Technical Manual: Split Unit Air Conditioner Wall Mounted C Series - Cooling Only (50Hz)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 31

R32

TECHNICAL MANUAL
Split Unit Air Conditioner
Wall Mounted C Series
FTV-C series
— Cooling Only [50Hz] —

TM-3WMJ-SL-MMA1
Table of Contents

Table of Contents
Nomenclature......................................................................................................................1
Indoor.............................................................................................................................1
Outdoor...........................................................................................................................1
Product Line-Up..............................................................................................................2
Application Information......................................................................................................3
Operating Range............................................................................................................3
Refrigerant Circuit Diagrams..........................................................................................3
Installation Guideline......................................................................................................4
Sound Data...........................................................................................................................8
Sound Pressure Level ...................................................................................................8
NC Curve........................................................................................................................9
Engineering & Physical Data............................................................................................ 11
Performance Data..............................................................................................................12
Calculation Steps..........................................................................................................12
Performance Tables......................................................................................................14
Outline & Dimension.........................................................................................................18
Wiring Diagram..................................................................................................................22
Service & Maintenance.....................................................................................................25
Troubleshooting................................................................................................................27
Nomenclature

Nomenclature
Indoor

FT V 25 C V1
Power Supply
V1 : 220-240V/1Ph/50Hz

Product Series
C : C series

Capacity*
25 : 2500 Watt
35 : 3500 Watt
50 : 5000 Watt
60 : 6000 Watt

Refrigerant & Mode


V : R32 , Cooling Only

Model
FT : Non Inverter Wall Mounted

Outdoor

R V 25 C V1
Power Supply
V1 : 220-240V/1Ph/60Hz
Product Series
C : C series

Capacity*
25 : 2500 Watt
35 : 3500 Watt
50 : 5000 Watt
60 : 6000 Watt
Refrigerant & Mode
V : R32 , Cooling Only

Model
R : Single Split Condensing unit

Remark:
*Capacity value under Nomenclature is an indication.
Please refer to Engineering and Physical Data for exact capacity value

1
Nomenclature

Product Line-Up

Indoor Unit
FTV
Classification

Air Purification
Handset

PCB

Fin
Nomenclature

Hydrophilic (Blue)

Saranet Filter
BRC52A62

WMJ02B

WMJ01B

FTV25CV1 X X X X
FTV35CV1 X X X X
FTV50CV1 X X X X
FTV60CV1 X X X X

Outdoor Unit
RV
Classification
Refrigerant Control

Compressor
Fin

Nomenclature
Bare Aluminium
Cap. Tube

Rotary

RV25CV1 X X X
RV35CV1 X X X
RV50CV1 X X X
RV60CV1 X X X

2
Application Information

Application Information
Operating Range
Ensure the operating temperature is in allowable range.
Cooling

Outdoor
DB (°C)

The use of your air conditioner


outside the range of working
temperature and humidity can
result in serious failure.

46

43

19

14 19 23 Indoor WB (°C)

Refrigerant Circuit Diagrams

Model:FTV25/35/50/60C - RV25/35/50/60C

3
Application Information

Installation Guideline

Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.

Installation Diagram

Caulk pipe
Indoor unit 55mm or more from ceiling hole gap Cut thermal insulation pipe
with putty. to an appropriate length and
Front panel wrap it with tape, making
sure that no gap is left in the
insulation pipe’s cut line.

50mm or more from walls Wrap the insulation pipe with the
(on both sides) finishing tape from bottom to top.

M4 x 12L Service lid


Air filter  Opening service lid
Service lid is opening/
closing type.
 Opening method
1) Remove the service lid
screws.
2) Pull out the service lid
diagonally down in the
direction of the arrow.
3) Pull down.

Outdoor Unit 500mm from


wall

Outdoor Clearance

If the condensing unit is operated in an atmosphere containing oils (including machine


oils), salt (coastal area), sulphide gas (near hot spring, oil refinery plant), such as
substances may lead to failure of the unit.

