Professional Documents
Culture Documents
2.4 Cooling Water Requirements: 2.4.1 Type of The System Closed System
2.4 Cooling Water Requirements: 2.4.1 Type of The System Closed System
No general recommendation can encompass the effects of all combinations of the various compounds,
solids and gases typically found in cooling water in interaction with different materials.
Closed system
In a closed system, the same cooling water is circulating through a system without contact with air.
Open system
An open system is a pass-through system, or a circulating system with a cooling tower. In the latter
case, the composition of the water that enters the cooler must be considered, and not the composition
of the make-up water. Due to the evaporative effect in the cooling tower, much higher concentrations
of ions can be obtained in the circulating water than in the make-up water.
The Ryznar Index (RSI) is a parameter for predicting whether water will tend to dissolve or precipitate
calcium carbonate. The adhesion of scaling deposits and their effect are different on different
materials, but the equilibrium of the water (scaling or corrosive) is only determined by its actual pH
value and by the saturation pH value (pHs).
The saturation pH value is determined by the relationship between the calcium hardness, the total
alkalinity, the total solids concentration and the temperature.
RSI = 2*pHs - pH
pHs = (9.3 + A + B) - (C + D)
Total
Dissolved
solids (mg/l)
From the table above, the RSI index should be between 5.6 and 7.5; otherwise, contact a specialist.
pH
The effect of pH is already calculated in the Ryznar index, but the pH itself has some additional
limitations:
This is the sum of all ions in the water. It can be derived from the dry residue after evaporation (but
not including suspended solids) or it can be estimated from the electrical conductivity.
Chlorides (Cl-)
Chloride ions will create pitting corrosion on stainless steel. Their concentration should be limited:
However, if the water is scaling, lower limits should be used. (See The Ryznar stability index (RSI)).
Sulphates (SO4--)
Carbonate hardness
Ammonia
Copper
< 1 ppm
Iron and manganese
< 1 ppm
Organics
No algae.
No oil.
Suspended solids
Remark
- Chloride and sulphate are interactive. In open systems the sum of the squares of these
values must not exceed 85,000. For recirculating systems with proper controls and treatment,
the sum of the squares may be up to 520,000. Note that the sulphate value must include any
sulphite present.
2.5 Pictographs
Moving/lifting
The compressor
3.21.Compressor
Check levelcan
the oilcontrol be moved
modes
(3-Fig. by a lift
3.2) which truck
must be using
in thethe slots
green in the
range orframe.
above. Make sure
Top up, if that the forks
necessary,
protrude
with from type
the correct the other
of oil.side
Seeofsection
the frame.
4.3. The compressor can also be lifted after inserting beams in
the slots.
The2.Elektronikon Make
Close condensate sure
drain
regulator that the
valves
allows beams cannot
the(5,operator
7 and 9-Fig. slide
to select and
3.1).threethat they protrude
control modes: from the frame equally. The
chains
3. Open
- Local must
the air
control mode be held parallel
outlet valve. to the bodywork by chain spreaders in order not to damage the
compressor.
4. If thecontrol
- Remote cooling The lifting equipment must
water was drained (see section 3.7):
mode be placed in such a way that the compressor will be lifted
- Local perpendicularly.
- close
Areathe drain valve
Network Lift(1-Fig.
(LAN) smoothly
control3.4)and avoid
in the
mode twisting.
water inlet pipe and fit the drain plug (2)
- fit the drain plugs (8-Fig. 3.3) underneath all coolers
5. Open the water inlet valve and outlet valve.
1 6.
Local3.1control
Open Preparation
the water
mode flow for
(remote initial
regulating start-up
valves
control mode(1, is
2 and
made 4-Fig. 3.3). Opening of these valves can be
inactive):
overlooked if, after previous operation, the settings have not been disturbed.
1. Consult section 2 for the dimension drawings, installation proposal and voltage supply
connections. Consult section 7.3 for the values of the fuses, electric supply cables, overload relay
and motor types.
