Data Center Facility - FusionModule500&800 Training
Data Center Facility - FusionModule500&800 Training
• 单击此处编辑母版文本
样式
Course Objective
Key parameters
2
Huawei DC Are Adaptable for All Solutions
NetEco6000
Mgmt. system
Management System
Solution
FusionModule500 FusionModule1000B
Micro DC Prefabricated DC
1-2 IT Rack, ≤3kW FusionModule800 FusionModule1000A 18-84 IT Rack, ≥100kW
Small DC FusionModule2000 FusionModule5000 Outdoor Small DC
1-10 IT Rack, 3~25kW Medium DC 4-8 IT Rack, 8~52kW
Medium-to-Large DC
2-48 IT Rack, ≤235kW 6-48 IT Rack, ≤310kW
Subsystem
UPS2000 iBattery
(1~20 kVA) Battery NetCol5000-A/C NetCol8000-A/C
UPS5000 PDU Management In-row PAC In-room PAC
(25~800 kVA) System (11~42kW) (50~253 kW)
3
Huawei FusionModule800 Smart Small
Data Center
05 Competition Analysis
4
小型机房建设面临的挑战
Traditional Small & Mini DC
5
Traditional Small DCs Have Lots of Defects
Traditional DC layout Traditional DC Mode:
IT rack
• UPS, PDU, IT racks, air conditioner are
independent deployment
PDU • Low integration
• Large footprint
6
Huawei FusionModule800 Smart Small
Data Center
01 Construction Challenges for Small DC
05 Competition Analysis
7
Modularization Keeps DC Room Clean and Tidy
Traditional small DC
FusionModule800 IT rack
PDU
VS
A/C rack
Battery box
UPS
8
Design Construction Deploy Run O&M
2 step
UPS 10+10 selection
VS
A/C 1+1
20 step
selection
10
Design Construction Deploy Run O&M
Back 1.2m
0.8m
Converged cabinet
Cooling
PDU 1.35m
IT rack
Front 1.2m
Large footprint
11
Design Construction Deploy Run O&M
Huawei solution saves 7000+$ electricity expense each year (10kW IT load, Traditional solution PUE of 2.5)
The saved electricity expense in 1-2 years is equivalent to the price of a set of FusionModule800.
12
Design Construction Deploy Run O&M
In many cases, the DC is running at low loads which can cause Ordinary A/C
condensation. Condensation have 3 big risk: When the load is less
than 20%, the
Short-circuit of live equipment
dehumidification is
! leads to safety incidents. stopped
13
Design Construction Deploy Run O&M
Temperature exceeds
the threshold. Emergency heat dissipation
The rear door will automatically open when fire alarm generation
A/C failure
Smoke alarm
14
Design Construction Deploy Run O&M
Current
Voltage
Tempe
rature
VS
• Log in the PAD, open rack door automatically after • The mechanical key is easy to lose.
secondary approval
16
Design Construction Deploy Run O&M
Site N
Local APP
17
Summery: Why Choose FusionModule500&800?
18
Huawei FusionModule800 Smart Small
Data Center
01 Construction Challenges for Small DC
03 Introduction of FusionModule800
04 Detailed Introduction of Subsystems
05 Competition Analysis
19
Huawei Small DC Solution
FusionModule800
20
Comparison between old and new products
Changes Old version New version Value
Normal temperature ≤15kW Normal temperature ≤25kW
Maximum load capacity High temperature ≤12kW High temperature ≤21kW Improve the scenario adaptability.
Latin America ≤15kW Latin America ≤15kW
Maximum number of cabinets (Asia, Africa,
≤8 ≤12 Improve the scenario adaptability.
and Europe)
Maximum number of equipment cabinets
≤6 ≤10 Improve the scenario adaptability.
(Asia, Africa, and Europe)
Maximum number of cabinets (Latin
≤8 ≤8 No change
America)
Maximum number of equipment cabinets
≤6 ≤6 No change
(Latin America)
Low temperature application condition None Yes Improve the scenario adaptability.
Intelligent power distribution, switch hot
None Only typical configuration Bid control
swap
Long backup power 30 min 15-240min Improve the scenario adaptability.