A C D
B
Service access
Return air

Return air
Discharge air

Obstacle

Obstacle
Obstacle

Obstacle
H

H/2

DIMENSION A B C D
MODELS
25 100 mm 500 mm 100 mm 500 mm
35/50/60 300 mm 1000 mm 300 mm 500 mm

4
Application Information

Cable Size

FTV25/35C FTV50/60C
Model Unit
RV25/35C RV50/60C
Power supply cable size mm 2
1.5 2.5
Number of wire 3 3
Interconnection cable size mm2 1.5 2.5
Number of wire 3 3
Recommended fuse A 16 20

Refrigerant Piping
Piping Length and Elevation
When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases,
system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity, and as the result
the compressor may become defective. Always choose the shortest path and follow the recommendation as
tabulated below:

Indoor Unit

L E
Outdoor Unit

Cooling Model
Indoor FTV25C FTV35C FTV50C FTV60C
Model
Outdoor RV25C RV35C RV50C RV60C
Min.Allowable Length (L), m 3
Max.Allowable Length (L), m 20 25 30 30
Max.Allowable Elevation (E), m 12 15 15 15
Gas Pipe Size, mm/(in) 9.52 / (3/8”) 9.52 / (3/8”) 12.70 / (1/2") 12.70 / (1/2”)
Liquid Pipe Size, mm/(in) 6.35 / (1/4”) 6.35 / (1/4”) 6.35 / (1/4") 6.35 / (1/4")

5
Application Information

Additional Charge
• The refrigerant gas is charged in the outdoor unit and, if the piping length is 7.5m, additional charge of the
refrigerant after vacuuming is not necessary.
• When the piping length is more than 7.5m, additional refrigerant charge (g) per additional 1m length as
tabulated:

Indoor FTV25/35/50/60C
Model
Outdoor RV25/35/50/60C
Add. Charge, g/m 17

Special precautions when dealing with R32 unit


Minimum floor area,
Minimum floor R32 charge, kg
R32 charge, Xm2
area, Xm2 for max
Model kg for (based on max
(based on 7.5m allowable pipe
7.5m piping allowable pipe length
piping) length*
*)
FTV25C-RV25C 0.44 0.26 0.73 0.51
FTV35C-RV35C 0.76 0.55 1.06 1.07
FTV50C-RV50C 0.75 0.54 1.13 1.22
FTV60C-RV60C 0.70 0.47 1.08 1.11

Installation Height, ho (m) = 1.8

*Max. Allowable Length (L), m for :-


FTV25C-RV25C : 20
FTV35C-RV35C : 25
FTV50/60C-RV50/60C : 30

• Installation of pipe work shall be kept to a minimum and pipe work shall be protected from physical damage and shall
not be installed in an unventilated space;
• Reusable mechanical connectors and flare joints shall be accessible for maintenance purposes.

WARNING
Prior to installation, ensure risk of ignition is minimised and avoid working in confined space. Ensure adequate
ventilation is available by opening windows or doors.

• When flared joints are reused indoors,the flare part shall be re-fabricated.
• Avoid installation of the air conditioner in a place where there is danger of exposure to continuously operating open
flames (for example an operating electric heaters).
• Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate
from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in
accordance with an industry recognised assessment specification.

Checking for presence of refrigerant


The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the
technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being
used is suitable for use with flammable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.

Presence of fire extinguisher


If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to
the charging area.

6
Application Information

No ignition sources
All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation,
repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space.
“No Smoking” signs shall be displayed.
The following checks shall be applied to installations:
-- marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
-- refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance
which may corrode refrigerant containing components, unless the components are constructed of materials which
are inherently resistant to being corroded or are suitably protected against being so corroded.

Leak detection methods


Ensure that the detector is not a potential source of ignition (for example a halide torch) and is suitable for the
refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant (for R32,
LFL is 13%) and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 %
maximum) is confirmed

Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine
shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is
suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires
brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a
part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system
both before and during the brazing process.

Removal and evacuation


When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures
shall be used. However, it is important that best practice is followed since flammability is a consideration. The
following procedure shall be adhered to:

• remove refrigerant;
• purge the circuit with inert gas;
• evacuate;
• purge again with inert gas;
• open the circuit by cutting or brazing.

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed”
with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or
oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with
OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling
down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN
charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This
operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for
the vacuum pump is not close to any ignition sources and there is ventilation available.

Labelling
This unit shall be labelled ‘de-commissioned and emptied of refrigerant’. This label shall be dated and signed.
Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

Initial safety checks shall include:


-- that capacitors are discharged, this shall be done in a safe manner to avoid possibility of sparking
-- there shall be no live electrical components and wiring are exposed while charging, recovering or purging
the system;

Repair to intrinsically safe components


Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not
exceed the permissible voltage and current permitted for the equipment in use. Replace components only with
parts specified by the manufacturer.