2. If not provided, stick warning labels next to the control panel and also on both sides of the
compressor in an obvious place inside the bodywork, indicating that the compressor is
automatically controlled (started and stopped) by the Elektronikon regulator.
3. A number of VCI (Volatile Corrosion Inhibitor) plates are provided inside the bodywork to protect
the compressor against corrosion. Remove the plates.
4. Check the voltage selecting wires at transformer (T1-Fig. 1.9) for correct connection (a label is
stuck on the transformer). Check the setting of overload relays (F25/27/29-Fig. 1.9). See section
7.3.
5. Remove the centre part of the drive coupling (4-Fig. 1.1).
6. Have the drive motor alignment checked by an Atlas Copco representative.
7. Start the drive motor and stop it immediately. Check the rotation of drive motor (1-Fig. 1.1) while
the compressor is coasting to a stop: the correct rotation direction is counter-clockwise when
looking at the drive end shaft of the motor. If wrong, switch off the voltage and reverse two
Remark
incoming electric lines.
8.When thecentre
Fit the electrical
part power to thecoupling
of the drive compressor is switched
(4-Fig. 1.1) usingoff,new
the bolts.
Elektronikon regulator will not
9.react to any
Check thatstart/stop command
the oil reservoir and the
is filled withoiloil
willto not
the be
fullheated
mark nor circulated.(3-Fig. 3.2). See section
of sight-glass
4.3. For drive motors equipped with sleeve bearings, check that oil is visible in the bearing sight-
glasses.
10. The outlet of the demister may be ducted outside of the bodywork. The maximum pressure drop
over this pipe is 0.5 mbar. Never install valves in this pipe. Avoid any obstruction or liquid lock by
sagging of the pipe.
11. Check that the cooling water drain valves (customer's installation) in the inlet and outlet piping are
closed. Check that the drain valve (1-Fig. 3.4) in the water inlet pipe is closed and the drain plug
(2) is fitted.
12. Open the water inlet and outlet valves (customer's installation), as well as the flow regulating
valves (1, 2 and 4-Fig. 3.3). Check for water flow.
13. Close the condensate drain valves (5, 7 and 9-Fig. 3.1).
14. Switch on the voltage.
On compressors provided with a reset button (5): the control panel will indicate an emergency
stop. Press reset button (5), then press key Reset (F3).
Check the oil reservoir temperature: if below 38 °C, the oil heater will be activated (see section
1.9.4 to check the oil temperature and to find the message Oil heater on).
1 Air outlet
2 Water outlet
3 Water inlet
4 Automatic drain outlet, first intercooler
condensate drain
5 Condensate drain valve, first
intercooler condensate drain
6 Automatic drain outlet, second
intercooler condensate drain
7 Condensate drain valve, second
intercooler condensate drain
8 Automatic drain outlet, aftercooler
condensate drain
9 Condensate drain valve, aftercooler
condensate drain
10 Condensate drain, blow-off silencer
1. Switch on the voltage. Check that voltage on LED (8) lights up.
2. Normally, the main screen is shown. See section 1.9.6.
3. Press start button (1). The compressor starts running in unloaded condition. Automatic operation
LED (10) will light up. Auxiliary oil pump (6-Fig. 3.3) should automatically turn off after the
compressor has reached full operating speed.
4. After 20 seconds (programmable), the compressor starts running loaded.
5. If necessary, regulate the water flow with the compressor running loaded, using valves (1, 2 and
4-Fig. 3.3). Consult section 7.4 for the cooling water temperature and pressure, and for the
cooling water consumption.
Press emergency stop button (7) (if not yet done so), switch off the voltage and depressurise the
compressor. After remedying the fault, unlock the emergency stop button by pulling it out and push
reset button (5) if available. Push key Reset (F3) on the regulator. Restart the compressor as
described above.