started
stop immediately. manually, start automatically if a machine in the running group
fails, start automatically according to load demand (load
NOTE: dependant sequencing) and, in the case of the AMF variant,
• The 6100 control system has no control over the load
start automatically on a failure of the mains supply.

transfer, therefore the load should be removed from the 4.2. Prime Power Variant - Normal Switch Positions
generating set before shutting down.
OFF / Generating Set Off
Any ‘Run-On’ or ‘Cooldown’ timers should be integrated
into the changeover system. The 6100 control system can  If selected while the engine is running the generating set
be programmed to perform the cooldown function itself if will ramp off load and stop.
required but must be requested prior to build.
NOTE:
 If selected while the engine is stopped will disable engine
starting. • If all generating sets are not running and there is load on
WARNING: the local bus the next available generating set in the
network may be sequenced on before the generating set
will initiate a stop sequence.

11
The 6200 control system has no control over the load transfer The generating set will now assume master status and
to/from the mains and so this should not be used to initiate sequence the lowest priority generating set offline if the
a manual load transfer. system load is less than the ‘Min Gen Load’ setpoint. The
generating set will continue running online until a shutdown
Any ‘Run-On’ or ‘Cooldown’ timers should be integrated into fault occurs or the control switch is turned out of ‘RUN’.
the changeover system. The 6200 control system can be
programmed to perform the cooldown function itself if  If selected with at least one generating set of a lower
required but must be requested prior to build. priority online the generating set will start, synchronise and
close to the local bus, soft load ramp and then load share
 If selected while the engine is stopped will disable engine with the other generating sets online. The lowest priority
starting. generating set may now sequence offline automatically if
the system load is less than the ‘Min Gen Load’ setpoint on
the active master generating set.
NOTE:
WARNING
• Leaving the control switch in the ‘RUN’ position will prevent
! if maintenance is to be carried out on the generating set this generating set from being sequenced offline.
Switching the control switch to the ‘AUTO’ position will
then the battery negative should be disconnected at the
battery itself. enable the automatic load dependant sequencing on this
generating set.
AUTO / Auto Start Position
 If selected with the engine stopped and other generating
 If selected while the system is dead and no generating sets of only higher priorities online the generating set will
sets are online the generating set will start and assume the start, synchronise and close to the local bus, soft load
load. ramp then load share with the other generating sets online.
The next lowest priority generating set online may be
 If selected while the engine is stopped with other sequenced offline if the system load is less than the ‘Min
generating sets of only lower priorities online the Gen Load’ setpoint on the active master generating set.
generating set will start, synchronise and close to the local
bus, soft load ramp then load share with the other NOTE:
generating sets online. The generating set will now
assume master status and sequence the lowest priority • Leaving the control switch in the ‘RUN’ position will prevent
generating set offline if the system load is less than the this generating set from being sequenced offline.
‘Min Gen Load’ setpoint. The generating set will continue Switching the control switch to the ‘AUTO’ position will
running online until a shutdown fault occurs or the control enable the automatic load dependant sequencing on this
switch is turned out of ‘AUTO’. generating set.
 If selected with at least one generating set of a lower Prime Power Variant - Additional Information
priority online the generating set will start, synchronise and
close to the local bus, soft load ramp then load share with In a Prime Power system with load dependant sequencing
the other generating sets online. The lowest priority enabled all generating sets must be turned to the ‘RUN’ position
generating set may now sequence offline automatically if on the control switch on startup. This will bring all generating
the system load is less than the ‘Min Gen Load’ setpoint on sets on line supplying the load and will allow the 6000 Control
the active master generating set. The generating set will System to initialise all load dependant sequencing correctly.
now revert to normal load dependant automatic sequencing After approximately 2 mins of running all generating sets can be
and will be brought on and offline by the active master placed in the ‘AUTO’ position for normal running.
generating set as required. While the generating sets are in load dependant sequencing
 If selected with other generating sets of only higher mode where the load dictates how many generating sets run.
priorities online the generating set will go directly into auto As the load increases then the number of sets increase and vice
sequencing and will not start unless the system load is versa. The generating sets have a pre-set starting priority as
greater than the ‘Max Gen Load’ setpoint on the active the load increases. As the load decreases they stop in reverse
master generating set. If this is the case the generating set order. The starting and stopping order sequence can be
will start, synchronise and close to the local bus, soft load changed by the operator at any time. Another feature in the
ramp then load share with the other generating sets online. automatic mode is that if a generating set stops because of a
The generating set will now revert to normal load fault then the next generating set in the sequence starts up and
dependant automatic sequencing and will be brought on synchronises automatically to the load. When the faulty
and offline by the active master generating set as required. generating set is repaired it will automatically take its place back
in the running sequence (see section on ‘AUTO’ switch
TEST / Generating Set Test Position position). The 6200 mode requires that there must be a
minimum of one generating set running.
 If selected while the engine is stopped the generating set
will start and run off load. The generating set will continue 4.3. AMF Variant - Normal Switch Positions
to run off load until the control switch is turned out of
‘TEST’. OFF / Generating Set Off

NOTE:  If selected while the engine is running the generating set will
ramp off load and stop.
• During this time the generating set will be unavailable for
NOTE:
automatic sequencing and will never close onto the load.
RUN / Generating Set Manual Run • If all generating sets are not running and there is load on
the local bus the next available generating set in the
 If selected while the system is dead and no generating network may be sequenced on before the generating set
sets are online the generating set will start and assume the will initiate a stop sequence.
load.
The 6200 control system has no control over the load
 If selected with the engine stopped and other generating transfer to/from the mains and so this should not be used
sets of only lower priorities online the generating set will to initiate a manual load transfer.
start, synchronise and close to the local bus, soft load
ramp then load share with the other generating sets online. Any ‘Run-On’ or ‘Cooldown’ timers should be integrated
into the changeover system. The 6200 control system can

12
be programmed to perform the cooldown function itself if  If selected while the engine is stopped with other
required but must be requested prior to build. generating sets of only lower priorities online and the
external start signal active the generating set will start,
If selected while the engine is stopped will disable engine synchronise and close to the local bus, soft load ramp then
starting. load share with the other generating sets online. The
generating set will now assume master status and
sequence the lowest priority generating set offline if the
WARNING system load is less than the ‘Min Gen Load’ setpoint. The
engine will continue to run until the control switch is turned
! If maintenance is to be carried out on the generating set out of ‘TEST’ and will remain online until the external start
signal is deactivated.
then the battery negative should be disconnected at the
battery itself.  If selected with at least one generating set of a lower
AUTO / Auto Start Position priority online and the external start signal active the
generating set will start, synchronise and close to the local
 If selected while the system is dead and no generating bus, soft load ramp then load share with the other
sets are online the generating set awaits an external (Volt generating sets online. The lowest priority generating set
Free) start signal indicating a mains failure from the may now sequence offline automatically if the system load
changeover system. is less than the ‘Min Gen Load’ setpoint on the active
Upon receiving this signal the generating set will start, master generating set. The generating set will now revert to
synchronise and close to the local bus, soft load ramp then normal load dependant automatic sequencing and will be
load share with the other generating sets online. The brought on and offline by the active master generating set
generating set will continue to run online for at least 5 as required. The engine will continue to run until the control
minutes then revert to normal load dependant automatic switch is turned out of ‘TEST’ and will be sequenced on
sequencing. and offline by the active master generating set as required.

 If selected while the engine is stopped with other  If selected with other generating sets of only higher
generating sets of only lower priorities online the priorities online, the engine is stopped, with the external
generating set awaits an external (Volt Free) start signal start signal active and the system load less than the ‘Min
indicating a mains failure from the changeover system. Gen Load’ setpoint the generating set will start and run off
Upon receiving this signal the generating set will start, load. The generating set will continue to run off load until
synchronise and close to the local bus, soft load ramp then the control switch is turned out of ‘TEST’ or the system
load share with the other generating sets online. The load becomes greater than the ‘Max Gen Load’ setpoint on
generating set will now assume master status and the active master generating set. If this is the case the
sequence the lowest priority generating set offline if the generating set will start, synchronise and close to the local
system load is less than the ‘Min Gen Load’ setpoint. The bus, soft load ramp then load share with the other
generating set will continue running online until a shutdown generating sets online. The generating set will now revert
fault occurs or the control switch is turned out of ‘AUTO’. to normal load dependant automatic sequencing and will be
brought on and offline by the active master generating set
 If selected with at least one generating set of a lower as required. The engine will continue to run until the control
priority online the generating set awaits an external (Volt switch is turned out of ‘TEST’ and will be sequenced on
Free) start signal indicating a mains failure from the and offline by the active master generating set as required.
changeover system.
Upon receiving this signal the generating set will start,  If selected with other generating sets of only higher
synchronise and close to the local bus, soft load ramp then priorities online, the engine is stopped, the external start
load share with the other generating sets online. The signal active and the system load greater than the ‘Max
lowest priority generating set may now sequence offline Gen Load’ setpoint the generating set will start,
automatically if the system load is less than the ‘Min Gen synchronise and close to the local bus, soft load ramp then
Load’ setpoint on the active master generating set. The load share with the other generating sets online. The
generating set will now revert to normal load dependant generating set will now revert to normal load dependant
automatic sequencing and will be brought on and offline by automatic sequencing and will be brought on and offline by
the active master generating set as required. the active master generating set as required. The engine
will continue to run until the control switch is turned out of
 If selected with other generating sets of only higher ‘TEST’ and will be sequenced on and offline by the active
priorities online the generating set awaits an external (Volt master generating set as required.
Free) start signal indicating a mains failure from the
changeover system. NOTE:
Upon receiving this signal the generating set will go directly
into auto sequencing and will not start unless the system • If it is required to disable the generating set from going
load is greater than the ‘Max Gen Load’ setpoint on the online the local alternator output circuit breaker should be
active master generating set. If this is the case the placed in the open position.
generating set will start, synchronise and close to the local
bus, soft load ramp then load share with the other RUN / Generating Set Manual Run
generating sets online. The generating set will now revert
 If selected while the system is dead and no generating
to normal load dependant automatic sequencing and will be
sets are online the generating set will start and assume any
brought on and offline by the active master generating set
load on the local bus.
as required.
 If selected with the engine stopped and other generating
TEST / Generating Set Test Position
sets of only lower priorities online the generating set will
 If selected while the engine is stopped and the external start, synchronise and close to the local bus, soft load
start signal is not active the generating set will start and run ramp then load share with the other generating sets online.
off load. The generating set will continue to run off load The generating set will now assume master status and
until the control switch is turned out of ‘TEST’ or the sequence the lowest priority generating set offline if the
generating set receives the external start signal. system load is less than the ‘Min Gen Load’ setpoint. The
Upon receiving this signal the generating set will generating set will continue running online until a shutdown
synchronise and close to the local bus, soft load ramp then fault occurs or the control switch is turned out of ‘RUN’.
load share with the other generating sets online. The
 If selected with at least one generating set of a lower
generating set will continue to run online for at least 5
priority online the generating set will start, synchronise and
minutes then revert to normal load dependant automatic
close to the local bus, soft load ramp and then load share
sequencing.

