FusionModule500&800

Data Center Facility Solution

Huawei Network Energy Product Line

• 单击此处编辑母版文本
样式
Course Objective

 Features and values

 Key parameters

 Comparison with others

2
Huawei DC Are Adaptable for All Solutions
NetEco6000
Mgmt. system

Management System
Solution

FusionModule500 FusionModule1000B
Micro DC Prefabricated DC
1-2 IT Rack, ≤3kW FusionModule800 FusionModule1000A 18-84 IT Rack, ≥100kW
Small DC FusionModule2000 FusionModule5000 Outdoor Small DC
1-10 IT Rack, 3~25kW Medium DC 4-8 IT Rack, 8~52kW
Medium-to-Large DC
2-48 IT Rack, ≤235kW 6-48 IT Rack, ≤310kW
Subsystem

UPS2000 iBattery
(1~20 kVA) Battery NetCol5000-A/C NetCol8000-A/C
UPS5000 PDU Management In-row PAC In-room PAC
(25~800 kVA) System (11~42kW) (50~253 kW)

3
Huawei FusionModule800 Smart Small
Data Center

01 Construction Challenges for Small DC


02 Features of Huawei Solutions

03 Introduction & configuration of Huawei Solutions

04 Detailed Introduction of Subsystems

05 Competition Analysis
4
小型机房建设面临的挑战
Traditional Small & Mini DC

5
Traditional Small DCs Have Lots of Defects
Traditional DC layout Traditional DC Mode:
IT rack
• UPS, PDU, IT racks, air conditioner are
independent deployment
PDU • Low integration

• Large footprint

A/C rack Traditional DC Mode Defects:


• Design Time Takes at Least a Week
• On-site Installation Takes at Least 10
Days
• Low Cooling Utilization, High Power
Battery box
Consumption
• Battery Catching Fire, Equipment
Condensation
UPS • Manual Inspection, Fault Positioning
Difficult, High O&M Costs

6
Huawei FusionModule800 Smart Small
Data Center
01 Construction Challenges for Small DC

02 Features of Huawei Solutions


03 Introduction & configuration of Huawei Solutions

04 Detailed Introduction of Subsystems

05 Competition Analysis
7
Modularization Keeps DC Room Clean and Tidy
Traditional small DC
FusionModule800 IT rack

PDU

VS
A/C rack

Battery box

UPS

8
Design Construction Deploy Run O&M

2 Step VS 20 Step, Save at Least 90% Design Time

2 step
UPS 10+10 selection

VS
A/C 1+1

20 step
selection

Confirm three variables:


Confirm two variables 1、Brand Choice: UPS, air conditioners, cabinets, batteries, monitoring ... (10 steps)
Step1、Total load; 2、Model and capacity selection: UPS, air conditioners, cabinets, batteries…(15 steps)
Step2、Redundancy design or not; 3、 Solution Design: Load size, cold power matching, part redundancy or not,
power supply single or dual ... (5 steps)
4、Drawing design
9
Design Construction Deploy Run O&M

Easy On-site Combination and Quick Installation in 2 days


Traditional construction mode
Site integration Commissioning
Design Equipment installation Run
equipment acceptance

10 days business on the line


FusionModule800
Typical Simple
Integration Rack
configur- Commiss- Run
transport combination
ation ioning Saving 80% of the installation time
2 days business on the line
The product is pre-fabricated Cabinets are simply The infrastructure is Services go online in
in the factory and packed for connected on site. established in 4 hours. two days.
1 transportation.
2 3 4

10
Design Construction Deploy Run O&M

Integration Solution, Saving at Least 2 racks Footprint


PDU A/C1 A/C2
UPS Saving 2 racks, saving area of 4.26m2

Back 1.2m
0.8m

Converged cabinet
Cooling

PDU 1.35m
IT rack

Front 1.2m

Large footprint

11
Design Construction Deploy Run O&M

High Energy Efficiency: PUE Is Down to 1.37


Aisle containment, Hot and cold air separation,
EC fan, DC inverter compressor, on-demand cooling
high cooling efficiency

Huawei solution saves 7000+$ electricity expense each year (10kW IT load, Traditional solution PUE of 2.5)
The saved electricity expense in 1-2 years is equivalent to the price of a set of FusionModule800.

