EC centrifugal fans - RadiPac

backward curved, single inlet, Ø 400

Highlights:
– 7-blade fan, 3-phase fan motor
– Output: 10 VDC, max.10 mA, 20 VDC, max. 50 mA, slave 0-10 V
– Input: sensor 0-10 V or 4-20 mA, 24 V external programming, 0-10 VDC/ PWM control
– Integrated PID controller along with RS485 MODBUS RTU technology
– Over-temperature protected electronics / motor
– Soft start, alarm relay, motor current limit, PFC passive, line undervoltage / phase failure detection
– Control interface with SELV potential safely disconnected from the mains
Material: Impeller: Aluminum sheet
Rotor: Coated in black
Electronic housing: Die-cast aluminum
Assembly: Galvanized steel with aluminum posts
Mounting position: Shaft horizontal or rotor on bottom; rotor on top on request
Condensate discharge holes: Rotor-side
Direction of rotation: Clockwise, seen on rotor

Electrical wiring diagram


Ingress protection rating
Nominal voltage range

Temperature range (1)


Current draw (1)
Power input (1)
Frequency

Speed (1)
Air flow

Mass
Nominal Data

UL
Type RadiPac Motor CFM VAC Hz Watts RPM A °C lbs

R3G400-AQ29-19 EG1R-240-400-39 M3G150-FF 5,285 200...240 50/60 3,100 2,550 8.4 -25...50 48 IP54 A Yes
R3G400-AQ23-09 EG1R-480-400-39 M3G150-FF 5,227 380...480 50/60 3,000 2,550 4.0 -25...60 48 IP54 A Yes
(1) Nominal data at maximum load.

n Pe I I LwAin
Curves A A
rpm W (460V) (230V) dB(A)
6.00
Measurement: LU-121371 A 1 2550 1972 2.6 5.7 93
in. wg

Air performance measured as per: A 2 2550 2697 3.6 7.6 87


4
ISO 5801, Installation category
A, without protection against A 3 2550 3000 4.0 8.4 85
5.00
5.00

3
accidental contact. A 4 2550 2792 3.7 7.9 88
Suction-side noise levels: LWA as
A 5 2100 1103 1.5 3.1 89
per ISO 13347, LPA measured at
4.00
4.00
1m distance to fan axis. A 6 2100 1517 2.0 4.2 83
8
The values given are valid A 7 2100 1668 2.2 4.6 81
7 under the measuring conditions
A 8 2100 1555 2.1 4.4 84
3.00
3.00 2 mentioned and may vary accoring
to the actual installation situation. A 9 1700 585 0.8 1.6 84
12
With any deviation to the standard A 10 1700 805 1.1 2.2 78
11
6
set-up, the specific values have
2.00
to be checked and reviewed once A 11 1700 885 1.2 2.5 76
installed or fitted. A 12 1700 825 1.1 2.3 79
16
10
15
For detailed information on the
measuring set-up, please contact
A 13 1300 262 0.3 0.7 78
1.00
1.00
14
ebm-papst. A 14 1300 360 0.5 1.0 72
A 15 1300 396 0.5 1.1 71
13 9 5 1
0.00 A 16 1300 369 0.5 1.0 73
Δpfa

0v 1000
1000 2000
2000 3000
3000 4000
4000 5000
5000 cfm600
R3G400-AQXX-XX Dimensions shown in inches (mm)

Depth of screw max. 0.98 (25)

2.76(70)

Ø11.10+0.1(282+2.5)
Ø9.13(232)

Ø17.91(455)

Tightening torque
31 +4.4 lbf-in (3.5 +0.5 Nm)

4.92(125) Accessory part: inlet nozzle


40075-2-4013, not included
7.17(182) in scope of delivery Ø9.92+0.01(252+0.3) Cable diameter min. 0.16 (4), max.
0.39(10), tightening torque
10.46+0.08(265.6+2) Ø10.83(275) 35.4 +5.3 lbf-in (4 +0.6 Nm)
0.35(9)

EGIR-XXX-400-39 Dimensions shown in inches (mm)

17.72(450) 12.64(321)
Ø0.28(7.1)
4 places
16.54(420)

19.69(500)

16.00(406.5)