13
with the other generating sets online. The lowest priority
generating set may now sequence offline automatically if • While the generating set is in the ‘OFF’ position all AMF
the system load is less than the ‘Min Gen Load’ setpoint on functions are disabled.
the active master generating set.
 If selected while the generating set is supplying the site
 If selected with the engine stopped and other generating load and the mains is dead the generating set will continue
sets of only higher priorities online the generating set will supplying the site load until the mains returns or a
start, synchronise and close to the local bus, soft load shutdown fault occurs.
ramp then load share with the other generating sets online. When the mains returns the generating set will wait for the
The next lowest priority generating set online may be duration of the mains stable delay timer then synchronise
sequenced offline if the system load is less than the ‘Min to the mains, close the mains breaker, soft unload ramp,
Gen Load’ setpoint on the active master generating set. open the generator breaker, cooldown and stop.
NOTE:  If selected while the generating set is supplying the site
load and the mains has returned after a mains failure but
• Leaving the control switch in the ‘RUN’ position will prevent the mains stable delay timer has not timed out the
this generating set from being sequenced offline. generating set will synchronise to the mains, close the
Switching the control switch to the ‘AUTO’ position will mains breaker, soft unload ramp, open the generator
enable the automatic load dependant sequencing on this breaker, cooldown and stop.
generating set.
 If selected while the engine is stopped will disable disable
AMF Variant - Additional Information engine starting.

In a Prime Power system with load dependant sequencing NOTE:


enabled all generating sets must be turned to the ‘RUN’ position
on the control switch on startup. This will bring all generating • While in the ‘OFF’ position all active mains breaker control
sets on line supplying the load and will allow the 6000 Control is disabled. If the mains fails during this time and the
System to initialise all load dependant sequencing correctly. mains breaker subsequently opens the control system will
After approximately 2 mins of running all generating sets can be not attempt to close the breaker until the control switch is
placed in the ‘AUTO’ position for normal running. turned to the ‘AUTO’ position.
While the generating sets are in load dependant sequencing
mode where the load dictates how many generating sets run. It is therefore strongly advised that if the generating set is
As the load increases then the number of sets increase and vice to be taken out of service for prolonged periods of time that
versa. The generating sets have a pre-set starting priority as the maintenance switch inside the control panel should be
the load increases. As the load decreases they stop in reverse switched to the ‘Maintenance’ position. This will re-close
order. The starting and stopping order sequence can be the mains breaker on a short term mains failure.
changed by the operator at any time. Another feature in the
automatic mode is that if a generating set stops because of a WARNING
fault then the next generating set in the sequence starts up and
synchronises automatically to the load. When the faulty
generating set is repaired it will automatically take its place back
! If maintenance is to be carried out on the generating
set then the battery negative should be disconnected
in the running sequence (see section on ‘AUTO’ switch
at the battery itself.
position). The 6200 mode requires that there must be a
minimum of one generating set running. AUTO / Auto Start Position

5. 6300 - Automatic Synchronising of One Generating Set with  If selected while the system is dead and the mains is
Mains supplying the load, the generating set is operating in AMF
mode and will not start.
5.1 Functional Description  If the mains supply goes outside spec the generating set
In addition to the automatic mains failure function (with soft load will start, open the mains breaker and assume the site
retransfer), this variant can operate in base load mode, peak load. The generating set will continue to run online until the
lopping mode or soft load transfer mode. The operating mode is mains returns or a shutdown fault occurs.
pre-programmed at the factory and must be specified when When the mains returns the generating set will wait for the
ordering. duration of the mains stable delay timer then synchronise
In all variants the 6300 Control System must have full control of to the mains, close the mains breaker, soft unload ramp,
both the generator and mains breakers with state feedback open the generator breaker, cooldown and stop.
provided for each by means of an auxiliary contact.  If an exercise timer is fitted to the generating set leaving
5.2. Base Load Operation the control system in the ‘AUTO’ position will enable the
generating set paralleling via the timer.
In this mode the generating set may be manually started. It will
automatically synchronise to the mains grid and take up load to TEST / Generating Set Test Position
a pre-set value (usually the full output of the generating set). If  If selected while the engine is stopped and the mains
there is insufficient local load for the generating set then it will supplying the load the generating set will start and run off
export its excess power to the mains. load. The generating set will continue to run off load until
With the generating set in the AUTO position the system will the control switch is turned out of ‘TEST’ or the mains
operate in AMF Mode and will start and supply the site load in supply goes outside specification.
the event of a mains failure. The generating set will perform a
soft load retransfer (closed retransfer) of the load back to the  If the mains supply goes outside spec the generating set
mains supply on return of the mains. will open the mains breaker and assume the site load. The
generating set will continue to run online until the mains
5.3. Base Load Variant - Normal Switch Positions
returns or a shutdown fault occurs.
OFF / Generating Set Off When the mains returns the generating set will wait for the
duration of the mains stable delay timer then synchronise
 If selected while the engine is running and the generating to the mains, close the mains breaker, soft unload ramp,
set is in Baseload the generating set will ramp off load, open the generator breaker and continue running offline.
disconnect the generating set, cooldown (if required) and
stop. NOTE:
NOTE:

14
mains breaker, soft unload ramp, open the generator
• If it is required to disable the generating set from going breaker, cooldown and stop.
online in the event of a mains failure the local alternator  If selected while the engine is stopped will disable disable
output circuit breaker should be placed in the open engine starting.
position.
NOTE:
RUN / Generating Set Manual Run
 If selected while the engine is stopped with the mains • While in the ‘OFF’ position all active mains breaker control
supplying the load the generating set will start, synchronise is disabled. If the mains fails during this time and the
with the mains, close the generator breaker and soft load mains breaker subsequently opens the control system will
ramp to a preset ‘Baseload’ level against the mains supply. not attempt to close the breaker until the control switch is
turned to the ‘AUTO’ position.
NOTE:

• If the site load is less than this Baseload level then the
It is therefore strongly advised that if the generating set is to be
taken out of service for prolonged periods of time that the
excess power will be exported to the mains utility. maintenance switch inside the control panel should be
switched to the ‘Maintenance’ position. This will re-close
the mains breaker on a short term mains failure.
 If the mains fails while the generating set is running in
parallel with the mains utility the 6300 control system will
WARNING:
disconnect the mains supply and assume the full site load.

NOTE:
! If maintenance is to be carried out on the generating set
then the battery negative should be disconnected at the
• It may be necessary to use an external means of mains battery itself.
failure detection. Consult the local mains provider for exact AUTO / Auto Start Position
requirements.
 If selected while the system is dead and the mains
5.4. Peak Shaving Operation supplying the load the generating set is operating in AMF
mode and will not start.
With the control switch in the AUTO position and the Process
switch in the ON position generating set will start on a signal  If the mains supply goes outside spec the generating set
from a pre-set time clock and run in parallel with the mains will start, open the mains breaker and assume the site
supply. After synchronising with the mains an external watt load. The generating set will continue to run online until the
transducer on the mains provides a signal of the load on the mains returns or a shutdown fault occurs.
mains. The 6300 uses this signal to adjust the load on the
generating set so that a minimum load is kept on the mains and When the mains returns the generating set will wait for the
the rest is supplied by the generating set. This continues until duration of the mains stable delay timer then synchronise
the generating set is at its maximum load then any further to the mains, close the mains breaker, soft unload ramp,
loading is put on the mains. open the generator breaker, cooldown and stop.
Turning the control switch to the RUN position at any time will  If an exercise timer is fitted to the generating set leaving
manually start the generating set and carry out the above the control system in the ‘AUTO’ position will enable the
operation. The generating set will run in parallel with the mains generating set paralleling via the timer.
until the control switch is returned to the OFF position or to the
AUTO position with the time clock start signal off. TEST / Generating Set Test Position

With the generating set in the AUTO position the system will  If selected while the engine is stopped and the mains
operate in AMF Mode and will start and supply the site load in supplying the load the generating set will start and run off
the event of a mains failure. The generating set will perform a load. The generating set will continue to run off load until
soft load retransfer (closed retransfer) of the load back to the the control switch is turned out of ‘TEST’ or the mains
mains supply on return of the mains. supply goes outside specification.

