Professional Documents
Culture Documents
IGA225 Integrated Governor & Actuator: Installation
IGA225 Integrated Governor & Actuator: Installation
Dimensions:
Internet Connection Smart VU Software [mm]
Computer
www.governors-america.com in
134
5.27
A computer and an internet connection will be required to download and then 26
1.03 117
run GAC’s SmartVU software.
A 4.63 A
PERFORMANCE
Available Torque 105
2.2 ft-lb max (2.7 Nm) 4.15
(Without Return Spring)
Max Angular Travel 25° ±1° CW/CCW
153
Isochronous Operation ± 0.25% 6.01
ENVIRONMENTAL
Ambient Temperature -40° to 85°C (-40 to 180°F) 9 104
.34 4.10
Relative Humidity Up to 95% D.62 SPOTFACE 90
2 PLACES 3.53
All Surface Finishes Fungus Proof and Corrosion Resistant
INPUT / OUTPUT
Supply 12-24 VDC Battery Systems (6.5 to 33 VDC)
Polarity Negative Ground (Case Isolated)
SECTION A-A
Power Consumption 70mA max. Continuous Plus Actuator Current 26
1.03
Speed Sensor Signal 1.0 -120 VRMS
Load Share / Synchronizer Input 0 -10 VDC ( 5V nominal, reversed, 107Hz / V Max)
Reverse Power Protection Yes
Transient Voltage Protection 60V
Overspeed Rated to 2A DC
119
RELIABILITY 4.69
Vibration 7G, 20-100 Hz
Shock 20G Peak
Testing 100% Functional Testing
2 - - -
DIAGRAM 1 FUEL LEVER AT MID FUEL POSITION
3 Magnetic Pickup (+) #20 AWG * Ground to Terminal 10
* 0 - 10 V Range, 5V Nominal,
4 Aux Input #20 AWG
Reverse Polarity
5 Speed Select A #20 AWG * Ground to Enable
6 Speed Select B #20 AWG * Ground to Enable
7 RS-232 Enable #20 AWG * Connect to ground to enable RS232
8 Overspeed Output #16 AWG * 2A Max
* 5K Ω Resistive or
9 Variable Speed Input #20 AWG
0-5 VDC selectable in software
Ground / Battery Pwr (-) Battery Twisted Pair to Magnetic
10 #16 AWG
/ Magnetic Pickup (-) Speed Pickup
For proportional actuators to operate with non-linear systems, it is important A 15 amp fuse must be installed in
to obtain a non-linear relationship between actuator stroke and fuel delivery. 11 Battery Power (+) #16 AWG the positive battery lead to protect
Carbureted, PT Pumps (CUMMINS), or other non-linear fuel systems require against any overload or short circuit
a non-linear fuel linkage configuration as illustrated in Diagram 2. A non-linear * 120 Ohm Resistor Built-In, Jumper
fuel system results when more engine power is developed for a given stroke at 12 CAN Termination #20 AWG
to CAN L #13
positions of low fuel settings rather than at high fuel settings. In this case the
13 (CAN L / RS232 TX) #20 AWG
levers should be parallel at full load. * Twist Wires 14 turns per foot.
14 (CAN H / RS232 RX) #20 AWG
DIAGRAM 2 FUEL LEVER AT FULL FUEL POSITION RECOMMENDATIONS
1. Shielded cable should be used for all external connections to the IGA
control. One end of each shield, including the speed sensor shield,
should be grounded to a single point on the IGA case.
Fuse
15 AMP Max
IGA Mating Connector Basic Wiring
- Battery +
12/24 VDC
14 13 12 11 10
9 8 7 6
5 4 3 2 1
In general, the linkage should be adjusted so that the fuel control lever minimum
and maximum fuel stops are used rather than the actuator internal mechanical +
stops. The actuator should be adjusted so that it operates over at least one half Magnetic Speed
Pick-Up -
(12 degrees) of its available travel.
IGA225
9 9 9 9
Setup Connection Menu
IGA225
IGA225
Case
5 4 3 2 1
CAN L CAN H 9 8 7 6
Main Menu Once the engine has been started, the linkage can be optimized by temporarily
inserting an ammeter in one of the wires between the speed control unit and the
actuator or by measuring the voltage across the actuator. Measure the actuator
current or voltage at no load and full load. The range and the starting current
or voltage are important for optimizing the linkage system. Typical values are
shown in the table following for 12 volt and 24 volt Systems.
ACTUATOR CURRENT/VOLTAGE
RANGE CHART
12 VOLTS 24 VOLTS
No Load 2.5 Amp, 4 Volts 0.5 Amps, 12 Volts
Full Load 4 Amp, 6 Volts 1.2 Amps, 18 Volts
To increase the range of the actuator voltage or current: move the linkage
to a lower hole on the actuator lever. A lower range of actuator current than sug-
gested can cause instability or poor performance.
To increase or decrease the no load current or voltage: Adjust the length of
the link between the actuator and the engine fuel control.
Smaller angles of actuator travel may improve transient performance, but will
IMPORTANT Click “Save Data to Device” to update governor’s memory. reduce available force at the fuel control lever. Allowing the actuator to operate
through at least one half (12 degrees) of its stroke will usually provide near
optimum response.
