ii 600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com
Contents
SAFETY INFORMATION
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
PRODUCT INFORMATION
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Acceptance and Initial Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Handling and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
EQUIPMENT REQUIRED
Equipment Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
TOOLS REQUIRED
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
INSTALLATION OF CONNECTORS
Shear Bolt Installation Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Compression Connector Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com iii
! !
SAFETY
FOR LIFE Safety for life SAFETY
FOR LIFE
Eaton’s Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We
actively promote safe practices in the use and maintenance of our products through our service literature, instructional
training programs, and the continuous efforts of all Eaton’s Cooper Power Systems employees involved in product design,
manufacture, marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around
high voltage lines and equipment, and support our “Safety For Life” mission.
Safety information
The instructions in this manual are not intended as a Safety instructions
substitute for proper training or adequate experience in the Following are general caution and warning statements that
safe operation of the equipment described. Only competent apply to this equipment. Additional statements, related to
technicians who are familiar with this equipment should specific tasks and procedures, are located throughout the
install, operate, and service it. manual.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions. DANGER
• Is trained in industry-accepted high and low-voltage safe Hazardous voltage. Contact with hazardous voltage
operating practices and procedures. will cause death or severe personal injury. Follow all
locally approved safety procedures when working
• Is trained and authorized to energize, de-energize, clear,
around high- and low-voltage lines and equipment.
and ground power distribution equipment.
G103.3
WARNING WARNING
Indicates a potentially hazardous situation which, if Power distribution and transmission equipment must
not avoided, could result in death or serious injury. be properly selected for the intended application.
It must be installed and serviced by competent
CAUTION personnel who have been trained and understand
proper safety procedures. These instructions are
Indicates a potentially hazardous situation which, if written for such personnel and are not a substitute
not avoided, may result in minor or moderate injury. for adequate training and experience in safety
CAUTION: Indicates a potentially hazardous situation procedures. Failure to properly select, install or
which, if not avoided, may result in equipment maintain power distribution and transmission
damage only. equipment can result in death, severe personal
injury, and equipment damage. G122.3
iv 600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com
Additional information
DANGER
These instructions cannot cover all details or variations
All associated apparatus must be de-energized during in the equipment, procedures, or process described nor
any hands-on installation or maintenance. provide directions for meeting every possible contingency
during installation, operation, or maintenance. For additional
information, contact your representative.
WARNING
The 600 A BOL-T Connector System is designed to be Acceptance and initial inspection
operated in accordance with normal safe operating Each BOL-T connector is in good condition when accepted
procedures. These instructions are not intended to by the carrier for shipment. Upon receipt, inspect the
supersede or replace existing safety and operating shipping container for signs of damage. Unpack the BOL-T
procedures. The elbow connector should be installed connector and inspect it thoroughly for damage incurred
and serviced only by personnel familiar with good during shipment. If damage is discovered, file a claim with
safety practices and the handling of high-voltage the carrier immediately.
electrical equipment.
Product information
Unthreaded Compression
Introduction Connector
Eaton's Cooper Power Systems 600 A 15/25 kV Class
BOL-T™ deadbreak connectors are used to terminate high- Test Point
voltage underground cable to deadfront apparatus such
as transformers, switches, and switchgear. They are fully Cable Adapter
shielded, submersible, and meet the requirements of IEEE
Std 386™-2006 standard – “Separable Insulated Connector
Systems”. 600 A deadbreak connectors from Eaton's Cooper
Power Systems are fully interchangeable with all other
Neutral Wire
manufacturers that also certify compliance with IEEE Std
386™-2006 standard. The BOL-T connector is rated for 900
A when used with all copper current carrying components.
Read this manual first Figure 1. Line illustration of 15/25 kV 600 A BOL-T
connector.
Read and understand the contents of this manual and follow
all locally approved procedures and safety practices before
installing or operating this equipment.
600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com 1
IMPORTANT Installation of connectors
Installation Instructions to be used for 600 A, 15/25 kV
Class BOL-T connector with shear bolt connector. Please
see page 6 for installation instructions using a compression Shear bolt installation procedure
connector.