5.5. Peak Shaving Variant - Normal Switch Positions  If the mains supply goes outside spec the generating set
will open the mains breaker and assume the site load. The
OFF / Generating Set Off generating set will continue to run online until the mains
returns or a shutdown fault occurs.
 If selected while the engine is running and the generating When the mains returns the generating set will wait for the
set is in main parallel the generating set will ramp off load, duration of the mains stable delay timer then synchronise
disconnect the generating set, cooldown (if required) and to the mains, close the mains breaker, soft unload ramp,
stop. open the generator breaker and continue running offline.
NOTE:

• While the generating set is in the ‘OFF’ position all AMF


functions are disabled.
 If selected while the generating set is supplying the site NOTE:
load and the mains is dead the generating set will continue
supplying the site load until the mains returns or a
shutdown fault occurs.
• If it is required to disable the generating set from going
online in the event of a mains failure the local alternator
 When the mains returns the generating set will wait for the output circuit breaker should be placed in the open
duration of the mains stable delay timer then synchronise position.
to the mains, close the mains breaker, soft unload ramp, RUN / Generating Set Manual Run
open the generator breaker, cooldown and stop. If selected while the engine is stopped with the mains supplying
 If selected while the generating set is supplying the site the load the generating set will start, synchronise with the
load and the mains has returned after a mains failure but mains, close the generator breaker and soft load ramp to a pre-
the mains stable delay timer has not timed out the set import power level from the mains supply. The generating
generating set will synchronise to the mains, close the set will maintain this import power level as the site load varies.

NOTE:

15
not attempt to close the breaker until the control switch is
• It may be necessary to fit external protection to prevent the turned to the ‘AUTO’ position.
generating set from exporting power to the mains utility.
Consult the local mains provider for exact requirements. It is therefore strongly advised that if the generating set is
to be taken out of service for prolonged periods of time that
 If the mains fails while the generating set is running in the maintenance switch inside the control panel should be
parallel with the mains utility the 6300 control system will switched to the ‘Maintenance’ position. This will re-close
disconnect the mains supply and assume the full site load. the mains breaker on a short term mains failure.

NOTE: WARNING

• It may be necessary to use an external means of mains ! If maintenance is to be carried out on the generating
failure detection. Consult the local mains provider for exact set then the battery negative should be disconnected
requirements. at the battery itself.
5.6. Soft Transfer Variant - Normal operation: AUTO / Auto Start Position
With the control switch in the AUTO position and the Process  If selected while the system is dead and the mains
switch in the ON position generating set will start on a signal supplying the load the generating set is operating in AMF
from a pre-set time clock and run in parallel with the mains mode and will not start.
supply. After synchronising with the mains an external watt
transducer on the mains provides a signal of the load on the  If the mains supply goes outside spec the generating set
mains. The 6300 uses this signal to adjust the load on the will start, open the mains breaker and assume the site
generating set to the point where zero load is being supplied by load. The generating set will continue to run online until the
the mains then opens the mains breaker so assuming the full mains returns or a shutdown fault occurs.
site load. On removal of the time clock start signal the When the mains returns the generating set will wait for the
generating set will resynch with the mains supply and perform a duration of the mains stable delay timer then synchronise
soft load retransfer (closed retransfer) of the site load back to to the mains, close the mains breaker, soft unload ramp,
the mains. open the generator breaker, cooldown and stop.

Turning the control switch to the RUN position at any time will  If an exercise timer is fitted to the generating set leaving
manually start the generating set and carry out the above the control system in the ‘AUTO’ position will enable the
operation. The generating set will continue supplying the site generating set paralleling via the timer.
load until the control switch is returned to the OFF position or to TEST / Generating Set Test Position
the AUTO position with the time clock start signal off.
 If selected while the engine is stopped and the mains
With the generating set in the AUTO position the system will supplying the load the generating set will start and run off
operate in AMF Mode and will start and supply the site load in load. The generating set will continue to run off load until
the event of a mains failure. The generating set will perform a the control switch is turned out of ‘TEST’ or the mains
soft load retransfer (closed retransfer) of the load back to the supply goes outside specification.
mains supply on return of the mains.
 If the mains supply goes outside spec the generating set
will open the mains breaker and assume the site load. The
5.7. Soft Transfer Variant - Normal Switch Positions
generating set will continue to run online until the mains
returns or a shutdown fault occurs.
OFF / Generating Set Off
When the mains returns the generating set will wait for the
duration of the mains stable delay timer then synchronise
 If selected while the engine is running and the generating to the mains, close the mains breaker, soft unload ramp,
set is in main parallel the generating set will ramp off load, open the generator breaker and continue running offline.
disconnect the generating set, cooldown (if required) and
stop. NOTE:
NOTE: • If it is required to disable the generating set from going
• While the generating set is in the ‘OFF’ position all AMF online in the event of a mains failure the local alternator
output circuit breaker should be placed in the open
functions are disabled. position.
 If selected while the generating set is supplying the site RUN / Generating Set Manual Run
load and the mains is dead the generating set will continue
supplying the site load until the mains returns or a  If selected while the engine is stopped with the mains
shutdown fault occurs. supplying the load the generating set will start, synchronise
When the mains returns the generating set will wait for the with the mains, close the generator breaker and soft load
duration of the mains stable delay timer then synchronise ramp to the point where there is no load being imported
to the mains, close the mains breaker, soft unload ramp, from the mains at which point the control system will open
open the generator breaker, cooldown and stop. the mains breaker and assume the full site load.
 If selected while the generating set is supplying the site NOTE:
load and the mains has returned after a mains failure but
the mains stable delay timer has not timed out the
generating set will synchronise to the mains, close the
• It may be necessary to fit external protection to prevent the
generating set from exporting power to the mains utility.
mains breaker, soft unload ramp, open the generator Consult the local mains provider for exact requirements.
breaker, cooldown and stop.
 If selected while the engine is stopped will disable disable  If the mains fails while the generating set is running in
engine starting. parallel with the mains utility the 6300 control system will
disconnect the mains supply and assume the full site load.
NOTE:

• While in the ‘OFF’ position all active mains breaker control NOTE:
is disabled. If the mains fails during this time and the
mains breaker subsequently opens the control system will
• It may be necessary to use an external means of mains
failure detection. Consult the local mains provider for exact
requirements.

16
6. Automatic Synchronising of Multiple Generating sets with WARNING:
Mains
! If maintenance is to be carried out on the generating
6.1. Functional Description set then the battery negative should be disconnected
at the battery itself.
In addition to the automatic mains failure function (with soft load
retransfer), this variant can operate in base load mode, peak AUTO / Auto Start Position
lopping mode or soft load transfer mode. The operating mode is
pre-programmed at the factory and must be specified when  If selected while the generating sets are stopped and the
ordering. mains is supplying the load, the generating set will enter
This section describes the functionality of the ‘standard’ system AMF mode and will not start.
which consists of up to 4 generating sets paralleling with each
 If the mains supply goes outside spec the generating set
other onto a local generator bus and with a single mains supply.
will start, open the mains breaker and assume the site
This system is fitted with a mains breaker, feeder breaker and a
load. The generating set will continue to run online until the
separate generator breaker for each generating set. For a
mains returns or a shutdown fault occurs.
detailed outline of the system wiring consult the relevant
When the mains returns the generating set will wait for the
drawings and / or a member of the Electrical Drawing Office.
duration of the mains stable delay timer then synchronise
The Electrical Drawing Office should also be consulted if the
to the mains, close the mains breaker, soft unload ramp,
requirements of the proposed installation dictate changes in the
open the generator breaker, cooldown and stop.
basic configuration of the system as this may require significant
modification to the control system philosophy.  If an external start signal is applied via the PLC panel the
generating set will start and enter RUN mode (see section
6.2. Base Load Operation
6.3.4).
In this mode the generating sets may be manually started either
TEST / Generating Set Test Position
by an external start signal starting all generating sets which are
in ‘AUTO’ or individually by selecting ‘RUN’ on the control  If selected while the engine is stopped and the mains
switch. Any generating sets told to run in baseload will supplying the load the generating set will start and run off
automatically synchronise to the mains grid and take up load to load. The generating set will continue to run off load until
a pre-set value (usually the full output of the generating set). If the control switch is turned out of ‘TEST’, the mains supply
there is insufficient local load for the generating sets then goes outside specification or the external start signal is
surplus power over and above the site load will be exported to received.
the mains.
 If the mains supply goes outside spec the generating set
With the generating sets in the AUTO position the system will will open the mains breaker and assume the site load. The
operate in AMF Mode and will start and supply the site load in generating set will continue to run online until the mains
the event of a mains failure. In his case the system will open returns or a shutdown fault occurs. When the mains returns
the feeder breaker and attempt to start all generating sets the generating set will wait for the duration of the mains
simultaneously. After all available generating sets have come stable delay timer then synchronise to the mains, close the
on-line and have closed to the local bus the feeder breaker will mains breaker, soft unload ramp, open the generator
close. The number of generating sets required to be on-line breaker and continue running offline.
before the feeder breaker will close can be customised for each
individual application. The generating set will perform a soft  If an external start signal is received the generating set will
load retransfer (closed retransfer) of the load back to the mains parallel to the mains supply and go into RUN mode (see
supply on return of the mains. section 6.3.)

