Professional Documents
Culture Documents
Balance Between Test Result and Analysis For Medium Voltage System
Balance Between Test Result and Analysis For Medium Voltage System
Paper 0427
BALANCE BETWEEN TEST RESULT AND ANALYSIS FOR MEDIUM VOLTAGE SYSTEM
Venugopal Vadivel Devraj Manna
Global Technology Centre Global Technology Centre
Schneider Electric India Private Limited Schneider Electric India Private Limited
India India
venu.gopal@in.schneider-electric.com devraj.manna@in.schneider-electric.com
INTRODUCTION
The major design constrains for the medium voltage
equipment designer is to optimize the size. Air constitutes
the main insulating medium in the most of the metal-clad
designs. And it is the limiting factor in determining the Figure 1: Experimental setup
dimensions of the equipment. To make the metal-clad
design as compact as possible it is necessary to ensure the
electrode/busbar arrangement which is used for connecting TEST CIRCUIT
the different switchgear components able to withstand the
A 140 kV single stage impulse generator is used for the
maximum electrical stress during the test.
testing. The standard positive polarity impulses of 1.2/ 50
For certain extent to minimize the size the often used air- µsec within its tolerance limit [1] are applied in each test
insulation can be strengthened by introducing the screens conditions. The Figure 2 shows the test circuit used for the
between bare live and earthed parts, by using insulated live testing. The values of the impulse generator parameters
parts or a combination of insulating materials which are during test are C1 25 nF, C2 1.19 nF, R1 350 Ω, R2 2400 Ω.
capable of withstanding high electrical fields. The atmospheric conditions during the testing are; ambient
temperature 31.5ºC, pressure 905 mbar and relative
In this paper the experimental test was carried out on the
humidity 68 %. The test procedure 2 in IEC 60060 is
Paper 0427
followed for the acceptance of the test results. per Table 1 is applied in all test conditions. As per
acceptance criteria [1] two flashover out off 15 impulses is
acceptable for the withstand voltage test.
As the clearance and creepage distance is less in the top side
of the bushing, adequate insulation is added to avoid the
flashover from top side. The flashovers are observed in the
bottom side of the bushing
Paper 0427
2D Analysis results:
ELECTRICAL FIELD PLOT ON THE HV
The Figures 4a), b) shows the potential and field
distribution for the analysis conditions 1&2 in the Table 2.
BUSBAR SURFACE
The Figures 5 shows the potential and field distribution for From the Figures 4&5, it is evident that the maximum field
the analysis condition 3 in the Table 2. The maximum field is concentrated on the busbar edge. In Figure 6 a line region
concentration was observed on the busbar surface. A-B is drawn on the busbar surface to obtain the maximum
Paper 0427
field (Emax). The Figure 7 a), b) shows the electrical field Table 3: Field efficiency factor η for the test conditions
plotted on the line region A-B.
Test Xtest Vtest Emean t: Emaxt ηtest
conditions mm kV kV/mm kV/mm %
1.Ph/E
without PC 125 82 0.66 8.66 7.6
screen
2.Ph/E with
70 82 1.17 9.72 12.0
Figure 6: Line region A -B on busbar surface for field plot PC screen
a) Ph/E b) Ph/Ph test conditions 3.Ph/Ph
w/o PC 80 65 0.81 3.41 23.9
screen
4.Ph/Ph
with PC 90 130 1.44 6.82 21.2
screen
The Table 4 shows the required distance (air clearance) X
derived from the above relations for the withstand voltage
of 95 kV for the same experimental setup.
Table 4: Derived air clearance X for 95 kV
Test V Emax Emean X
η %
conditions kV kV/mm kV/mm mm
1.Ph/E
without PC 6.5 95 10.04 0.66 145
screen
2.Ph/E with
10.4 95 11.26 1.17 81
PC screen
3.Ph/Ph
w/o PC 16.3 95 4.98 0.81 118
screen
4.Ph/Ph
with PC 29.0 95 4.99 1.44 66
Figure 7: Electrical field plot on line regions A - B. screen
a) Analysis conditions 1&2 b) Analysis conditions 3&4 For validation, the test condition 1 in Table 4 is verified
with actual test by keeping Ph/E clearance as 145 mm and it
withstood for 95 kV impulses. The similar method can be
RELATION BETWEEN TEST AND ANALYSIS adopted for deriving X for other impulse voltages.
The Table 3 shows the field efficiency factor η [2] for all
the test conditions. The factor η is obtained from the ratio of CONCLUSION
Emax (maximum electrical field) obtained from the 2D
analysis to Emean (mean electrical field) from the From the above discussion it is possible to establish a
experimental condition. This factor η is clearly related to relationship between test results and the analysis values
electrostatic field analysis. The η equals unity for a uniform (Emax) which helps to derive the approximate air clearance
field, and it approaches zero for highly non-uniform field. required for withstanding a specific impulse voltage.
The following relations shows relationship between η, Emax, However the derived air clearance will depend on the
Emean and the air clearance X. electrode configuration and the system environment. It is
recommended to perform a dielectric analysis on the
Vtest E Mean test
E Meantest = ; η test = medium voltage system to identify the possible failure
X test E Max test location and improve the design before performing the
actual tests. A dielectric analysis improves the design and
E Max test η V significantly reduces iterations to achieve the desirable
E Maxderived = Vrequired ;η derived = test test results.
Vtest Vrequired
Vrequired Vrequired REFERENCES
X derived = = − − − −1
E Meantest E Maxderived η derived [1] IEC 60060-1, 1989, “High-voltage test techniques.
Part 1: General definitions and test requirements”
[2] E. Kuffel, W.S. Zaengl and J. Kuffel, 2000, "High
Voltage Engineering", Butterworth-Heinemann