NNote: If concentric neutral cable is not being used,
Prepare the cable
Step 1.
follow cable preparation directions in shield
adapter kit. Train cable
•• Position cable vertically so that it is centered between
Tools required
"A"
(See Table 1)
•• Torque Wrench
•• 5/16" Hex Wrench for Splice Application Bushing
•• Cable Stripping Tools
•• 5 mm or 8 mm Allen Wrench Cable
D A
2 600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions for S600-10-2 July 2014 www.cooperpower.com
Table 1. Shear Bolt Stripback Dimensions
Connector
Code S1 S3 S4
Allen Wrench
(mm) 5 8 8
Length with or without
Variable Measurement Name Tolerance Centering Ring in (mm)
A Bushing to Cable (+/-0.25) 2.00 2.00 2.00
(50.8) (50.8) (50.8)
B Jacket (+/-0.25) 12.00 12.00 12.00
(304.8) (304.8) (304.8)
C Insulation Shield (+/-0.125) 9.38 9.38 9.38
(238.2) (238.2) (238.2)
D Conductor (+/-0.125) 2.75 3.38 4.00
(69.85) (85.85) (101.6)
E Cable Adapter Check Maximum 7.25 7.25 7.25
(184.1) (184.1) (184.1)
600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com 3
Step 2. Step 4.
Remove concentric neutral wires or jacket Put tape marker in place
NNote: Care should be taken to not cut or score the ••Measure 1" (25 mm) from end of insulation shield. (Refer
neutral conductors when cutting the cable jacket. to Figure 5.)
•• Measure reference length "B" from end of cable. (Refer to •• Wrap two turns of tape to serve as marker for cable
Figure 4 and Table 1 to determine variable "B" length. adapter location.
•• For jacketed neutral cable, remove jacket to "B" Tape Marker Insulation Shield
dimension.
Insulation
•• For unjacketed neutral cable, bind neutral wires using
three (3) wraps of tape at "B" dimension.
•• Pull back concentric neutral wires. Allow enough extra 1" "C"
concentric neutral wires to connect to ground after installation (25 mm) (See Table 1)
and allow movement to insulated standoff bushing.
Figure 5. Line illustration of cable stripback.
Bushing
Step 5.
"A" Remove conductor insulation
(See Table 1)
NNote: Do not pencil cable.
•• Remove insulation exposing bare conductor to length of
Cable "D". (Refer to Figure 6 and Table 1 to determine variable
"B"
(See Table 1) "D" length.)
NNote: Do not unwind conductor strands.
Concentric Neutral
Wires "D"
(See Table 1)
Bevel .25"
(6 mm)
Insulation
4 600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions for S600-10-2 July 2014 www.cooperpower.com
Step 7.
Clean insulation
Not Straight
Straight
NNote: Do not apply solvent directly to cable.
•• Clean insulation thoroughly with solvent dampened rag, Cable
wiping from conductor end toward insulation shield. Insulation Major OD
(Refer to Figure 8.) flared out
Straight
Not Straight
Wipe Insulation
Cable
Insulation
Shield
Tape
Wiping Direction Marker
Step 8.
Lubricate and install cable adapter
••Lubricate exposed cable insulation.
•• Lubricate inside of cable adapter.
•• Slide small end of cable adapter over cable using twisting
motion until small end is flush with tape marker. (Refer to
Figure 9.)
•• After sliding the cable adapter into position make sure
that no bulge is present (see Figure 10).
Lubricate Insulation Cable Adapter
Figure 10. Cross sectional view of cable adapter
positioning.
Bolt 3
WARNING
Equipment Damage/Personal Injury. Improperly St
art Bolt 1
positioned cable adapter may result in equipment wi
th
damage or personal injury. Bo
lt 1
600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com 5
Step 9. Install BOL-T T-body with mating parts
Install shear bolt connector Step 11.
NNote: Refer to the separate installation instructions Install DT625 T-body
supplied with the shear bolt connector. •• Clean and lubricate outside of cable adapter with lubricant
supplied.
•• If the lug is supplied with centering sleeves, check the
chart supplied with the lug and determine if a sleeve is •• Clean and lubricate inside of T-body with lubricant sup-
required and what the correct color would be. plied.
•• Wire brush conductor (aluminum only). NNote: If test point T-body is used, insure test point is
•• Immediately insert the conductor completely into the opposite front plate side of T-body.
barrel of the lug and rotate connector to distribute •• Without moving the cable adapter, slide T-body onto cable
inhibitor. adapter until compression connector eye is centered in
•• Align flats of connector and apparatus bushing for 600 A interfaces. (Refer to Figure 13.)
minimum conductor strain. NNote: The end of the cable adapter must line up with
NNote: Connector must be fully seated on cable conductor. the top edge of the tape marker after T-body
assembly. Refer to Figure 10.