NOTE:

• If it is required to disable the generating set from going


6.3. Base Load Variant - Normal Switch Positions online in the event of a mains failure the local alternator
output circuit breaker should be placed in the open
OFF / Generating Set Off position.
 If selected while the engine is running and the generating
set is in Baseload the generating set will ramp off load, RUN / Generating Set Manual Run
disconnect from the local bus, cooldown (if required) and
 If selected while the engine is stopped with the mains
stop.
supplying the load the generating set will start, synchronise
with the mains, close the generator breaker and soft load
NOTE:
ramp to a pre-set ‘Baseload’ level against the mains
• While the generating set is in the ‘OFF’ position all AMF supply.
and externally triggered starting functions are disabled.
NOTE:
 If selected while the generating set is supplying the site
load and the mains is dead the generating set will continue • If the site load is less than this Baseload level then the
supplying the site load until the mains returns or a excess power will be exported to the mains utility.
shutdown fault occurs.
When the mains returns the generating set will wait for the  If the mains fails while the generating set is running in
duration of the mains stable delay timer then synchronise parallel with the mains utility the 6400 control system will
to the mains, close the mains breaker, soft unload ramp, disconnect the mains supply and assume the full site load.
open the generator breaker, cooldown and stop.
NOTE:
 If selected while the generating set is supplying the site
load and the mains has returned after a mains failure but • It may be necessary to use an external means of mains
the mains stable delay timer has not timed out the failure detection. Consult the local mains provider for exact
generating set will synchronise to the mains, close the requirements.
mains breaker, soft unload ramp, open the generator
breaker, cooldown and stop. 6.4 Peak Shaving Operation
 If selected while the engine is stopped will disable engine With the control switch in the AUTO position and the Process
starting. switch in the ON position generating set will start on a signal
from a pre-set time clock or externally applied run signal and run

17
in parallel with the mains supply. After synchronising with the  If the mains supply goes outside spec the generating set
mains an external watt transducer provides a signal which is will open the mains breaker and assume the site load. The
representative of the loading applied to the mains supply. The generating set will continue to run online until the mains
6400 uses this signal to adjust the load on the generating set so returns or a shutdown fault occurs.
that a minimum load is kept on the mains. This continues until
the generating set is at its maximum load after which any further When the mains returns the generating set will wait for the
loading is put on the mains. duration of the mains stable delay timer then synchronise
to the mains, close the mains breaker, soft unload ramp,
Turning the control switch to the RUN position at any time will open the generator breaker and continue running offline.
manually start the generating set and carry out the above
operation. The generating set will run in parallel with the mains NOTE:
until the control switch is returned to the OFF position or to the
AUTO position with the external start signal removed. • If it is required to disable the generating set from going
With the generating set in the AUTO position the system will online in the event of a mains failure the local alternator
operate in AMF Mode and will start and supply the site load in output circuit breaker should be placed in the open
the event of a mains failure. The generating set will perform a position.
soft load retransfer (closed retransfer) of the load back to the
mains supply on return of the mains. RUN / Generating set Manual Run

6.5 Peak Shaving Variant - Normal Switch Positions  If selected while the engine is stopped with the mains
supplying the load the generating set will start, synchronise
OFF / Generating Set Off with the mains, close the generator breaker and soft load
 If selected while the engine is running and the generating ramp to a preset import / export power level from the mains
set is in main parallel the generating set will ramp off load, supply. The generating set will maintain this import /
disconnect the generating set from the local bus, cooldown export power level as the site load varies.
(if required) and stop.
NOTE:
NOTE:
• It may be necessary to fit external protection to prevent the
• While the generating set is in the ‘OFF’ position all AMF generating set from exporting power to the mains utility.
functions are disabled. Consult the local mains provider for exact requirements.

 If selected while the generating set is supplying the site


load and the mains is dead the generating set will continue  If the mains fails while the generating set is running in
supplying the site load until the mains returns or a parallel with the mains utility the 6400 control system will
shutdown fault occurs. disconnect the mains supply and assume the full site load.
When the mains returns the generating set will wait for the
duration of the mains stable delay timer then synchronise
to the mains, close the mains breaker, soft unload ramp, NOTE:
open the generator breaker, cooldown and stop.
• It may be necessary to use an external means of mains
 If selected while the generating set is supplying the site failure detection. Consult the local mains provider for exact
load and the mains has returned after a mains failure but requirements.
the mains stable delay timer has not timed out the
generating set will synchronise to the mains, close the 6.6 Soft Transfer Variant - Normal operation:
mains breaker, soft unload ramp, open the generator With the control switch in the AUTO position and the Process
breaker, cooldown and stop. switch in the ON position generating set will start on a signal
 If selected while the engine is stopped will disable engine from a preset time clock or externally applied start signal and
starting. run in parallel with the mains supply. After synchronising with
the mains an external watt transducer on the mains provides a
WARNING: signal of the load on the mains. The 6400 uses this signal to
! if maintenance is to be carried out on the generating
adjust the load on the generating set to the point where zero
load is being supplied by the mains then opens the mains
set then the battery negative should be disconnected breaker so assuming the full site load. On removal of the time
at the battery itself. clock start signal the generating set will resynch with the mains
AUTO / Auto Start Position supply and perform a soft load retransfer (closed retransfer) of
the site load back to the mains.
 If selected while the generating sets are stopped and the
mains is supplying the load, the generating set will enter Turning the control switch to the RUN position at any time will
AMF mode and will not start. manually start the generating set and carry out the above
operation. The generating set will continue supplying the site
 If the mains supply goes outside spec the generating set load until the control switch is returned to the OFF position or to
will start, open the mains breaker and assume the site the AUTO position with the external start signal removed.
load. The generating set will continue to run online until the
mains returns or a shutdown fault occurs. NOTE:
When the mains returns the generating set will wait for the
duration of the mains stable delay timer then synchronise • If only one generating set is turned into the RUN position
to the mains, close the mains breaker, soft unload ramp, the site load may exceed the maximum generating set load
open the generator breaker, cooldown and stop. in which case the generating set will never reach the zero
load transfer point and will not disconnect the mains
 If an external start signal is applied via the PLC panel the supply.
generating set will start and enter RUN mode (see section With the generating set in the AUTO position the system
6.5.). will operate in AMF Mode and will start and supply the site
load in the event of a mains failure. The generating set will
TEST / Generating set Test Position perform a soft load retransfer (closed retransfer) of the load
back to the mains supply on return of the mains.
 If selected while the engine is stopped and the mains
supplying the load the generating set will start and run off 6.7 Soft Transfer Variant - Normal Switch Positions
load. The generating set will continue to run off load until
the control switch is turned out of ‘TEST’ or the mains OFF / Generating set Off
supply goes outside specification.

18
 If selected while the engine is running and the generating with the mains, close the generator breaker and soft load
set is in main parallel the generating set will ramp off load, ramp to the point where there is no load being imported
disconnect the generating set from the local bus, cooldown from the mains at which point the control system will open
(if required) and stop. the mains breaker and assume the full site load.

NOTE: NOTE:

• While the generating set is in the ‘OFF’ position all AMF • It may be necessary to fit external protection to prevent the
functions are disabled. generating set from exporting power to the mains utility.
Consult the local mains provider for exact requirements.
 If selected while the generating set is supplying the site
load and the mains is dead the generating set will continue  If the mains fails while the generating set is running in
supplying the site load until the mains returns or a parallel with the mains utility the 6300 control system will
shutdown fault occurs. disconnect the mains supply and assume the full site load.
When the mains returns the generating set will wait for the
duration of the mains stable delay timer then synchronise NOTE:
to the mains, close the mains breaker, soft unload ramp,
open the generator breaker, cooldown and stop. • It may be necessary to use an external means of mains
 If selected while the generating set is supplying the site failure detection. Consult the local mains provider for exact
load and the mains has returned after a mains failure but requirements.
the mains stable delay timer has not timed out the
generating set will synchronise to the mains, close the 7. Alarm / Event Indication and Logging
mains breaker, soft unload ramp, open the generator
breaker, cooldown and stop. Fault conditions on the 6000 Series Control Panel are set as
 If selected while the engine is stopped will disable disable warnings, alarms, soft shutdowns and hard shutdowns.
engine starting. Warnings flash the ALARM light only, alarms energise the
audible alarm and flash the ALARM lamp, soft shutdowns
WARNING unload the generator, open the breaker and perform a cooldown
cycle if required. Hard shutdowns immediately open the breaker
! If maintenance is to be carried out on the generating and shut the generating set down. All alarms are logged with a
set then the battery negative should be disconnected timestamp in the ALARM / EVENT LOG. These settings are
at the battery itself. intrinsic to the setup parameters in the software and can only be
changed with suitable security clearance. When a hard
shutdown fault is sensed, the alarm lamp illuminates, the audible
alarm is energised and the generating set is automatically shut
AUTO / Auto Start Position
down immediately. The audible alarm will remain energised until
 If selected while the generating sets are stopped and the the ALARM RESET pushbutton is pressed. The engine remains
mains supplying the load the generating set will enter in locked out until the fault has been acknowledged. The alarm
AMF mode and will not start. lamp will flash until the enter ( ) pushbutton is pressed while in
the ALARM / EVENT LOG. This will acknowledge the alarm and
 If the mains supply goes outside spec the generating set allow the generator to start but will not clear it from the log. The
will start, open the mains breaker and assume the site alarm may be cleared from the log by pressing the ALARM
load. The generating set will continue to run online until the RESET pushbutton while in the ALARM/EVENT LOG subject to
mains returns or a shutdown fault occurs. technician level or higher security clearance. The possible fault
When the mains returns the generating set will wait for the conditions available for sensing are dependant on the particular
duration of the mains stable delay timer then synchronise operating mode of the generating set. See earlier section for a
to the mains, close the mains breaker, soft unload ramp, list of all available alarms/shutdowns.
open the generator breaker, cooldown and stop.
 If an external start signal is applied via the PLC panel the 8. Remote Control and Monitoring Via a PC:
generating set will start and enter RUN mode (see section
6.7.). 8.1 System Outline