7
Sound Data

Sound Data
Sound Pressure Level
1/1 Octave Sound Pressure (dB, ref 20µPa) Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria

High 30 34 35 33 29 21 8 37 32
Med 27 31 32 28 23 14 6 33 26
FTV25C
Low 24 26 27 22 15 7 7 27 21
Quiet 23 24 25 20 13 6 5 25 NA
High 33 36 37 35 32 24 12 39 34
Med 31 33 34 30 26 17 11 35 29
FTV35C
Low 30 28 29 24 19 11 10 29 23
Quiet 29 27 28 23 18 11 10 28 22
High 21 31 36 38 36 27 15 42 37
Med 17 28 34 35 32 23 13 39 34
FTV50C
Low 14 26 31 32 29 20 12 36 32
Quiet 12 25 31 31 27 20 13 35 30
High 40 42 42 42 39 32 20 46 43
Med 37 39 39 39 36 27 19 43 39
FTV60C
Low 34 37 37 36 32 24 18 39 35
Quiet 31 35 35 33 29 22 18 37 33

Model Measuring Location

FTV25/35/50/60C
0.8m

Microphone

Standard : JIS C 9612 1.0m

8
Sound Data

NC Curve

FTV25C
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
30
NC-30

NC-25
20
NC-20
Q
10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FTV35C
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
30
NC-30

Q NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

9
Sound Data

FTV50C
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
30
NC-30
Q
NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FTV60C
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
30 Q NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

10
Engineering & Physical Data

Engineering & Physical Data


Engineering Data - R32 MODEL (Cooling)
INDOOR UNIT FTV25C FTV35C FTV50C FTV60C
MODEL
OUTDOOR UNIT RV25C RV35C RV50C RV60C
Btu/h 9000 12000 18000 22000
NOMINAL COOLING CAPACITY
W 2640 3520 5280 6450
NOMINAL TOTAL INPUT POWER (COOLING) W 780 1100 1810 2115
NOMINAL RUNNING CURRENT A 3.63 5.08 8.35 9.74
EER W/W 3.38 3.20 2.91 3.05
REFRIGERANT CHARGE kg 0.44 0.76 0.75 0.70
POWER SOURCE V/Ph/Hz 220-240/1/50
REFRIGERANT TYPE R32
AUTO LOUVER(UP & DOWN) &
AIR DISCHARGE
CONTROL MANUAL (LEFT & RIGHT)
OPERATION WIRELESS REMOTE CONTROL
TURBO CFM 358 372 594 641
HIGH CFM 342 355 531 614
AIR FLOW MEDIUM CFM 282 298 474 537
LOW CFM 225 242 422 474
QUIET CFM 209 225 381 418
SOUND PRESSURE LEVEL (T/H/M/L/Q) dBA 39/37/33/27/25 40/39/35/29/28 44/42/39/36/35 48/46/43/39/37
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 288 X 800 X 206 310 X 1065 X 224
PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 344 X 874 X 274 386 X 1136 X 314
UNIT WEIGHT kg 9 14
CONDENSATE DRAIN SIZE mm 19.05
INDOOR UNIT

TYPE CROSS FLOW FAN


FAN
DRIVE DIRECT
TYPE SILICON CONTROLLED RECTIFIER
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE CLASS E
FAN MOTOR RATED INPUT POWER W 37 42 61 72
RATED RUNNING CURRENT A 0.19 0.21 0.30 0.34
MOTOR OUTPUT W 18 18 26 30
POLES 4
MATERIAL COPPER
TUBE
DIAMETER mm 7
COIL MATERIAL ALUMINIUM
FIN FACE AREA m2 0.18 0.29
ROW 2
TYPE SARANET
AIR QUALITY FILTER
QUANTITY pc 2
CASING COLOUR WHITE
AIR FLOW CFM 644 827 1430 1590
SOUND PRESSURE LEVEL dBA 46 48 51 52
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 485 X 566 X 256 550 X 658 X 273 651 X 855 X 328 651 X 855 X 328
PACKING DIMENSION HEIGHT X WIDTH X DEPTH mm 532 X 668 X 366 580 X 775 X 335 693 X 990 X 415 693 X 990 X 415
UNIT WEIGHT kg 21 28 41 41
PIPE LIQUID mm 6.35
SIZE
CONNECTION GAS mm 9.52 12.7
PRE-CHARGED m 7.5
PIPE LENGTH
MAXIMUM m 20 25 30 30
TYPE PROPELLER
FAN
DRIVE DIRECT
TYPE 1-PHASE FIXED SPEED
INDEX OF PROTECTION (IP) IP23
OUTDOOR UNIT