•• With an Allen hex key as specified in Table 1 screw in bolt
No. 1 until it breaks off smoothly. Proceed with bolt No. •• Remove tape marker from cable.
2 in a similar way. If the lug has more than two (2) bolts,
600 A Interfaces
continue with bolt No. 3 and bolt No. 4, (not shown in
Figure 11). See Figure 11 for tightening sequences.
•• Once all the bolts have broken off, smooth any rough Test Point on Accessible
edges with a file and install the covering caps. Carefully Side
clean off any filings. T-body
•• Wipe excess inhibitor from connector and adapter
surfaces. Apparatus
Bushing
Step 10.
Check dimensions
Lubricate
••Check length from end of compression connector to top
of cable adapter.
•• Length should be no longer than "E" dimension. (Refer to Cable Adapter
Figure 12 and Table 1.)
Tape Marker
Cable Adapter
Tape Marker
Concentric Neutral
Wires
6 600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions for S600-10-2 July 2014 www.cooperpower.com
Compression connector installation procedure Step 2.
Remove concentric neutral wires or jacket
Equipment provided NNote: Care should be taken to not cut or score the
•• BOL-T Connector Assembly Kit including: neutral conductors when cutting the cable jacket.
•• T-body •• Measure 12.75" (324 mm) from end of cable. Refer to
•• Cable Adapter Figure 15.
•• Insulating Plug with Cap
•• Compression Connector with 11/16" unthreaded spade •• For jacketed neutral cable, remove jacket to 12.75"
•• Silicone Lubricant dimension.
•• Threaded Stud
•• Instruction Sheets •• For unjacketed neutral cable, bind neutral wires using
three (3) wraps of tape at 12.75" dimension.
Tools required •• Pull back concentric neutral wires. Allow enough extra
•• Torque Wrench and 1" socket for BOL-T concentric neutral wires to connect to ground after installation
•• 5/16" Hex Wrench for Separable Splice Applications and allow movement to insulated standoff bushing.
•• Cable Stripping Tools Bushing
Cable preparation
Step 1
1.75" ± .25"
Train cable (45 mm ± 7 mm)
•• Position cable vertically so that it is centered between
apparatus bushing and parking pocket, parallel to, and 6"
(152 mm) from apparatus frontplate. Cable
12.75" ± .25"
(324 mm ± 7 mm)
•• Provide adequate cable slack for cable movement
between standoff bushing and apparatus bushing.
•• Support cable as needed to maintain position. Concentric Neutral
Wires
•• Cut cable 1.75" (45 mm) from centerline of bushing. Refer
to Figure 14.
Figure 15. Line illustration of removing concentric
neutral wires.
6"
(152 mm)
Step 3.
Remove insulation shield
••Remove insulation shield 9.75" (248 mm) from end of
cable. Refer to Figure 16.
1.75" ± .25"
(45 mm ± 7 mm) •• Do not cut or nick insulation.
Existing Step 4.
Bushing
Put tape marker in place
Cable ••Measure 1" (25 mm) from end of insulation shield. (Refer
to Figure 16.)
•• Wrap two turns of tape to serve as marker for cable
Figure 14. Line illustration for cable training.
adapter location.
••
Insulation
1" 9.75"
(25 mm) (248 mm ± 3 mm)
600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com 7
Step 5. Step 7.
Remove conductor insulation Clean insulation
NNote: Do not pencil cable. NNote: Do not apply solvent directly to cable.
•• Remove insulation exposing bare conductor to length of •• Clean insulation thoroughly with solvent dampened rag,
4.38" (111 mm). Refer to Figure 17. wiping from conductor end toward insulation shield.
(Refer to Figure 19.)
NNote: Do not unwind conductor strands.
•• Ensure that all traces of conductive residue are removed.
4.38" ± .13"
(111 mm ± 3 mm) Wipe Insulation
Figure 17. Line illustration of bare conductor length. Figure 19. Line illustration of insulation cleaning.
Step 6.
Step 8.
