Column Number: COLUMN C3 Date: March 17, 2020

Project Name: PROPOSED 2-STOREY RESIDENTAIL Designed by: MCDESGUERRA

I. Design Parameters Judgement: SAFE


Cross Section Properties
B = 200 mm. H = 400 mm. cc = 40 mm. fyt = 276.00 Mpa.
Materials Strength
fc'= 21.00 Mpa. fy = 414.00 Mpa. Es = 200 Gpa.
Rebar Arrangement
Y-axis
db = D10
Number of bars along Y-axis: 2
Number of bars along Z-axis: 3
Total number of Bars: 6
Shear Capacity (Design of Lateral Ties) Cross Section :
Z-axis
modification factor (λ) = 1.00
number of legs (Z) = 2.00
number of legs (Y) = 3.00
dby = D10 Spacing = 100 mm. (for lateral ties)
Design Loads:
Pu = 96.077 kN Muz = 20.67 kN.m. Muy = 2.63 kN.m.
Vuz = 12.048 kN Vuy = 16.68 kN

II. Calculations:
Min.S Max S. Max Pu
Bar Spacing Check: 35.00 285.51 Max MY
Sactual(z) = 90.00 OK OK Max MZ
Sactual(y) = 145.00 OK OK

ß1 = 0.85
Balanced Condition: Due to My: Du to Mz:
cby = 85.80 mm. c = 174.28 mm. c = 25.08 mm.
Pby= 469.71 kN Pny= 981.50 kN Pnz= 850.69 kN
ebz= 84.24 mm. ez= 27.34 mm. ey= 215.15 mm.
cbz = 204.14 mm.
Pbz= 616.67 kN
eby= 143.68 mm.

Values of Φ: Note: Column Splice Shall be Located


Φy = 0.90 midheight of Column with lap
Φz = 0.90 length equal to 520 mm. with
Lateral Ties spaced not more
Section Capacities: than 150 mm.
Pn = 627.97 kN
Pcy = 883.35 kN OK
Pcz = 765.62 kN OK
Mcy = 24.15 kN-m OK
Mcz = 164.72 kN-m OK
Vuycap = 84.18 kN OK
Vuyzcap = 255.81 kN OK

Check Spacing for Crack Control:


Sminy = 1716.64 mm OK
Sminz = 572.215 mm OK

Provide 1 @ 50 from face of support


9 @ 50 mm. o.c.
Rest @ 100 mm. o.c.