Professional Documents
Culture Documents
Dermaga Multi Purposed PT Jhonlin Group: Electrical Consumption List and Power Balanced
Dermaga Multi Purposed PT Jhonlin Group: Electrical Consumption List and Power Balanced
Voltage
ID Equipment Equipment Full Load
Rev. No Description Load Factor Eff Current Power
Continues Intermittent Standby
Num Tag No. Rating Factor
(FLC)
ber
kW kW Dec DEC A Cos a kW kVAR kVA A kW kVAR kVA A kW kVAR kVA A
1 LDP 6.00 4.50 7.50 11.40
2 LED 1000 W-01 380 1.00 1.25 0.8 0.8 1.90 0.8 1.00 0.75 1.25 1.90
3 LED 1000 W-02 380 1.00 1.25 0.8 0.8 1.90 0.8 1.00 0.75 1.25 1.90
4 LED 1000 W-03 380 1.00 1.25 0.8 0.8 1.90 0.8 1.00 0.75 1.25 1.90
5 LED 1000 W-04 380 1.00 1.25 0.8 0.8 1.90 0.8 1.00 0.75 1.25 1.90
6 LED 1000 W-05 380 1.00 1.25 0.8 0.8 1.90 0.8 1.00 0.75 1.25 1.90
7 LED 1000 W-06 380 1.00 1.25 0.8 0.8 1.90 0.8 1.00 0.75 1.25 1.90
Normal Load = (1 x Total Continues Load) + (0.5 x Total Inttermittent Load) Normal = 6.00 kW 1.06 kVAR 7.06 kVA 10.72 A
Peak Load = Normal Load + (0.1 x Total Standby Load) Peak Load = 6.00 kW 1.06 kVAR 7.06 kVA 10.72 A
Demand Load = Peak Load x 1.25 Demand Load = 7.50 kW 1.32 kVAR 8.82 kVA 13.41 A