Bevel insulation
•• Remove sharp edge of insulation by beveling at a 45°
Lubricate and install cable adapter
angle for approximately .25" (6 mm). (Refer to Figure 18.) ••Lubricate exposed cable insulation.
•• Lubricate inside of cable adapter.
•• Slide small end of cable adapter over cable using twisting
.25"
Bevel
(6 mm)
motion until small end is flush with tape marker. (Refer to
Figure 20.)
•• After sliding the cable adapter into position make sure
that no bulge is present (see Figure 21).
Insulation
Lubricate Insulation Cable Adapter
Figure 18. Line illustration of insulation bevel.
WARNING
Equipment Damage/Personal Injury. Improperly
positioned cable adapter may result in equipment
damage or personal injury.
8 600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions for S600-10-2 July 2014 www.cooperpower.com
Step 9.
Install compression connector
Not Straight
Straight
NNote: Refer to the chart supplied with the crimp
Cable
connector for tool and die to be used.
Insulation Major OD •• Wire brush conductor (aluminum only).
flared out
•• Remove protective cap from compression connector.
bulge
Straight
Not Straight
Cable NNote: Connector must be fully seated on cable conductor.
Insulation
Shield •• Align flats of connector and apparatus bushing for
Tape minimum conductor strain.
Marker
•• Make first crimp 1/2" (13 mm) below shoulder of
compression connector. (Refer to Figure 22).
•• Rotate each successive crimp 90° on compression
Correct Positioning Incorrect Positioning connector and allow 1/8" (3 mm) between crimps.
•• Wipe excess inhibitor from connector and adapter
surfaces.
Bushing
Tool Shoulder
Crimping
Area Cable
Adapter
Figure 21. Cross sectional view of cable adapter
positioning. Figure 22. Line illustration of crimping area.
600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com 9
Step 10. Install BOL-T T-body with mating parts
Check dimensions Step 11.
•• Check length from end of com
pression connector to top Install DT625 T-body
of cable adapter. •• Clean and lubricate outside of cable adapter with
•• Length should be between 6.50-7.25" (165 - 184 mm). (Re lubricant supplied.
fer to Figure 23.) •• Clean and lubricate inside of T-body with lubricant
supplied.
NNote: If test point T-body is used, insure test point is
opposite front plate side of T-body.
6.50-7.25" •• Without moving the cable adapter, slide T-body onto cable
(165-184 mm) adapter until compression connector eye is centered in
Compression 600 A interfaces. (Refer to Figure 24.)
Connector
NNote: The end of the cable adapter must line up with
the top edge of the tape marker after T-body
assembly. Refer to Figure 21.
Cable
Adapter •• Remove tape marker from cable.
Tape
Marker 600 A Interfaces
Concentric
Neutral Wires
Test Point on
Accessible
Figure 23. Line illustration for dimensional check. Side T-body
Apparatus
Bushing
Lubricate
Cable Adapter
Tape Marker
10 600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions for S600-10-2 July 2014 www.cooperpower.com
Completing T-body termination Install BOL-T connector onto apparatus bushing
Step 13.
Step 12. Install T-body onto apparatus bushing
Install STUD into apparatus bushing •• Clean and lubricate mating interfaces of apparatus
NNote: Use only the symmetrical aluminum (STUD-A) or bushing and T-body with lubricant supplied.
copper (STUD-C) stud in separable splice and BOL-T •• Push T-body onto apparatus bushing ensuring that the
applications. Do no use the non-symmetrical stud on the bushing passes through the hole of the
extended length STUD-T. compression connector. See Figure 26.
•• Ensure unit is de-energized. Clean and Lubricate 600 A Interfaces
•• Thread the stud into the apparatus bushing unit hand
tight. Refer to Figure 25.
T-body
Apparatus Bushing
•• Remove any shavings that may have been raised during Figure 26. Line illustration of BOL-T connector installation
the threading procedure. onto apparatus bushing.
1/2" CROWSFOOT
WRENCH
600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com 11
Step 14. Step 15.
Install insulating plug Check tightness of termination
•• Clean and lubricate the mating interfaces of T-body and ••Check tightness by hand by moving T-body forward and
insulating plug. back (perpendicular to the apparatus frontplate). Do not
move side to side as this may loosen the connection.