12
Design Construction Deploy Run O&M

Low-load Dehumidification Prevents Condensation

In many cases, the DC is running at low loads which can cause Ordinary A/C
condensation. Condensation have 3 big risk: When the load is less
than 20%, the
Short-circuit of live equipment
dehumidification is
! leads to safety incidents. stopped

Reduced creepage distance


Huawei A/C
! easily results in electric shock. Patented design, 10% low
load, still reliable
dehumidification, "0"
condensation
Component rust corrosion
! shortens the product life. Note: the traditional DC is generally
deployed dehumidifier in the DC

13
Design Construction Deploy Run O&M

Auto-spring door – FusionModule800


Automatically open the door to dissipation overheat and link with fire extinguishing system
Open the front door first and then the rear door

Temperature exceeds
the threshold. Emergency heat dissipation

The rear door will automatically open when fire alarm generation

A/C failure

Fire fighting linkage

Smoke alarm
14
Design Construction Deploy Run O&M

Intelligent PDU: online maintenance, PUE & load rate monitoring

PUE Intelligent PDU

Current
Voltage

Tempe
rature

Load Rate • The system can Monitors the general mains


input voltage, frequency, current, and power, as
well as the UPS input voltage, frequency, current,
switch temperature, and so on.
• The system can monitors the current, electric
energy, and switch status of power distribution
branches of IT equipment and A/C , calculated
the PUE and load rate.
• Displays the PUE value of the smart module in a
data dashboard, allows you to view the historical
PUE curve.
15 Only BC6,BC7 have this function
Design Construction Deploy Run O&M

Facial recognition on local PAD – FusionModule800


Facial recognition login Traditional password login
• Log in the local PAD without password or card swiping • Manually entered :easy to forget the password.

VS
• Log in the PAD, open rack door automatically after • The mechanical key is easy to lose.
secondary approval

16
Design Construction Deploy Run O&M

Data Real-time Upload, Multi-DC Centralized Monitoring

NetEco6000 Remote APP


Intranet/Internet
One module

Site N

Local APP

FusionModule800 FusionModule500 FusionModule500

Site 1 Site 2 Site 3

17
Summery: Why Choose FusionModule500&800?

18
Huawei FusionModule800 Smart Small
Data Center
01 Construction Challenges for Small DC

02 Features of Huawei Solutions

03 Introduction of FusionModule800
04 Detailed Introduction of Subsystems

05 Competition Analysis
19
Huawei Small DC Solution
FusionModule800

20
Comparison between old and new products
Changes Old version New version Value
Normal temperature ≤15kW Normal temperature ≤25kW
Maximum load capacity High temperature ≤12kW High temperature ≤21kW Improve the scenario adaptability.
Latin America ≤15kW Latin America ≤15kW
Maximum number of cabinets (Asia, Africa,
≤8 ≤12 Improve the scenario adaptability.
and Europe)
Maximum number of equipment cabinets
≤6 ≤10 Improve the scenario adaptability.
(Asia, Africa, and Europe)
Maximum number of cabinets (Latin
≤8 ≤8 No change
America)
Maximum number of equipment cabinets
≤6 ≤6 No change
(Latin America)
Low temperature application condition None Yes Improve the scenario adaptability.
Intelligent power distribution, switch hot
None Only typical configuration Bid control
swap
Long backup power 30 min 15-240min Improve the scenario adaptability.
Cold & hot sealed
Full sealed aisle Cold aisle Dustproof and noise reduction
(module total depth 1350mm)
Height difference between the indoor and
-5-20m -8-30m Improve the scenario adaptability.
outdoor units of smart cooling
Long pipe ≤60m ≤80m Improve the scenario adaptability.
Cooling capacity 11kW 12.5kW Improve scenario adaptability + control bidding
Improve the sense of technology and O&M
Electronic access control Not supported Supported
efficiency.
Improve the sense of technology and O&M
Local face recognition door opening Not supported Supported
efficiency.
Automatic open door Not supported Supported Improve reliability.
Remote door opening Not supported Supported Improve the scenario adaptability.
Climate lamp Not supported Optional Improve the sense of science and technology.
rPDU: National standard +IEC+intelligent
Not supported Optional. It is installed onsite. Flexible configuration
IEC (optional)
ATS: Optional Not supported Optional. It is installed onsite. Flexible configuration

21
FusionModule800: Integrated Solution for DC of 1–10 ICT Racks

 Total IT racks: 0~10 rack( Total racks:1~12)