Cold & hot sealed
Full sealed aisle Cold aisle Dustproof and noise reduction
(module total depth 1350mm)
Height difference between the indoor and
-5-20m -8-30m Improve the scenario adaptability.
outdoor units of smart cooling
Long pipe ≤60m ≤80m Improve the scenario adaptability.
Cooling capacity 11kW 12.5kW Improve scenario adaptability + control bidding
Improve the sense of technology and O&M
Electronic access control Not supported Supported
efficiency.
Improve the sense of technology and O&M
Local face recognition door opening Not supported Supported
efficiency.
Automatic open door Not supported Supported Improve reliability.
Remote door opening Not supported Supported Improve the scenario adaptability.
Climate lamp Not supported Optional Improve the sense of science and technology.
rPDU: National standard +IEC+intelligent
Not supported Optional. It is installed onsite. Flexible configuration
IEC (optional)
ATS: Optional Not supported Optional. It is installed onsite. Flexible configuration
21
FusionModule800: Integrated Solution for DC of 1–10 ICT Racks
Depth 1350mm
Monitoring
module
Air conditioners
1100 mm
Hot aisle
250 mm
Cold aisle Maximum racks configuration: 1≤N≤12
22
幻灯片 22
G(DCE3 该布局图只有5个机柜,说是最大配置,而实际最多支撑6个机柜,
Guojinchao (Clark, Data Center Energy), 2018/9/26
Cold and hot aisle containment, Energy saving, dustproof, and noise reduction
Hot aisle
1100mm
1350mm IT IT IT IT IT
A/C Server Server
Server Server Server
Cold aisle
250mm
Traditional DC
Cold and hot aisle containment
Traditional DC 1:Open space
Traditional DC:
• Room-level A/C, cold and hot airflow mixing together, low cooling efficiency.
23
Power and Signal Cable are Separated, Reliable Cabling
(simple cable trough) (M-shape cable trough)
1 2
1 2
Power and signal cable are separated, which reduces Flexible cabling and piping type, suitable for all kinds of
interference scenarios
Remarks:
Onsite survey items: 1、Electric cable length between the mains and modules;2、Distance between indoor and outdoor units
3、Pipe routing method
24
Cabinet dimension installation space recommendations
Back
Cold aisle
25
Standard solution, Simplified design
BC6/7 : Intelligent power distribution
8.5kW~17KW
≤8.5KW(T1<) 8.5kW~17KW(T1<) 17kW~25KW(T1<) ≤8.5KW(T1<)
IT load (T1<)
≤7kW(T3) 7kW~14kW(T3) 14kW~21kW(T3) ≤7kW(T3)
7kW~14kW(T3)
BC1 BC2 BC3 BC4 BC5 BC6 BC7
24U 31U 31
24U
16U
26
Basic Configuration Introduction
Note:
• The non-redundancy A/C solution can be used only in Tier 1 DC. NO-redundant A/C solution are not suitable for Operators’ s DC
• ATS is optional ,installed onsite. (will delivered in November.2019,can’t proposed for early projects before November)
• RPDU(choose one): Common: IEC or GB(optional). Intelligent: Only IEC is supported. BC6,BC7
• T1: -20℃~+45℃; LT: -40℃~+45℃; T3: -10℃~+55℃ Intelligent power distribution
8.5kW~17KW
≤8.5KW(T1<) 8.5kW~17KW (T1<) 17kW~25KW(T1<) ≤8.5KW(T1<)
IT load (T1<)
≤7kW (T3) 7kW~14kW(T3) 14kW~21kW(T3) ≤7kW (T3)
7kW~14kW(T3)
Configuration BC1 BC2 BC3 BC4 BC5 BC6 BC7
Structure Cold and hot aisle containment
Number of IT
4 12 12 12 20 12 12
output
Temperature sensor, Smoke sensor, SMS alarm, Local app on the mobile phone, PAD, intelligent door lock, ECC800
Standard
ATS,(intelligent/ no-intelligent)RPDU, Video system, battery, ibattery,IT rack, remote app on the mobile phone,, network rack
Optional
Water sensor
A/C Non-
Remark A/C Non-redundantA/C Non-redundant A/C Non-redundant A/C Non-redundant
redundant
27
Huawei FusionModule800 Smart Small
Data Center
01 Construction Challenges for Small DC