•• Insert insulating plug into back of T-body engaging the
threads of the stud. See Figure 27. •• If tight:
•• By hand, turning clockwise, thread insulating plug in as •• Re-torque to 55 ft-lbs.
far as possible.
•• If loose:
•• Using a torque wrench and 1" socket complete threading
•• Remove insulating plug and T-body from apparatus
clockwise until tight. Torque to 55 ft-lbs. See Figure 28.
bushing.
•• Inspect threads of the stud and insulating plug for
Thread by hand T-body damage.
•• If damaged, replace damaged component and re-install
Apparatus per previous installation instructions.
Bushing
•• If no damage is found, re-install per previous
installation instructions.
Insulating Plug
Step 16.
Cap the insulating plug
••Clean and lubricate inner surface of insulating plug cap
with lubricant supplied.
•• Attach hotstick onto cap ring.
•• Push cap onto insulating plug until it snaps into place.
Refer to Figure 29.
T-body
Concentric Neutral
Wires
Apparatus
Bushing
Complete
Threading Concentric Neutral
Wires
Concentric Neutral
Wires
12 600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions for S600-10-2 July 2014 www.cooperpower.com
Step 17. Separable Splice Assembly Instructions
Ground system NNote: Use only the symmetrical aluminum (STUD-A) or
copper (STUD-C) stud in BOL-T separable splice
•• Connect one concentric neutral wire to drain wire tab of
applications. Do not use the copper alloy non-
the T-body or use a separate uninsulated copper wire
symmetrical extended length T-OP II (STUD-T) stud.
(#14 AWG/2.5 mm). Refer to Figure 30.
•• Prepare the cables and install the cable adapters,
unthreaded compression connectors, and T-bodies accord-
T-body ing to the instruction sheet included with the T-body
(S600-46-2).
NNote: Before any component is installed, clean and
lubricate all mating interfaces using the supplied
lubricant. (i.e. T-bodies, insulating plugs, connector
plugs, and cable adapters.)
•• Obtain first insulating plug, if a stud is not factory
Drain
Wire Tab
installed, hand thread a 5/8" stud into the insulating plug.
Insert the insulating plug into the first T-body, lining up the
Uninsulated hole in the compression connector with the 5/8" stud.
Drain Wire
•• Insert the connecting plug into the open interface of
Concentric Neutral the first T-body and hand tighten to the 5/8" stud of the
Wires insulating plug.
Figure 30. Installation of the drain wire. •• Secure the connecting plug by inserting a 5/16" hex
style wrench (HD625, HD635CP, or customer supplied
alternate) into the hex hole at the base of the connector
plug threads. Use a torque wrench to tighten the
connecting plug to 55 ft-lbs. Refer to Figure 31.
•• Insert the interface of the connecting plug into the
interface on the second T-body.
Insulating Plug
Connecting
Plug
600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com 13
•• Repeat the above assembly procedures for each
additional splice tap. (Refer to Figure 32.) Insulating Plug
•• After the last connecting plug and T-body are installed, Connecting Plug Connecting Plug
1" Wrench 5/16" Hex
obtain the second insulating plug. If stud has not Shaft
been factory installed, hand thread a 5/8" stud into the
insulating plug.
•• Install the second insulating plug, with stud, into the
open interface of the last T-body. Hand thread the Connecting Plug
insulating plug into the connecting plug.
•• Secure the first insulating plug using a 1" wrench. Using
a 1" socket on a torque wrench, tighten the second
insulating plug to 55 ft-lbs. (Refer to Figure 33.)
•• Clean and lubricate the inner surface of two insulating Socket
Wrench Torque
plug caps with the lubricant supplied. Wrench
Drain
•• Push the caps onto the insulating plugs until they snap Drain Wire
into place. Wire
•• Connect one drain wire to the tie-off tab of each T-body Figure 32. Installing to connecting plugs.
and connect the other end to a common ground point.
NNote: If splice is disassembled, all connecting plugs and
insulating plugs should be completely removed,
cleaned, regreased, and reassembled following
the above procedure to ensure connection points Insulating Torque
are properly torqued. Insulating Plug Connecting Plug Plug Wrench
Drain Drain
Wire Wire
14 600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions for S600-10-2 July 2014 www.cooperpower.com
This page is intentionally left blank.
600 A 15/25 kV class BOL-T and separable splice connector assembly installation instructions S600-10-2 July 2014 www.cooperpower.com 15
!