Integrated architecture
Electrical cable tray (optional)
 Cooling: Rack A/C(12.5kW/pcs)
Data cable tray(optional)
 Cold and hot aisle containment: Cold aisle containment
Spring to open
the door(rear)
250mm+1100mm hot aisle containment.
Camera (optional)
Spring to open
the door(front)
 Maximum IT load: ≤ 25kW(T1&LT), ≤ 21kW(T3),
Indicator light  Power density per Rack ≤7kW(T1&LT), ≤6kW(T3)
Glass
PDU door
G(DCE3
2000 mm Touch screen IT Converged IT IT Battery
UPS Rack Rack Rack Rack Rack
Aisle

Depth 1350mm
Monitoring
module

Air conditioners

1100 mm
Hot aisle

250 mm
Cold aisle Maximum racks configuration: 1≤N≤12

22
幻灯片 22

G(DCE3 该布局图只有5个机柜,说是最大配置,而实际最多支撑6个机柜,
Guojinchao (Clark, Data Center Energy), 2018/9/26
Cold and hot aisle containment, Energy saving, dustproof, and noise reduction

Hot aisle
1100mm
1350mm IT IT IT IT IT
A/C Server Server
Server Server Server

Cold aisle
250mm
Traditional DC
Cold and hot aisle containment
Traditional DC 1:Open space
Traditional DC:

• Open space, air conditioner cools the environment firstly;

• Room-level A/C, cold and hot airflow mixing together, low cooling efficiency.

Cold or hot aisle containment:

• Need to save the energy and reduce the noise

Cold and hot aisle containment:


Old Version FM800: Cold or hot aisle containment
• Energy saving, dustproof, and noise reduction.

23
Power and Signal Cable are Separated, Reliable Cabling
(simple cable trough) (M-shape cable trough)

1 2
1 2

Top cabling and piping Bottom cabling and piping

(1) Signal cable tough (2) Power cable tough

Power and signal cable are separated, which reduces Flexible cabling and piping type, suitable for all kinds of
interference scenarios
Remarks:
Onsite survey items: 1、Electric cable length between the mains and modules;2、Distance between indoor and outdoor units
3、Pipe routing method

24
Cabinet dimension installation space recommendations

Back

Install against the wall


800mm
(suggested)

Netw Conv Batter


IT IT IT IT IT
ork
cabin cabin
erged y
cabin cabin cabin
1200mm
Left cabin
et
et et
cabin
et
cabin
et
et et et (suggested) Right

Cold aisle

• Each cabinets has a aisle 1200mm


(suggested)
• Aisle:Depth 250mm(Cold aisle)
• Front door: dual-layer glass door
Front
• Back door: mesh door
• Cabinet dimension: 600*2000(W*H)
Recommend reserved space
• Cabinet total depth: 1100+250=1350mm

25
Standard solution, Simplified design
BC6/7 : Intelligent power distribution
8.5kW~17KW
≤8.5KW(T1&LT) 8.5kW~17KW(T1&LT) 17kW~25KW(T1&LT) ≤8.5KW(T1&LT)
IT load (T1&LT)
≤7kW(T3) 7kW~14kW(T3) 14kW~21kW(T3) ≤7kW(T3)
7kW~14kW(T3)
BC1 BC2 BC3 BC4 BC5 BC6 BC7

24U 31U 31
24U
16U

26
Basic Configuration Introduction
Note:
• The non-redundancy A/C solution can be used only in Tier 1 DC. NO-redundant A/C solution are not suitable for Operators’ s DC
• ATS is optional ,installed onsite. (will delivered in November.2019,can’t proposed for early projects before November)
• RPDU(choose one): Common: IEC or GB(optional). Intelligent: Only IEC is supported. BC6,BC7
• T1: -20℃~+45℃; LT: -40℃~+45℃; T3: -10℃~+55℃ Intelligent power distribution
8.5kW~17KW
≤8.5KW(T1&LT) 8.5kW~17KW (T1&LT) 17kW~25KW(T1&LT) ≤8.5KW(T1&LT)
IT load (T1&LT)
≤7kW (T3) 7kW~14kW(T3) 14kW~21kW(T3) ≤7kW (T3)
7kW~14kW(T3)
Configuration BC1 BC2 BC3 BC4 BC5 BC6 BC7
Structure Cold and hot aisle containment

UPS(KVA) 10+0 10+10 20+0 20+20 20*2+0 10+10 20+20

Air conditioner 1+0 1+1 2+0 2+0 3+0 1+1 2+0


Heating and
humidification 0 1 1 1 1 1 1
quantity
Intelligent PDU NO NO NO NO NO YES YES