TEST / Generating set Test Position The PC-Tools package is available in two main forms, which are
subdivided into 5 variants in total. A brief description of each is
 If selected while the engine is stopped and the mains given below:
supplying the load the generating set will start and run off
load. The generating set will continue to run off load until  PC options:
the control switch is turned out of ‘TEST’ or the mains
PC1: This option offers monitoring of the 6000 series
supply goes outside specification.
system only via a direct hardwired connection to the control
 If the mains supply goes outside spec the generating set system.
will open the mains breaker and assume the site load. The
PC2: This option offers monitoring and control of the 6000
generating set will continue to run online until the mains series system via a direct hardwired connection to the
returns or a shutdown fault occurs.
control system.
When the mains returns the generating set will wait for the
duration of the mains stable delay timer then synchronise  TEL options:
to the mains, close the mains breaker, soft unload ramp,
open the generator breaker and continue running offline. TEL1: This option offers monitoring of the 6000 series
system only via a standard telephone line.
NOTE:
TEL2: This option offers monitoring and control of the 6000
• If it is required to disable the generating set from going series system via a standard telephone line.
online in the event of a mains failure the local alternator TEL3: This option offers monitoring and control of the 6000
output circuit breaker should be placed in the open series system via a standard telephone line with fault alert
position. callback.
RUN / Generating set Manual Run The PC1 and PC2 options use a separate control box per
 If selected while the engine is stopped with the mains control system to interface between the RS-232 serial
supplying the load the generating set will start, synchronise communications port of the monitoring PC and the RS-422

19
communications network used by the 6000 series control
panels. The GP 6000 software in conjunction with the Servlink
software then utilises the information transmitted by this
communication path to allow users to monitor or control various
aspects of the 6000 series control panel from the computer.
The TEL1, TEL2 and TEL3 options also use a separate but
different control box per system to interface between the RS-
422 network used by the 6000 series control panels and the
telephone line.
Each 6000 series control system should have its own dedicated
communications path, e.g. one hard wired connection with one
PC1 interface panel per 6100 or 6300 panel with PC1option,
and one telephone line with one PC1 interface panel per 6200
or 6400 system with PC1 option.
Each control box requires a mains supply but does contain
battery backup to enable uninterrupted remote communications
even in the event of a mains and/or generator system failure.
The control box used with the TEL3 option differs from that used
with the TEL1 and TEL2 options in that it also incorporates the
fault callback unit. This control box will require two dedicated
telephone lines, one for data transfer and one for the recorded
The operator can now carry out any of the functions accessible
message callback facility.
by using the membrane keypad on the hardware control itself.
This is done by simply clicking on the appropriate button on the
front panel display, which will cause the 6000 series control to
8.2 Functional Description react in exactly the same manner as if the button was pressed
locally.
The GP 6000 software duplicates the front panel of the 6000
series hardware platform. All the monitoring information which In addition to the Monitoring version of the GP6000 software
can be obtained from the hardware can also be accessed by the there is also a version which gives the remote operator the
GP 6000 software in a format which is identical to that of the capability to simulate the operation of the control switch, panel
hardware. This makes the software mounted emergency stop button, and the speed/volts
raise/lower buttons. This version is used with the PC2, TEL2
very familiar to those accustomed to the 6000 controller keypad
and TEL3 options. An example of the front panel display for this
functions and LCD readout displays.
version is shown below:
There are two main information display sections within the GP
6000 software. These are the ‘Master Situation Monitor’ and the
‘Front Panel Display’. The ‘Master Situation Monitor’ displays
the essential information from up to eight of the individual control
panels in the system. The parameters displayed are:
 Network Address
 Network Priority
 Present kW loading of the generating set
 Alarm Status (ALARM or OK)
An example of a typical 3 generating set 6200 system display is
shown below:

As it can be seen, this version is identical to the monitoring only


version with the exception of the added control buttons on the
right side of the display.
These control buttons not only allow the remote operator to
perform all the basic control functions but also indicate the
current state of these control inputs, i.e. if the panel mounted
emergency stop is locked on or has been released etc.
The control system works by acknowledging a change of state
of any of these switch inputs, whether triggered locally or
In this example the Master Situation Monitor is showing an remotely, as the last valid control input. This means that there
alarm condition on generating set number 3. Highlighting is no overriding priority put on either the local or remote inputs,
generating set number 3, and then clicking on the front panel and so it is quite conceivable that the local control switch could
display icon in the lower right corner of the Master Situation be in the AUTO position but due to the remote operator pressing
Monitor brings up the front panel display for generating set the RUN button, the generating set will be operating in the RUN
number 3: mode. It should be noted however that the status as

20
indicated on the remote display will always match the Each TEL1 and TEL2 option requires one dedicated, analogue
current operating mode of the controller. telephone line.
Each TEL3 option requires two dedicated, analogue telephone
The Emergency Stop control operates in a slightly different lines.
manner however due to safety constraints. In this case the
local panel mounted emergency stop always has priority while NOTE:
pressed. This prevents the remote operator from starting the
generating set if the local emergency stop button is still locked
on due to the occurrence of a dangerous or potentially
• Connection of the TEL1, TEL2 and TEL3 option interface
boxes to a digital telephone line, such as used on some
dangerous situation. Once the local emergency stop button has PBX switchboard systems, may result in permanent
been released the alarm can be reset and the generating set damage to the interface system.
started either locally or remotely.
8.4 Equipment Supplied With Each Option:
It should also be noted that in the case of a 6100, or 6200
system that as all mains failure and load transfer functions are PC1 Option
performed by an external changeover system the PC2, TEL2
and TEL3. Options cannot be used to initiate a manual load 1 x PC interface box.
transfer/ re-transfer of the load to/from the mains supply. 1 x 9-pin serial cable.
1 x GP6000 Monitoring Software package.
8.3 Hardware Specifications
PC2 Option
Communications:
RS-422 protocol 1 x PC Interface box.
9600 Baud (fixed maximum) 1 x 9-pin serial cable.
No Parity 1 x GP6000 Monitoring and Control Software package.
1 Stop Bit

TEL1 Option
Computer Requirements:
1 x TEL1 interface box.
Minimum: 1 x GP6000 Monitoring Software package.
PC compatible running Windows 95 or Windows NT 4.0 and 1 x Telephone cable (cable connectors fitted will depend on
above, 3 MB hard drive space. country).

Recommended: TEL2 Option

100 MHz Pentium PC, 16 MB RAM, 3 MB hard drive space, 1 x TEL2 interface box.
running Windows 95 or Windows NT 4.0 and above. 1 x GP6000 Monitoring and Control Software package.
1 x Telephone cable (cable connectors fitted will depend on
Modem Requirements (for TEL1, TEL2 and TEL3 options country).
only):
TEL3 Option
Remote PC end:
1 x TEL3 interface box with integral fault alert callback.
9600 Baud Capability (minimum) 1 x GP6000 Monitoring and Control Software package.
2 x Telephone cables (cable connectors fitted will depend on
8 Data Bits country).
No Parity
9. Initial Startup and Commissioning
1 Stop Bit
Recommended: 9.1 Test Procedure for Single Generating set Systems.

Multitech MT1932ZDX-K, MT2834ZDX-K, MT2834ZPX-Internal Pre-Startup Instructions

US-Robotics Sportster 14.4 Vi Fax/Modem, Sportster 14.4  Check all electrical connections.
Fax/Modem, Sportster Voice 33.6 Fax/Modem, Courier Dual
 Check engine oil and coolant level.
Std, Courier HST.
 Ensure that the control switch is in the OFF position.
Miracom Courier HST
 Power up the 6000 series control panel.
Megahertz CC3144/CC4144 PCMCIA
Xircom PS-CEM28 range  The unit will carry out a RAM check after which it will
display the application code version installed in the unit.
NEC (AT&T) 14.4 Kbps Data/Fax Modem Verify that this is the latest version. If not, download the
latest version. The unit should now display the ‘Control
Tornado FM144E Overview’ screen.
PC1 and PC2 communications path.  Enter security code.
Standard RS-422 protocol communications.  Check all program setpoints.
Recommended cable: 6-core (3 x twisted pair), overall  Set synchroniser to ‘Run’.
screened, min core diameter of 0.5mm2.
 Set ‘Load Control Mode’ to ‘Droop’.
Maximum length: 1km (special attention must be paid to cable
routing to minimise interference).  For multiple unit systems set ‘Number of Units’ to ‘Single’.
Connection Method: daisy chain (parallel looped) with PC Ensure that the generating set is connected to a isolated bus or
interface box at one end of the line - screen earthed at one load bank.
place only but interconnected.
Start engine using the ‘RUN’ position on the control switch.
TEL1, TEL2, and TEL3 communications path.
Check operation of Emergency stop button.
Hardwired RS-422 connection as in PC1, PC2 option.
Re-start generating set by clearing Emergency stop fault while
control switch still in ‘RUN’.