INSULATION GRADE B F F
FAN MOTOR RATED INPUT POWER W 35 51 79 123
RATED RUNNING CURRENT A 0.16 0.23 0.35 0.54
MOTOR OUTPUT W 15 20 32 60
POLES 6
TYPE ROTARY
OIL TYPE FW68DA FW50S
OIL AMOUNT cm3 180 270 670 670
COMPRESSOR
RATED INPUT POWER W 708 1007 1670 1920
RATED RUNNING CURRENT A 3.28 4.64 7.70 8.86
LOCKED ROTOR AMP. A 17.6 27.9 34.0 32.0
MATERIAL COPPER ALUMINIUM
TUBE
DIAMETER mm 7 NA
COIL MATERIAL ALUMINIUM
FIN FACE AREA m2 0.28 0.32 0.51 0.51
ROW 1 2 1 1
CASING COLOUR IVORY WHITE
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING
INDOOR: 27°C DB / 19°C WB
OUTDOOR: 35°C DB

11
Performance Data

Performance Data
Calculation Steps
Interpolation method can be used to get the total Solution:
cooling capacity, TC and sensible cooling capacity, Based on the Performance Table,
SC and power input, PI at those temperatures which
1. Refer to the Indoor DB column,
are not stated out in the table. Extrapolation method
-- 25°C is located between 24°C & 27°C
is not allowed to be used.
for 16°C WB.
Example: -- 25°C is located between 24°C & 27°C
for 19°C WB.
Indoor Condition: 25°C DB, 17°C WB -- Thus, Interpolation needs to be applied.
Outdoor Condition: 37°C DB
Fan Speed: High 2. Refer to the Indoor WB column,
-- 17°C is located between 16°C & 19°C
for 25°C DB.
-- Thus, Interpolation needs to be applied.
3. Refer to the Outdoor DB column,
-- 37°C is located between 35°C & 40°C.
-- Thus, Interpolation needs to be applied.

1st Step 2nd Step 3rd Step


Interpolation of Indoor WB Interpolation of Indoor DB Interpolation of Outdoor DB
Find TC, SC & PI Find TC, SC & PI Find TC, SC & PI
(a) Indoor: 25°C DB, 16°C WB (a) Indoor: 25°C DB, 17°C WB (a) Indoor: 25°C DB, 17°C WB
Outdoor: 35°C DB Outdoor: 35°C DB Outdoor: 37°C DB
(b) Indoor: 25°C DB, 19°C WB (b) Indoor: 25°C DB, 17°C WB
Outdoor: 35°C DB Outdoor: 40°C DB
(c) Indoor: 25°C DB, 16°C WB
Outdoor: 40°C DB
(d) Indoor: 25°C DB, 19°C WB
Outdoor: 40°C DB

Details of Calculation:
1st Step: By Interpolation Method
To obtain the TC, SC & PI for 25°C – 24°C x1 – 1.80kW
⇒ =
27°C – 24°C 1.83kW – 1.80kW
(a) Indoor Condition: 25°C DB, 16°C WB
Outdoor Condition: 35°C DB ⇒ x1 = 1.81kW
Outdoor temperature Similarly,
EWB EDB 35°C
y1 = 1.75kW
TC SC PI
z1 = 0.63kW

24 1.80 1.71 0.63


16 25 x1 y1 z1
27 1.83 1.83 0.63

12
Performance Data

(b) Indoor Condition: 25°C DB, 19°C WB By Interpolation Method


Outdoor Condition: 35°C DB 25°C – 24°C x2 – 1.99kW
⇒ =
Outdoor temperature 27°C – 24°C 1.99kW – 1.99kW
EWB EDB 35°C ⇒ x2 = 1.99kW
TC SC PI
Similarly,
y2 = 1.39kW
24 1.99 1.32 0.64
19 25 x2 y2 z2 z2 = 0.64kW
27 1.99 1.53 0.64

Repeat the same process for (c) & (d) in 1st Step

(c) x3 = 1.69 kW; y3 = 1.63 kW; z3 = 0.68 kW (d) x4 = 1.83 W; y4 = 1.30 kW; z4 = 0.69 kW

2nd Step: By Interpolation Method


To obtain the TC, SC & PI for 17°C – 16°C x5 – 1.81kW
⇒ =
(a) Indoor Condition: 25°C DB, 17°C WB 19°C – 16°C 1.99kW – 1.81kW
Outdoor Condition: 35°C DB ⇒ x5 = 1.87kW
Outdoor temperature Similarly,
EWB EDB 35°C
y5 = 1.63kW
TC SC PI
z5 =0.63kW