Power input Single input is default , ATS is Optional

Number of IT
4 12 12 12 20 12 12
output
Temperature sensor, Smoke sensor, SMS alarm, Local app on the mobile phone, PAD, intelligent door lock, ECC800
Standard
ATS,(intelligent/ no-intelligent)RPDU, Video system, battery, ibattery,IT rack, remote app on the mobile phone,, network rack
Optional
Water sensor
A/C Non-
Remark A/C Non-redundantA/C Non-redundant A/C Non-redundant A/C Non-redundant
redundant

27
Huawei FusionModule800 Smart Small
Data Center
01 Construction Challenges for Small DC

02 Features of Huawei Solutions

03 Introduction of Huawei Fusionmodule800

04 Detailed Introduction of Subsystems


05 Competition Analysis
28
PDU UPS A/C Monitoring Battery

Modular design for PDU, meeting different application scenarios

Power distribution
PDU1 PDU2 PDU3 PDU4 PDU5 ATS
module

Height 3U 6U 6U 6U+3U 6U+4U 8U


IT path 4 12 12 20 12 NA
Main switch 63A 100A 100A 125A 100A 125A

IT load ≤8.5kW ≤8.5KW ≤8.5 or ≤17kW ≤25kW ≤17kW or ≤8.5kW NA

A/C input switch 1PC 2PCS 3PCS 4PCS 3PCS NA

BC1 BC2 BC3/4 BC5 BC6,BC7 Optional

Non-intelligent PDU Intelligent PDU

29 Huawei Confidential
PDU UPS A/C Monitoring Battery

Electrical system :Support the topology of N/N+1


Electrical system : N+1 topology Electrical system : N+1 topology
Electrical system : N (with ATS*)
(without ATS*)

1. A/C supply from Utility power, UPS supply to IT load,ECC800,PAD.


2. The ATS is configured when dual power input
3. The 10kVA UPS parallel system cannot share battery. The 20kVA UPS parallel system can share battery.

30 Huawei Confidential
PDU UPS A/C Monitoring Battery

Rack-mounted 95% High Efficiency UPS Ensures Reliable Power


Battery pack 9AH
Supports 3 kinds of back up types, •Height:3U
15min-30min back up time •Voltage:240V
•Quantity:maximum 8 pcs

Parameter 10kVA 20kVA Battery cabinet


•Battery capacity:
Maximum efficiency 94.5% 95% 26AH/40AH/65AH/100AH
•Quantity:
Input voltage 138V AC~485V AC, 40~70HZ
In the module1~2pcs
Surge protection C-level SPD
Out of the module 1-4pcs
Height 2U 3U •Optional iBattery function

Output power factor 0.9 0.9 Battery rack


•Battery capacity:
Installation Mode Rack-mounted 26AH/40AH/65AH/100AH
CE, CB, TUV efficiency test, RoHS, REACH, •Quantity:1~2pcs
Authentication
WEEE, ECA certification (UK)

31 Huawei Confidential
PDU UPS A/C Monitoring Battery

Rack-mounted Air Conditioner, DC Inverter Cooling


Overall Parameter
• T1:–20°C~45°C
EC fan + DC inverter variable Operating temperature of the outdoor
• LT:–40°C~45°C
unit
frequency compressor • T3:–10°C~55°C
The vertical distance betweenbetween
-8-30m
indoor and outdoor unit
Maximum length of one-way pipe ≤80m
Cabling and Pipe mode Upward and downward routing.
Certification REACH、RoHS、CE、CB、EAC 、SASO
Item Indoor Unit
Power system 220/230/240Vac, 50Hz/60Hz, and 1Ph+N+PE
17.3A with heating and humidification
Maximum current
3.3A without heating and humidification
Rack-mounted Air conditioner Cooling mode Air-cooled (horizontal air flow)
Refrigerant R410A
Cooling capacity 12.5kW
Fan Type EC fan
Maximum airflow 2600m3/h
Installation Mode Rack-mounted
Temperature control unit Outdoor unit
Maximum working current T1;24A. T3;30A. LT:30A
Number of fans 1 (T1&LT), 2 (T3)

32 Huawei Confidential
PDU UPS A/C Monitoring Battery

Standard configuration ECC can support 2-3modules centralized monitoring

Module 1 Module 2 Module 3

Web page

Module 1 Module 2 Module 3

33 Huawei Confidential
PDU UPS A/C Monitoring Battery

Standard northbound interfaces, standardized construction


ECC800-pro: standard northbound
interface
 Accommodates all devices ,
standardizes northbound interfaces.
ECC800  Standard SNMP protocol, which
can be easily integrated by a third-
party DCIM
 ECC800-pro standard Mib
package can be provided to
complete simple development .