Power distribution
PDU1 PDU2 PDU3 PDU4 PDU5 ATS
module
29 Huawei Confidential
PDU UPS A/C Monitoring Battery
30 Huawei Confidential
PDU UPS A/C Monitoring Battery
31 Huawei Confidential
PDU UPS A/C Monitoring Battery
32 Huawei Confidential
PDU UPS A/C Monitoring Battery
Web page
33 Huawei Confidential
PDU UPS A/C Monitoring Battery
35 Huawei Confidential
Huawei FusionModule800 Smart Small
Data Center
01 Construction Challenges for Small DC
05 Competition Analysis
36
HTB: Ten Highlights of FusionModule800
FusionModule800 Traditional small DC APC
37
Huawei FusionModule500 Smart Mini
Data Center
To Build a
Modular, Intelligent, Energy Saving
Data Center
38
Modularization Keeps DC Room Clean and Tidy
VS
39
40
FusionModule500: Integrated Solution for DC of 1–2 ICT Racks
Integrated architecture 1~2 ICT racks
PDU
UPS
Battery pack
41
220V, 1Ph+N+PE 208V, 2Ph
24 U
IT Space
3kVA/24U
4 battery
2 battery optional
optional 12U
6U
Aisle type NO
UPS(KVA) 3 3 6 10
Air conditioner NO
43
HTB: Ten Highlights of FusionModule500
FusionModule500 Traditional MINI DC APC
1 PDU, UPS, Battery pack and monitoring are Standard configuration NO YES
integrated in one rack
2 Multiple DCs management YES NO YES
3 Mobile APP(remote) Optional NO YES
44
There are hundreds of sites in one project!
Energy Government
Mexico Uganda
PEMEX Safe City
123PCS 108PCS
Education Congo-Kinshasa
MOF
Cote d’Ivoire
105PCS
20kVA+3 IT racks (Ivory Coast)
MOE
617PCS Finance
Paraguay
Philippines
“Many a little MOE
ICBC(Asia)
964PCS
makes a mickle.”
Thailand KMITL
(King Mongkut's Australia
Institute of Technology Commonweal
Ladkrabang)
th Bank
400PCS
3D DEMO: http://3ms.huawei.com/mm/docMaintain/mmMaintain.do?method=showMMDetail&f_id=DCI16101316410180
45 Huawei Confidential
把数字世界带入每个人、每个家庭、
每个组织,构建万物互联的智能世界。
Bring digital to every person, home and
organization for a fully connected,
intelligent world.
New Features:
1. Indoor integrated solution with cold and hot aisle containment;
2. 6 kVA UPS plus lithium battery, saving footprint;
3. Split-type cooling system with outdoor units;
4. The fire extinguish module and 48 V DC output are optional.
Application: Edge data centers with ICT loads less than 3 kW, enough
space for outdoor unit installation
47
FusionModule500 with integrated cooling system
Launch Time : June 30, 2020
New Features:
1. Indoor integrated solution with cold and hot aisle containment;
2. 6 kVA UPS+lithium battery, saving footprint;
3. Integrated cooling system without outdoor units;
4. The fire extinguishing module and 48 V DC output are optional.
Application: Edge data centers with less than 3kW power have no outdoor
unit installation space, and heat dissipation in the room .
48
FusionModule500 with high-level protection for outdoor scenarios
Launch Time : June 30, 2020
New Features:
1. outdoor integrated solution with cold and hot aisle containment, IP55
protection;
2. 6 kVA UPS+lithium battery, saving footprint;
3. The cabinet door is integrated cooling system without outdoor units;
4. The 48 V DC output is optional.
Application: outdoor sites such as transportation, manufacturing, water
conservancy, and forest sites.
Dimension 750*750*2000mm(W*D*H) Available space 9U(4.5kW @ 8 hours backup)
1.5kW cooling capacity, air conditioner
UPS 6kVA *1 Cooling system
is integrated in the door
Power output 220V AC+48V DC(optional) Protection level IP55
Lithium Optional
100Ah @ 3U 48V DC output
battery Functions
49
Embracing the Lithium!
FusionModule800 with lithium battery is coming
Number of IT cabinet 4 6
50