21
Check the RPM reading on the ‘Engine Overview’ screen.  Connect screen to panel earth at one end only ensuring
that the screen connection is carried right through to the
Set up electronic governor (if fitted). opposite end of the system.
Ensure that generator breaker closes.  Ensure proper RS-485 termination by setting DIP switches
Ensure that generating set is running in ‘Droop’ mode by looking 4, 7, and 8 on switch bank SW-3 (located beside J-8) are in
at the ‘Synchroscope’ screen. the ‘ON’ position on both units at the end of the
communication path.
Check that the Volts and Speed Bias outputs on the ‘I/O Status’
screen are both zero.  Ensure DIP switches 4-8 on switch bank SW-3 are in the
‘OFF’ position on all other units.
Check the generator output voltage on the load bank.
Ensure all control switches is in the ‘OFF’ position.
Calibrate the Line-Neutral voltages as seen on the ‘Gen Phases’
screen. Power up all 6000 series panels.

Adjust output voltage at AVR to specified voltage. Enter security code.

Verify operation of the Volts raise/lower switches (if applicable). Set up all controllers as follows:

 Verify that ‘Volts Bias’ reading in ‘I/O Status’ screen  Set synchroniser to ‘Check’ on all but first machine.
changes when raise/lower switches are pressed.
 Set synchroniser to ‘Run’ on fist machine only.
 Set ‘Voltage Ramp Time’ if necessary.
 Set ‘Number of units’ setpoint to ‘Multiple’.
Verify operation of the Speed raise/lower switches (if
applicable).  Set ‘Load Control Mode’ to ‘Normal’.
 Verify that ‘Speed Bias’ reading in ‘I/O Status’ screen  Disable any Loss of Mains detection.
changes when raise/lower switches are pressed.
 Set ‘Load Raise Rate’ and ‘Load Lower Rate’ if necessary.  Set up network addresses and priorities ensuring that
network addresses are all unique.
If the 6000 series control panel is controlling the generating
set volts:  Disable closure of all generating set breakers, except first
unit, by disconnecting the close signal from the control
 Set AVR ‘Droop’ potentiometer to halfway. panel.
 Set AVR ‘Trim’ pot to give +/- 10% output voltage swing for Turn all control switches to Auto and verify network
+/- 100% voltage bias output (by using the Volts communications:
raise/lower switches).
 All generating sets in ‘AUTO’ should be shown in the
If Mains PT connected: ‘Control Overview’ screen after the ‘UNIT:’ prompt.
 Check mains voltage readout (U:) in ‘Synchroscope’  If any controllers are missing from the display, check that
screen. there is no duplication of network priorities, check all RS-
Calibrate if necessary. 485 cable connections and that the end of line termination
resistors are set correctly (see above).
Apply a small load to the generating set.
 If all of the above are correct, but any controllers are still
Check CT polarity by observing current readouts in the ‘Gen missing from the display, increase the ‘NetComm
Phases’ screen. Dropouts’ setpoint to 10.
Load generating set to full load.  If communications still not correct, replace faulty controller
and repeat all previous setup procedures.
Check current readouts on ‘Gen Phases’ screen.
Turn all control switches back to ‘OFF’.
Calibrate current readouts if necessary.
Turn control switch on first unit to ‘RUN’.
Remove load.
Verify that first unit starts and closes onto the bus.
Turn control switch to ‘OFF’.
Calibrate Synchroniser on all remaining units.
Verify that generating set shuts down correctly.
 Turn control switch on next unit to ‘RUN’.
Set ‘Load Control Mode’ to ‘Normal’.
 Change to the ‘Synchroscope’ screen.
Start generating set by turning the control switch to ‘RUN’.
 Verify that the ‘Mains/Bus’ sensing changes to ‘BUS’.
Check operation of all shutdowns and alarms.
Load up generating set to full load and complete full load test.  Verify that the ‘Dead Bus’ display changes to ‘NO’.

Remove load and shut down generating set.  Verify the Bus Volts readout, ‘U:’ on screen, is correct and
calibrate if necessary.
Test Procedure for Multiple Generating set Systems.
 Verify synching by measuring volts across generating set
Test each individual unit in single generating set mode as breaker.
outlined above.
 When satisfied that synchroniser is correct, shut down
Connect all generating sets to common local bus. generating set and repeat steps 1-7 for next unit.
Set up RS-485 communication lines. Check synchroniser operation on next unit:
 Connect proper RS-485 twisted pair, overall screened  Ensure that first unit is running and closed onto the bus.
cable of characteristic impedance of 120 ohms between all
generating sets in system.  Apply a load of approx. 1/2 full load capacity of first
generating set.
 If RS-485, 120 ohm cable is not available standard twisted
pair, overall screened cable should suffice.  Turn the control switch on the next generating set to
‘RUN’.

22
 Confirm phase/voltage matching and synchroniser Take units off line one at a time ensuring that bus load does not
operation. exceed full load capacity of remaining units.

 Verify generating set breaker closure.  Verify unload ramping.


Check ‘Load Control’:  Verify unload trip.
 Verify load ramping operation.  Verify cooldown operation.
 Verify that ramp rate is reasonable. Carry any further application specific operational tests required.

 Reduce ‘Load Control Gain’ setting if unstable during


ramping.
 Verify that operating mode changes to ‘ISOCH’ when
ramping complete.
 Increase bus load to approximately 1/2 full load capacity of
all generating sets currently on-line.
 Verify real load sharing operation.
 Reduce ‘Load Share Gain’ if unstable during load sharing.
 Verify Var/PF sharing (if applicable).
 Reduce ‘VAR/PF Gain’ if unstable during Var/PF sharing.
Repeat Synchroniser and Load Control operational checks for
all remaining generating sets.
Once all sets are on line and correctly set up, increase load on
bus to full system load capacity.
Run on full load for 5-10 mins to verify long term stability.

23
10. Troubleshooting

10.1 Control Hardware and I/O


Problem Probable Cause Corrective Action

Unit does not power up No input power supply Check +12 Vdc or +24 Vdc power supply
Input power supply reversed Ensure proper polarity of power supply to
GCP-1
Discrete inputs don’t show active in I/O STATUS Faulty wiring of discrete input switches Verify wiring of discrete input switches
screen when switches are activated
Displayed generator voltages are very small Faulty wiring of generator Potential Verify wiring of generator Potential
Transformers(PT’s) Transformers(PT’s)
Generator PT inputs are improperly Calibrate the appropriate PT input
calibrated channel(s). See section 1.10 Calibration of
Control Inputs and Outputs
I/O STATUS shows relay(s) is energized, but action(i.e. Faulty wiring of relay output contacts Verify wiring of relay output contacts
alarm) does not occur
Generator voltage fluctuates or is unstable at no load AVR dynamics are improperly set up Tune the AVR dynamics for stable
on generator operation. See AVR manufacturer’s
instruction manual for more details
Voltages or currents displayed by GCP-1 are different GCP-1 PT inputs are inaccurately Calibrate the appropriate PT input
than measured parameter calibrated channel(s). See section 1.10 Calibration of
Control Inputs and Outputs

10.2 Engine Control / Sensing Parameters


Problem Probable Cause Corrective Action

Start command(i.e. test or run with load) does not start Configuration menu has not been Enter the configuration set points in the
engine accepted or entered properly Configuration menu such that all “*” and “#”
symbols are removed from the lower two
lines of the display. See section 1.3.4
Description of set points for more details.
An active alarm condition exists Commit or reset alarm condition(s). See
section 1.3.2 Description of Screens
Relay output contacts are not properly Verify wiring of relay output contacts
connected to engine starter, fuel solenoid
Starter motor stays engaged after engine starts Crank cutout set point in Engine control Set CRANK CUTOUT set point to
menu is to large appropriate value. See section 1.3.4
Description of set points
Inadequate MPU signal to GCP-1 input Verify MPU wiring, and that adequate MPU
signal exists at input to GCP-1 control
Engine starts, but starter re-engages while engine is Inadequate MPU signal to GCP-1 input Verify MPU wiring, and that adequate MPU
running signal exists at input to GCP-1 control
Engine speed is unstable when unit is at no load Speed control dynamics are improperly set Tune the speed control dynamics for stable
up operation. See speed control
manufacturer’s instruction manual for more
details
When crank command is issued, GCP-1 loses power Battery is too weak for the current demand Install a higher capacity battery or a more
and conducts a reset and RAM test of the starter motor efficient starter motor
Faulty wiring of power supply to the GCP- Verify wiring of power supply to the GCP-1
1 control control

24
10.3 Synchronisation
Problem Probable Cause Corrective Action

Unit never adequately matches phase Synchronizer Mode set point in Set synchronizer Mode to appropriate
synchroscope menu set to PERMISSIVE setting. See section 1.3.4 Description of
Set points
Synchronizer dynamics in synchroscope Tune synchronizer dynamics. See section
menu are improperly set up 1.3.4 Description of Set points
Synchronizer displays small phase difference, but Generator A phase PT input is L-L and bus Verify that Generator A phase PT input bus
measured phase difference is large A phase PT input is L-N or vice versa A phase PT input are the same form (i.e. L-
N or L-L)
Bus and/or generator PT inputs are not A Verify that Bus and generator PT inputs
phase are A phase
Synchronizer improperly calibrated Calibrate synchronizer. See section 1.10
Calibration of Control Inputs and Outputs
Synchronizer matches phase, but never closes Synchronizer Mode set point in Set synchronizer Mode to appropriate
breaker/contactor synchroscope menu is set to CHECK setting. See section 1.3.4 Description of
Set points
Dwell time set point in synchroscope menu Reduce Dwell Time set point in
is too large synchroscope menu. See section 1.3.4
Description of Set points
Synchronizer displays matched phase, but measured Generator or bus PT is reversed polarity Verify correct polarity of Generator and bus
phase difference is ~180 degrees, or when breaker (faulty wiring) PT inputs
closes it crash parallels the set 180 degrees out of
phase
Unit won’t close to dead bus Multiple unit system with DEADBUS ENABLE DEADBUS CLOSING set point in
CLOSING set point in configuration menu configuration menu. See section 1.3.4
set to DISABLED Description of Set points
Synchronizer set point is set to CHECK Set synchronizer Mode to appropriate
setting. See section 1.3.4 Description of
Set points