16 1.81 1.75 0.63


17 25 x5 y5 z5
19 1.99 1.39 0.64

Repeat the same process for (b) in 2nd Step

(c) x6 = 1.74 kW; y6 = 1.52 kW; z6 = 0.68 kW

3rd Step:
To obtain the TC, SC & PI for
(a) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 37°C DB
Outdoor temperature
EWB EDB 35°C 37°C 40°C
TC SC PI TC SC PI TC SC PI

25 17 1.87 1.63 0.63 x y z 1.74 1.52 0.68

By Interpolation Method Similarly,


37°C – 35°C x – 1.87kW y = 1.59kW
⇒ =
40°C – 35°C 1.74kW – 1.87kW z = 0.65kW
⇒ x = 1.82kW

13
Performance Data

Performance Tables

Model: FTV25C - RV25C


Cooling Mode
Outdoor temperature
AFR
EWB EDB 19°C 25°C 30°C 35°C 40°C 46°C
(CFM)
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
21°C 2.49 2.11 0.59 2.40 2.06 0.64 2.31 2.00 0.69 2.22 1.94 0.75 2.04 1.81 0.82 1.88 1.70 0.90
24°C 2.49 2.49 0.59 2.40 2.40 0.64 2.31 2.31 0.69 2.22 2.22 0.75 2.04 2.04 0.82 1.89 1.89 0.90
16°C
27°C 2.51 2.51 0.59 2.43 2.43 0.64 2.34 2.34 0.70 2.25 2.25 0.75 2.08 2.08 0.82 1.94 1.94 0.90
30°C 2.59 2.59 0.60 2.51 2.51 0.65 2.44 2.44 0.70 2.36 2.36 0.76 2.19 2.19 0.83 2.05 2.05 0.91
24°C 2.74 1.97 0.60 2.65 1.92 0.65 2.55 1.87 0.71 2.45 1.82 0.77 2.25 1.69 0.83 2.08 1.59 0.92
27°C 2.75 2.26 0.60 2.65 2.21 0.65 2.55 2.15 0.71 2.45 2.10 0.77 2.25 1.97 0.83 2.08 1.86 0.92
225 19°C
30°C 2.75 2.75 0.60 2.66 2.66 0.65 2.56 2.56 0.71 2.46 2.46 0.77 2.27 2.27 0.83 2.11 2.11 0.92
33°C 2.78 2.78 0.60 2.69 2.69 0.65 2.61 2.61 0.71 2.52 2.52 0.77 2.33 2.33 0.84 2.18 2.18 0.92
27°C 3.02 1.93 0.61 2.92 1.88 0.66 2.81 1.84 0.72 2.70 1.79 0.78 2.48 1.66 0.85 2.30 1.57 0.93
30°C 3.02 2.35 0.61 2.92 2.30 0.66 2.81 2.25 0.72 2.70 2.20 0.78 2.48 2.06 0.85 2.30 1.95 0.93
22°C
33°C 3.02 2.75 0.61 2.92 2.69 0.66 2.81 2.64 0.72 2.70 2.59 0.78 2.49 2.43 0.85 2.30 2.30 0.93
36°C 3.03 3.03 0.61 2.93 2.93 0.66 2.83 2.83 0.72 2.73 2.73 0.78 2.52 2.52 0.85 2.34 2.34 0.94
21°C 2.59 2.20 0.60 2.50 2.15 0.65 2.40 2.09 0.70 2.30 2.03 0.76 2.11 1.89 0.82 1.95 1.78 0.91
24°C 2.60 2.60 0.60 2.50 2.50 0.65 2.41 2.41 0.70 2.31 2.31 0.76 2.13 2.13 0.82 1.96 1.96 0.91
16°C
27°C 2.63 2.63 0.60 2.54 2.54 0.65 2.45 2.45 0.70 2.36 2.36 0.76 2.18 2.18 0.83 2.03 2.03 0.91
30°C 2.74 2.74 0.60 2.66 2.66 0.65 2.58 2.58 0.71 2.49 2.49 0.77 2.31 2.31 0.84 2.16 2.16 0.92
24°C 2.85 2.08 0.61 2.75 2.03 0.66 2.65 1.98 0.71 2.54 1.93 0.77 2.33 1.79 0.84 2.16 1.69 0.92
27°C 2.86 2.40 0.61 2.76 2.35 0.66 2.65 2.30 0.71 2.55 2.24 0.77 2.34 2.09 0.84 2.16 1.98 0.92
282 19°C