MAIN MENU
7 PRE-START PARAMETER
1.
ADJUSTMENT PROCEDURE
Increase this parameter until instability develops.
Reconfirm that the linkage is not binding and that friction
IMPORTANT 2. Then, gradually decrease this parameter until stability re-
is minimal. Before starting the engine, push the actuator to
P turns.
the full fuel position and release. It should return instantly to the no fuel position
without any binding. (GAIN) 3. Finally, decrease this parameter one increment further to
ensure stable performance.
The following parameters must be set before starting the engine:
4. If instability persists, adjust the stability parameter.
Setup & Safety 1. Follow the same adjustment procedure as the P parameter.
I
• Overspeed (STABILITY) 2. If instability persists, adjust the deadtime parameter.
• Teeth D
1. Follow the same adjustment procedure as the P parameter.
(DEADTIME)
• Ramp Up
• Ramp Down P, I, & D parameter adjustments may require minor changes after
NOTE
engine load is applied. Normally, adjustments made at no load
achieve satisfactory performance. If further performance improvements are re-
quired, refer to Section (11) GOVERNOR ADVANCED SETTINGS and Section
Starting Parameters
(12) SYSTEM TROUBLESHOOTING.
For more details on these parameters, refer to Section 11 GOVER-
NOTE
NOR ADVANCED SETTINGS.
• Crank Cutoff
• Actuator Ramp Rate
• Actuator Begin Point
Idle speed must be set below operation speed but above crank
NOTE
termination (600-1200) even if it is not being used.
Perform the following precedure with the unit powered and the
STARTING PARAMETERS CAUTION
engine not running to set the variable speed limits. The potenti-
Name Range Default Definition ometers must be calibrated to those limits afterwards.
RPM at which EDG switches from
Crank Cutoff 100 - 500 480 Variable Speed Setup Procedure
starting to governing
Throttle position’s rate of change 1. In the “[3 - Idle Speed]” parameter under “FIXED SPEED PARAMETERS”,
Actuator Ramp Rate 0 - 100 2 from the throttle begin point to 100%, input a value 50 RPM below the desired idle speed setting.
during the start/crank cycle (% / s)
Starting position of the actuator
Actuator Begin Point 0 -100 100
during the start/crank cycle (%)
5. Input the desired maximum RPM in the box labeled “Speed Max” and hit the
“Enter” key.
8. Set the speed input to its maximum; either 5 volts or turn the potentiometer full
clockwise.
9. Click the button leveled “Speed Pot Calibration” and hit enter ( or click the
button labeled “Save Data to Device” )
UPDATE RATE & PID SCALE
The displayed values under “Pot min” and “Pot max” are in
NOTE
counts. When a 5k potentiometer is used as a variable speed Name Range Default Definition
input, the total speed range will be 0 to 2.5V, which is equivalent to 0 to
Changes the rate at which the PID
512 counts displayed. When a 0 to 5V input is used, the full range of 0 to Update Rate 4 - 250 4 routine is called.(ms)
1023 counts will be displayed and the unit will operate at its best resolution.
P Scale 0 - 20 17 If a PID Scale multiplier is changed
(e.g. P Scale), the corresponding
I Scale 0 - 20 17 parameter (e.g. P) will be affected in
ENGINE RESPONSE PARAMETERS
D Scale 0 - 20 12 two ways. See below.
Name Range Default Definition
0 -100, Proportional (P) set point of the PID
P 20
100 = Max Gain control
0 -100,
I 100 = Longest 36 Integral (I) set point of the PID control
Time
D 0 -100 21 Derivative (D) set point of the PID control PID Multipliers
SPECIAL FUNCTIONS
Name Range Default Definition
Enables or disables the multi-PID
tables which displays a variable map
Multiple PID Off, On OFF
over full engine speed and actuator
duty cycle range.
AUX
Name Range Default Definition
Aux Input Enable Off, On Off Enables or disables load sync input.
12 SYSTEM TROUBLESHOOTING
Overspeed shuts down engine 1. Check resistance between Terminals 3 & Ground. Should be 30 1. OVERSPEED set too low
before running speed is reached to 1200 ohms. See specific Magnetic Pick-up data for resistance. 2. If the speed sensor signal is erroneous, then check the wiring.
1. Measure the voltage at the battery while cranking. 1. If the voltage is less than:
a. 7V for a 12V system, or
b. 14V for a 24V system,
Then: Check or replace battery.
Actuator does not energize fully
2. Momentarily connect Terminals 1 and 11. The actuator should 1. Actuator or battery wiring in error
move to the full fuel position. 2. Actuator or linkage binding
3. Defective actuator
4. Fuse opens. Check for short in actuator or harness.
1. Measure the actuator output, Terminals 1 & 2, while running un- 1. If voltage measurement is within 2 VDC of the battery supply voltage lev-
Engine remains below desired der governor control. el, then fuel control is restricted from reaching full fuel position, possibly
governed speed due to mechanical governor, carburetor spring, or linkage interference.
2. SPEED parameter set too low