Synchronizer won’t voltage match VOLTAGE MATCHING set point in ENABLE the VOLTAGE MATCHING set
synchroscope menu is DISABLED point in synchroscope menu. See section
1.3.4 Description of Set points
Synchronizer does not voltage match within spec. Generator A phase PT and/or Bus A Calibrate the Generator A phase PT and
phase PT input(s) are inadequately Bus A phase PT inputs. See section 1.10
calibrated Calibration of Control Inputs and Outputs
Voltage matching tolerance set point in Appropriately set the Voltage matching
synchroscope menu is too large tolerance set point in synchroscope menu.
See section 1.3.4 Description of Set points

10.4 Breaker Close / Open Control


Problem Probable Cause Corrective Action

When generator set is in synchronization, the Synchronizer set to CHECK Set synchronizer Mode to appropriate setting.
breaker never closes See section 1.3.4 Description of Set points

Faulty wiring causing the relay output to not Verify wiring of the relay output contacts.
make connection to the breaker
Dwell time set point in the synchroscope menu is Reduce Dwell time set point in the
too long synchroscope menu. See section 1.3.4
Description of Set points
Contactor closes for a brief moment and then C B CONTROL set point in configuration menu Appropriately set the C B CONTROL set point
opens is set for BREAKER in configuration menu. See section 1.3.4
Description of Set points
C B HOLD TIME set point in synchroscope Increase C B HOLD TIME set point in
menu is too short synchroscope menu. See section 1.3.4
Description of Set points
Faulty wiring on C.B. aux contacts Verify wiring of C.B. aux contacts to GCP-1
input
Breaker close relay stays energized when a close C B CONTROL set point is set for Appropriately set the C B CONTROL set point

25
command is given and never issues an open CONTACTOR in configuration menu. See section 1.3.4
command Description of Set points

10.5 Real Load Control


Problem Probable Cause Corrective Action

kW for a phase(s) reads negative. Current transformer(CT) has reversed Verify/reverse polarity of current
polarity transformer for effected channel(s)
NOTE: engine generator set must be off
to safely open circuit a current
transformer
Unit carries improper proportion of real load during Rated kW set point in configuration menu Appropriately set Rated kW set point in
isochronous load sharing set at incorrect value configuration menu. See section 1.3.4
Description of Set points
A proportional dc speed error exists on the Adjust speed setting of speed control to
speed control unit (no-load speed not set to match the bus frequency. If unit is carrying
match bus frequency) too little load, the speed setting needs
increased. If unit is carrying too much load,
the speed setting needs decreased.
Real load control is unstable when paralleled with the Real load control dynamics in real load Tune Real load control dynamics in real
mains source control menu are improperly set up load control menu. See section 1.3.4
Description of Set points
Process control operation causes overload or reverse PROCESS ACTION set point in process Appropriately set PROCESS ACTION set
power control menu set for incorrect action point in process control menu. See section
1.3.4 Description of Set points
Loading and/or unloading is too fast/slow Load and/or unload ramp rates in the real Appropriately increase/decrease the Load
load control menu are set incorrectly and/or unload ramp rates in the real load
control menu. See section 1.3.4 Description
of Set points
Engine speed/load has an instability that fluctuates very Speed control dynamics are improperly set Tune the speed control dynamics for stable
quickly. up operation. See speed control
manufacturer’s instruction manual for more
details

10.6 Reactive Load Control


Problem Probable Cause Corrective Action

Phase power factors do not agree. Two of the three CT’s are connected to incorrect phase Verify CT’s are connected to the
phases are extremely far out of range inputs appropriate input terminals
NOTE: engine generator set must be off
to safely open circuit a current
transformer
Unit carries improper proportion of reactive load during Rated kVA set point in the configuration Appropriately set the Rated kVA set point in
isochronous load sharing menu is set at incorrect value the configuration menu. See section 1.3.4
Description of Set points
Generator A phase PT input(s) are Calibrate the Generator A phase PT
improperly calibrated input(s) of the generator set(s). See section
1.10 Calibration of Control Inputs and
Outputs
Reactive load control is unstable when paralleled with the Reactive load control dynamics in the Tune the Reactive load control dynamics in
mains source reactive load control menu are improperly the reactive load control menu. See section
set up 1.3.4 Description of Set points
Unit maintains a constant VAR load rather than a VAR/PF set point in the reactive load Appropriately set the VAR/PF set point in
constant power factor when paralleled with the mains control menu is set to VAR CONTROL the reactive load control menu. See section
source 1.3.4 Description of Set points
Unit maintains a constant power factor load rather than a VAR/PF set point is set to PF CONTROL Appropriately set the VAR/PF set point in
constant VAR when paralleled with the mains source the reactive load control menu. See section
1.3.4 Description of Set points
Multiple generator sets are unstable when VAR/PF VOLTS RAMP TIME set point in reactive Appropriately set the VOLTS RAMP TIME
sharing at light loads load control menu is not adjusted properly set point in reactive load control menu. See
section 1.3.4 Description of Set points
Droop Current Transformer not properly Verify the connection of the Droop Current
connected to AVR Transformer to the AVR. See AVR
manufacturer’s instruction manual for more
details

26
10.7 Sequencing
Problem Probable Cause Corrective Action

Unit number(s) does not show up in the sequencing switch in manual position Switch unit(s) to the Auto switch active
order in the sequencing screen/unit doesn’t auto position. See section 1.1.5 DC
sequence inputs/outputs
Automatic mode set point in the configuration ENABLE the Automatic mode set point in
menu set to disabled the configuration menu. See section 1.3.4
Description of Set points
Unit has an active alarm Commit or reset alarm condition(s). See
section 1.3.2 Description of Screens
RS-485 Network not connected at unit(s) Verify that the RS-485 network is
connected to all GCP-1 controls in system.
RS-485 Network is inadequately terminated Verify that the RS-485 Network is correctly
terminated. See section 1.9.6 Inter-Control
Communications (RS-485)
When system load is large enough to require additional NEXT GENERATING SET DELAY set point in Increase NEXT GENERATING SET
gen-sets, more than one set is sequenced on line sequencing menu is too short DELAY set point in sequencing menu. See
section 1.3.4 Description of Set points
MAX START TIME set point in sequencing Increase MAX START TIME set point in
menu is too short sequencing menu. See section 1.3.4
Description of Set points
When system load is small enough to take additional REDUCED LOAD DELAY set point in Increase REDUCED LOAD DELAY set
sets off line, more than one set is sequenced off line sequencing menu is too short point in sequencing menu. See section
1.3.4 Description of Set points
MAX STOP TIME set point in sequencing Increase MAX STOP TIME set point in
menu is too short sequencing menu. See section 1.3.4
Description of Set points

10.8 Mains / Bus Sensing


Problem Probable Cause Corrective Action

Unit(s) do not respond to loss of mains Shutdown/alarm set points for mains Appropriately set mains high/low frequency
sensing not set for LOSS OF MAINS and high/low voltage set points in
shutdown/alarm menu. See section 1.3.4
Description of set points
Unit(s) do not have an active auto switch Switch unit(s) to the Auto switch active
input position. See section 1.1.5 DC
inputs/outputs
Unit does not recognize when mains are in spec. Set points for mains high/low frequency Increase Mains high frequency and voltage
and high/low voltage in shutdown/alarm and decrease mains low frequency and
menu are set too tight for sensing when voltage set points in the shutdown/alarm
mains are in spec menu. See section 1.3.4 Description of Set
points

10.9 Communications
Problem Probable Cause Corrective Action

A unit number(s) does not show up in the sequencing RS-485 Network is inadequately Verify that the RS-485 Network is correctly
order in the sequencing screen terminated terminated. See section 1.9.6 Inter-Control
Communications (RS-485)
RS-485 Network not connected at unit(s) Verify that the RS-485 Network is
connected to the GCP-1 RS-485 input at
all units
RS-485 network is connected with reverse Verify the polarity of the RS-485 network
polarity at one or more units on all units
If a unit with the network termination is powered down, +5Vdc power supply is not linked between Verify that the +5Vdc power supply is
communications become unreliable or completely units (inadequate wiring) linked between all units
cease

