4010 SFIO Programmed IC Installation Instructions
4010 SFIO Programmed IC Installation Instructions
Installation Instructions
Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS
DAMAGED. Upon unpacking your Simplex product, inspect the contents of the
carton for shipping damage. If damage is apparent, immediately file a claim
with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any
internal adjustments or repairs. Servicing should be performed by qualified
Simplex Representatives.
Overview This publication shows how to replace an existing 742-147 IC (U25) in a 4010
Fire Alarm Control Panel (FACP) with a replacement programmed IC. For
additional wiring information, refer to the 4010 Fire Alarm Installing, Operating,
and Programming Instructions (574-052).
WARNING: During this procedure the FACP is not a functional fire
alarm. Inform building personnel and the local fire
department as required.
Checklist Three steps must take place to complete the IC replacement. Check off Steps 1
through 3 as you complete each task.
❏ 3. Download the Rev. 2.01 (or higher) master EXEC. File (4010.BIN).
Download the archived programming information from your PC to the
FACP.
Removing the SFIO Chip To remove the programmed IC (U25) from an SFIO board in an FACP, follow
Steps 1 through 8 and refer to Figures 1 and 2.
1. Using a “B” Key, unlock and open the door assembly on the FACP.
2. Remove the retainer from the panel.
3. Disconnect the FACP batteries.
4. Remove AC Power from the FACP at the breaker.
7. Locate the IC (U25) on the SFIO board. The IC is positioned half way
down the right side of the board next to P7 (see Figure 2).
8. With an IC Extractor (553-412, 553-413, or compatible tool), remove the IC
from the SFIO board.
Retainer
Back Box
Chassis
SFIO Board
Assembly
Keyboard
Door Assembly Mounting
Assembly
2
Technical Manuals Online! - http://www.tech-man.com
Installing the SFIO Chip To install the replacement IC into an FACP, follow Steps 1 through 7 and refer
to Figure 2.
WARNING: PTCs in the lower left corner of the SFIO must not touch
each other or any other metal surface. Use caution when
handling PTCs, the edges are sharp.
4. Check the baud rate settings by referring to the 4010 Fire Alarm Installing
Operating and Programming Instructions (574-052).
5. Reapply power to the FACP. Connect the AC power first and then connect
battery power.
Top (in panel) 6. Verify that all FACP operations work properly.
7. Re-install the retainer into the panel.
Flat Edge
4010 SFIO IC (U25)
P7
PTCs
Service Port
Figure 2. Expanded View of SFIO IC (U25)
3
Technical Manuals Online! - http://www.tech-man.com
Troubleshooting The FACP must be reconfigured for the replacement IC. If after completing the
download, you experience problems refer to the following information.
Note: If a negative Earth ground is detected, that was not present prior to
the chip replacement, check the Switching Regulator (U51). U51 is
located on the bottom left corner of the board. This regulator
sometimes touches the display, thus creating a ground.
If you are unable to download the CFIG from the PC, use an archived CFIG
disk OR…
If you are unable to either download the CFIG from the PC or from an
archived CFIG disk, use the AUTO-CFIG feature from the 4010 Front Panel
or PC Programmer to restore the original CFIG data base functionality from
hard copy records.
574-779
Rev. A