ECC800-pro: standard capability:


 2 WAN ports and 2 LAN ports
 4 RS485 ports are reserved.
 5 AI/DI ports
 1 Dry contact extended ports
 1 USB port
ECC800-pro extension capability:
 The AI/DI port is modular
expansion.
 Expanding the FE through ETH
34 Huawei Confidential
PDU UPS A/C Monitoring Battery

3 kinds of back up types

Battery Pack Battery Cabinet Battery Rack


Items Specification Items Specification

Capacity 9AH Cabinet in module:2000mm×600mm×1350mm, No more than 2


Dimension(HxWxD)
Cabinet out of module:2000mm×600mm×1100(1200)mm
Voltage 240V
Capacity 26AH/40AH/65AH/100AH
UPS 10kVA/20kVA QTY per cabinet 40(26AH/40AH);20(65AH/100AH)

Dimension Weight 160kg


130mm×430mm×685mm
(HxWxD) IP rating IP20
Weight 69kg(9AH) Backup time 15min/30min

35 Huawei Confidential
Huawei FusionModule800 Smart Small
Data Center
01 Construction Challenges for Small DC

02 Features of Huawei Solutions

03 Introduction & configuration of Huawei Solutions

04 Detailed Introduction of Subsystems

05 Competition Analysis
36
HTB: Ten Highlights of FusionModule800
FusionModule800 Traditional small DC APC

1 Cooling, PDU,UPS and monitoring are Standard configuration NO NO


integrated in one rack
2 Smart management, multiple DCs management Optional NO YES

3 LI-L2 integration management Optional NO NO

4 Mobile APP(remote) Optional NO YES

5 10 inch PAD(nearby Wifi+APP) Standard configuration NO YES

6 Dehumidification at low load rate patent NO NO


Standard configuration

7 Rack air conditioner Standard configuration NO NO

8 Aisle containment Standard configuration NO YES

9 CE certification for converged cabinet and AC Standard configuration NO YES

10 iBattery Support NO YES

37
Huawei FusionModule500 Smart Mini
Data Center
To Build a
Modular, Intelligent, Energy Saving
Data Center

38
Modularization Keeps DC Room Clean and Tidy

Traditional mini DC FusionModule500

VS

39
40
FusionModule500: Integrated Solution for DC of 1–2 ICT Racks
Integrated architecture 1~2 ICT racks

Natural heat dissipation(no air conditioner)

Monitoring Total IT load recommend less than 3 kW


module
Power backup time: 15min~240min

PDU

UPS

Battery pack

Rack dimension(W x D x H):


600X850X1200(24U);600X1100X2000(42U)

41
220V, 1Ph+N+PE 208V, 2Ph

4 Typical Configurations, Rapid to Output Final Solutions


3kVA/42U 6kVA/42U 10kVA/42U

24 U
IT Space
3kVA/24U

4 battery
2 battery optional
optional 12U
6U

BC1 BC3 BC4 BC5


42
Detailed Introduction of 4 Basic Configurations
Power type 220/230/240V, 50/60Hz, 1Ph+N+PE

Basic configuration BC1 BC3 BC4 BC5

Aisle type NO
UPS(KVA) 3 3 6 10
Air conditioner NO

Power input Single


rPDU 1、2 (optional)
UPS output 5
Temperature and humidity sensor, Smoke sensor, Door status sensor, Water sensor,
Standard Configuration
ECC800e
Video system、Power backup system,iBattery, Mobile APP(remote), SMS alarm,
Optional PAD,
WIFI module, rPDU

Network cabinet can be flexible expansion,Maximum of 4

43
HTB: Ten Highlights of FusionModule500
FusionModule500 Traditional MINI DC APC

1 PDU, UPS, Battery pack and monitoring are Standard configuration NO YES
integrated in one rack
2 Multiple DCs management YES NO YES
3 Mobile APP(remote) Optional NO YES