27
11. Definition of Terms

AMF Automatic Mains Failure. The ability of a control to


detect, and take action on a mains failure Breaker A device used to connect one power source to a
condition. The GCP–1, which has AMF load, or to another power source. Breakers can be
capabilities, can be programmed to sense a loss either manually or automatically operated, and will
of mains condition based on mains voltage, usually contain overcurrent protection. The GCP–
frequency, or a sudden load surge on a generator 1 controls motorized breakers by issuing a
operating in parallel with the mains. The action momentary breaker close output to energize the
taken by the GCP–1 when it senses a mains breaker coil, and a separate breaker open output
failure can be programmed for either an alarm to shunt trip the breaker to open it.
action, or a standby power action where all
generators start and tie to the load after the failed
mains have been isolated from that load. Contactor A device used to connect one power source to a
load, or to another power source. Contactors are
Automatic A control mode used by the GCP–1 to activate typically automatic in operation, and are energized
Control several automatic functions within the control. for closure from an external source. The GCP–1
These functions, which are dependent upon controls contactors by issuing a contactor close
program setpoints and system configuration, are output to close the contactor, and removing this
Loss of Mains detection, Automatic Sequencing, output to open the contactor.
and Automatic dead bus closing, Automatic
control also effectively connects those GCP–1 Dead Bus The ability of a generator breaker control device to
units in automatic to the Local Operating Network Closing sense, and safely close onto a load which has no
(LON). other generators or sources of power tied to it.
Dead Bus Closing must not allow two generators
to attempt closure to the dead bus at the same
Auto Switch A discrete input to the control which will initiate
time, since an out of phase paralleling situation
automatic operation of the GCP–1.
would likely occur. The GCP–1 uses its Local
Operating Network to ensure safe dead bus
ATS Automatic Transfer Switch. A device which closing among all units tied to this network. The
isolates the mains upon a sensed fault in the units have a single dead bus token, which allows
mains, or through manual operation. The ATS the unit possessing it to close to the dead bus.
selects a secondary power source, such as a Only one token exists on the network, so there is
diesel generator to supply the load when the no possibility of multiple units closing to the dead
mains have been isolated. The ATS will also re- bus simultaneously. Dead Bus Closing is always
connect the load to the mains when they are re- active in single unit configurations.
established and stable. The GCP–1 control has
ATS functions. Droop A reduction in the reference of a controlled
parameter as the amplitude of that parameter
Audible An alarm condition used by the GCP–1 for various increases (negative feedback). The GCP–1 uses
Alarm alarm settings which will cause the audible alarm Kilowatt Droop as a manual means of loading the
relay output to energize when reaching or generator when paralleling to another generator,
exceeding the alarm parameters. or to the mains.

Automatic The automatic addition, or subtraction of Dwell A term used to describe the amount of time
Sequencing generators to/from the load based on Time required during synchronization in which one
predetermined load levels being crossed for power source is within a specified phase angle
specific periods of time. Automatic sequencing is window of another source it is synchronizing to.
a function of a multiple generator system which is
operating in load sharing mode isolated from the
mains, or process control mode in parallel with the Hard A shutdown condition used by the GCP–1 for
mains. Shutdown various alarm settings which will cause the unit to
immediately open its generator breaker if on load,
and shut down by immediately opening its fuel
AVR Automatic Voltage Regulator. A device which solenoid output when reaching or exceeding the
controls the field excitation of an AC generator in alarm parameters.
such a way as to maintain a specific voltage level
over the operating load range of the generator.
Isochronous A term which is used to describe a generator set
The GCP–1 control biases the voltage setting of
which will maintain its frequency at a constant
the AVR to voltage match during synchronization
level as the load on that generator changes. The
and to control reactive load during load share and
GCP–1 typically uses isochronous load control
mains parallel operation.
when in load sharing, or when operating as a
single unit. This assures a constant frequency
Base A term used to describe a generator loading under all generator loads which are within the
Load condition in which the generator is paralleled to capacity of the generator.
another source of power, typically the mains, and
Inverse Time A time delay used for over current and reverse
loaded to a fixed kW level. The generator
Delay power detection, which utilizes both time and
maintains this kW level regardless of load on the
amplitude of the condition to determine the active
Mains.
trip level. The inverse time delay accounts for
rapid high amplitude conditions to cause a trip, as
well as long duration low amplitude conditions.

28
load as required starting at the highest network
Isolated Bus A bus which is electrically isolated from the mains. priority (lowest numerical value), and adding units
of lower priority (higher numerical value) as the
load on that system increases above certain
KVA Kilovolt-Amps. The power rating of the generator defined limits. Automatic sequencing will also
set KVA is determined by multiplying the rated remove units from the load in a reverse order of
voltage of the generator by the rated current. that used for sequencing units on load, that is from
lowest priority (highest numerical value) to highest
priority (lowest numerical value). In addition to all
KVAR Kilovolt-Amps Reactive. Reactive load is this, the unit with the highest network priority on
produced by a phase angle differential between the network is considered the master, and all
the volts and the amps of the generator. KVAR other units with lower priorities are slaves to that
can either be a product of inductive or capacitive master.
loads when operating on an isolated bus, or can
be produced by the generator when operating in
parallel with another power source such as the No Parallel An operating mode of the GCP–1 which will not
mains. allow the generators to operate in parallel with the
mains under any circumstances. All transitions to
and from the mains are completed using an open
kW Kilowatts. Watts are the product of the voltage of transition action.
the generator and the current, which is produced
within the voltage cycle. kW load is resistive in
nature.
Parallel To synchronize and close an operating generator
to another generator, or to the mains.

Load Typically the kW load on the generator at any Power A right triangle which is used to determine the
given time. Triangle amplitude relationship between KVA, KW, and
KVAR

Load Surge A condition in which a step load on the generator, A switch input which selects a mode of control
which is operating in a mains parallel mode (base Control used while in parallel with the mains. When
load or process) above a certain amplitude can be operating in process control, the GCP–1 receives
used to trigger a Loss of Mains condition. a 4-20 mA, or 1-5 VDC input from an external
transducer. This transducer monitors a variable
which is affected by the generator operation.
Loss of A condition in which the sensed mains PT input to Variables such as imported power to a site,
Mains the GCP–1 falls below certain voltage and/or exported power to the mains, exhaust
frequency setpoints for a given period of time. temperature, and fuel gas pressure levels are
Load Surge can also be used to detect a Loss of typical for monitoring with a transducer. The
Mains condition. The GCP–1 can be configured to GCP–1 uses an internal reference level for the
trigger a Loss of Mains (LOM) reaction to these process input, and compares this reference to the
conditions, and provide on site power generation transducer input.The GCP then raises or lowers
to supplement the load until such time as the the amount of load on the generator to maintain
mains return and are stable. the process transducer input to the referenced
value.
Mains To synchronize and close an operating generator
Parallel to the mains. The GCP–1 can be configured for Proportional A mode of load control used by the GCP–1 while
Mains Parallel operation. Load Sharing operating multiple units on an isolated bus.
Proportional Load Sharing measures the total KVA
capacity of all the units on the bus and divides the
Master The Highest Priority unit in an operating automatic total KVA load on the bus by this capacity. This
system. The Master Control controls load sharing, value is then sent over the network as a load
VAR/PF sharing, sequencing, synchronization to reference for all units operating in parallel on the
the mains, mains breaker closure/opening, and bus. The result of this is the ability of various KVA
multiple unit starting. rated units operating at their respective proportion
of the total load on the bus. This allows consistent
load sharing among units of various sizes
throughout their entire operating load range.
Manual A switch input to the GCP–1 which puts the
control in a manual operating mode. When in
Run With A discrete input to the GCP–1 which signals the
manual, the GCP–1 does not communicate with
Load unit to operate the generator on load. The way that
other units on the network, and if in a multiple unit
the control puts the generator on load depends
system, will not issue a dead bus closing
upon software configuration, and the type of
command. Being in manual also cancels any Loss
system the GCP–1 is configured for.
of Mains detection for that particular unit.

Network A unique address assigned to each unit, which is Slave A GCP–1 with lower network priority (Higher
Address operating in an automatic system. The network numerical value) than the master.
address is that particular units “name” on the
network so that it can be properly identified by
Soft A shutdown condition used by the GCP–1 for
other units operating on the same network.
Shutdown various alarm settings which will cause the unit to
softly unload and cooldown when reaching or
Network A unique number assigned to each unit operating exceeding the alarm parameters.
Priority in automatic on the network. Network priority
defines the sequence in which units will be taken
on/off load when operating in an automatic
sequencing configuration (load sharing or process Soft Transfer A Load Control Mode of the GCP–1 which allows
control). Automatic sequencing will place units on the unit, or group of units to transfer power from

29
the mains to the on site generators. Upon
reaching either a base load reference, or process
control reference level, the GCP–1 will issue a
command to open the mains breaker. This results
in a complete transition of power from the mains to
the on site generators.

Synchronize To match the frequency, phase angle, and voltage


of a generator to another power source such as a
generator or the mains. This will allow a safe
smooth breaker closure of that generator to the
power source. The GCP–1 uses Phase and
Voltage Matching to ensure there is a minimum of
potential across the breaker prior to closure.

Test A discrete input to the GCP–1 which is used to


start the engine for test and initial start check out.
The test input is also used with the run with load
or process inputs, and a software setpoint, to put
the GCP–1 into a soft transfer mode.

VAR/PF The ability to control a level of VAR or PF on a


Control generator while in parallel with the mains. The
GCP–1 has VAR/PF control features which allow
the user to set a desired VAR or PF level on the
generator while in parallel with the mains. The
VAR or PF level is maintained by changing the
excitation level of the generator. This is
accomplished by changing the voltage reference
level of the AVR from the GCP1.

VAR/PF The ability to share the VAR and PF load on


Sharing multiple units operating on an isolated bus. Like
load sharing, the GCP–1 VAR/PF sharing
measures the VARs of the load on the isolated
bus, and divides this value by the total VAR
capacity of the generators tied to the load. A
proportional VAR/PF level is then maintained
between all units tied to the load based on their
rated VAR capacity.

30

You might also like