5 Automatic Startup of Air Conditioner When Mains Optional NO NO


Restarts

6 iBattery Optional NO YES


7 Unoccupied space 24U NO YES
8 PAD(nearby Wi-Fi) Optional NO YES

9 Earthquake-proof report YES NO YES

10 CE certificate of converged cabinet YES NO YES

44
There are hundreds of sites in one project!
Energy Government
Mexico Uganda
PEMEX Safe City
123PCS 108PCS

Education Congo-Kinshasa
MOF
Cote d’Ivoire
105PCS
20kVA+3 IT racks (Ivory Coast)
MOE
617PCS Finance
Paraguay
Philippines
“Many a little MOE
ICBC(Asia)
964PCS
makes a mickle.”
Thailand KMITL
(King Mongkut's Australia
Institute of Technology Commonweal
Ladkrabang)
th Bank
400PCS

3D DEMO: http://3ms.huawei.com/mm/docMaintain/mmMaintain.do?method=showMMDetail&f_id=DCI16101316410180
45 Huawei Confidential
把数字世界带入每个人、每个家庭、
每个组织,构建万物互联的智能世界。
Bring digital to every person, home and
organization for a fully connected,
intelligent world.

Copyright©2018 Huawei Technologies Co., Ltd.


All Rights Reserved.

The information in this document may contain predictive


statements including, without limitation, statements regarding
the future financial and operating results, future product
portfolio, new technology, etc. There are a number of factors that
could cause actual results and developments to differ materially
from those expressed or implied in the predictive statements.
Therefore, such information is provided for reference purpose
only and constitutes neither an offer nor an acceptance. Huawei
may change the information at any time without notice.
FusionModule500 with Split-type cooling system
Launch Time : April 30, 2020

New Features:
1. Indoor integrated solution with cold and hot aisle containment;
2. 6 kVA UPS plus lithium battery, saving footprint;
3. Split-type cooling system with outdoor units;
4. The fire extinguish module and 48 V DC output are optional.
Application: Edge data centers with ICT loads less than 3 kW, enough
space for outdoor unit installation

Dimension 600*1350*2000mm(W*D*H) Available space 27U(3kW @ 1hour backup)

3.5kW cooling capacity, air


UPS 6kVA *1 Cooling system
conditioner with outdoor unit

Power output 220V AC+48V DC(optional) Protection level IP20

Optional 48V DC output,fire extinguish


Lithium battery 100Ah @ 3U
Functions module

47
FusionModule500 with integrated cooling system
Launch Time : June 30, 2020

New Features:
1. Indoor integrated solution with cold and hot aisle containment;
2. 6 kVA UPS+lithium battery, saving footprint;
3. Integrated cooling system without outdoor units;
4. The fire extinguishing module and 48 V DC output are optional.
Application: Edge data centers with less than 3kW power have no outdoor
unit installation space, and heat dissipation in the room .

Dimension 600*1100*2000mm(W*D*H) Available space 20U(3kW @ 1hour backup)


3.5kW cooling capacity, air conditioner
UPS 6kVA *1 Cooling system
without outdoor unit
Power output 220V AC+48V DC(optional) Protection level IP20

Lithium battery 100Ah @ 3U Optional Functions 48V DC output,fire extinguish module

48
FusionModule500 with high-level protection for outdoor scenarios
Launch Time : June 30, 2020

New Features:
1. outdoor integrated solution with cold and hot aisle containment, IP55
protection;
2. 6 kVA UPS+lithium battery, saving footprint;
3. The cabinet door is integrated cooling system without outdoor units;
4. The 48 V DC output is optional.
Application: outdoor sites such as transportation, manufacturing, water
conservancy, and forest sites.
Dimension 750*750*2000mm(W*D*H) Available space 9U(4.5kW @ 8 hours backup)
1.5kW cooling capacity, air conditioner
UPS 6kVA *1 Cooling system
is integrated in the door
Power output 220V AC+48V DC(optional) Protection level IP55
Lithium Optional
100Ah @ 3U 48V DC output
battery Functions

49
Embracing the Lithium!
FusionModule800 with lithium battery is coming

Currently, Only BC1 and BC4 support lithium battery!


Launch Time : June 30, 2020
Other configurations will support lithium batteries by the end of this year.

Items BC1 BC4

Power Capacity 0-8.5kW(T1&LT) 8.5kW~17kW(T1&LT)

Number of IT cabinet 4 6

UPS configuration 6kVA *2 6kVA *4

working temperature -40℃~55℃

Aisle containment Cold and hot aisle containment

Backup time 15min~4hours

50