30°C 2.87 2.87 0.61 2.77 2.77 0.66 2.67 2.67 0.71 2.57 2.57 0.77 2.37 2.37 0.84 2.20 2.20 0.93
33°C 2.92 2.92 0.61 2.83 2.83 0.66 2.74 2.74 0.72 2.65 2.65 0.78 2.45 2.45 0.85 2.29 2.29 0.93
27°C 3.13 2.04 0.62 3.02 1.99 0.67 2.91 1.94 0.73 2.80 1.89 0.79 2.57 1.76 0.85 2.38 1.66 0.94
30°C 3.14 2.50 0.62 3.03 2.45 0.67 2.92 2.40 0.73 2.80 2.34 0.79 2.57 2.19 0.86 2.38 2.08 0.94
22°C
33°C 3.14 2.94 0.62 3.03 2.88 0.67 2.92 2.82 0.73 2.81 2.76 0.79 2.58 2.58 0.86 2.39 2.39 0.94
36°C 3.16 3.16 0.62 3.06 3.06 0.67 2.95 2.95 0.73 2.85 2.85 0.79 2.63 2.63 0.86 2.45 2.45 0.95
21°C 2.69 2.30 0.60 2.59 2.24 0.65 2.49 2.18 0.71 2.38 2.12 0.77 2.19 1.98 0.83 2.02 1.86 0.91
24°C 2.70 2.70 0.60 2.60 2.60 0.65 2.50 2.50 0.71 2.40 2.40 0.77 2.21 2.21 0.83 2.04 2.04 0.92
16°C
27°C 2.74 2.74 0.61 2.65 2.65 0.66 2.56 2.56 0.71 2.47 2.47 0.77 2.28 2.28 0.84 2.13 2.13 0.92
30°C 2.88 2.88 0.61 2.80 2.80 0.66 2.71 2.71 0.72 2.62 2.62 0.78 2.43 2.43 0.85 2.27 2.27 0.93
24°C 2.96 2.21 0.61 2.85 2.15 0.66 2.74 2.10 0.72 2.63 2.04 0.78 2.41 1.90 0.85 2.23 1.79 0.93
27°C 2.96 2.55 0.61 2.86 2.49 0.66 2.75 2.44 0.72 2.64 2.38 0.78 2.42 2.22 0.85 2.24 2.10 0.93
342 19°C
30°C 2.99 2.99 0.61 2.88 2.88 0.67 2.78 2.78 0.72 2.67 2.67 0.78 2.46 2.46 0.85 2.29 2.29 0.94
33°C 3.05 3.05 0.62 2.96 2.96 0.67 2.87 2.87 0.73 2.78 2.78 0.79 2.57 2.57 0.86 2.41 2.41 0.95
27°C 3.24 2.16 0.62 3.13 2.11 0.68 3.01 2.06 0.73 2.89 2.00 0.79 2.65 1.87 0.86 2.45 1.77 0.95
30°C 3.25 2.66 0.62 3.13 2.61 0.68 3.02 2.55 0.73 2.90 2.50 0.80 2.66 2.34 0.86 2.46 2.22 0.95
22°C
33°C 3.26 3.12 0.63 3.15 3.06 0.68 3.03 3.00 0.73 2.91 2.91 0.80 2.68 2.68 0.86 2.48 2.48 0.95
36°C 3.29 3.29 0.63 3.19 3.19 0.68 3.08 3.08 0.74 2.97 2.97 0.80 2.74 2.74 0.87 2.56 2.56 0.96

Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling Capacity (kW)
SC: Sensible Cooling Capacity (kW)
PI: Power Input (kW)

Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) without pressure trip.

14
Performance Data

Model: FTV35C - RV35C


Cooling Mode
Outdoor temperature
AFR
EWB EDB 19°C 25°C 30°C 35°C 40°C 46°C
(CFM)
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
21°C 3.32 2.41 0.84 3.20 2.35 0.90 3.08 2.28 0.98 2.96 2.22 1.06 2.72 2.06 1.15 2.51 1.94 1.27
24°C 3.32 2.89 0.84 3.20 2.82 0.90 3.09 2.75 0.98 2.96 2.69 1.06 2.72 2.51 1.15 2.52 2.37 1.27
16°C
27°C 3.35 3.27 0.84 3.24 3.20 0.91 3.12 3.12 0.98 3.01 3.01 1.06 2.77 2.77 1.16 2.58 2.58 1.27
30°C 3.45 3.45 0.84 3.35 3.35 0.91 3.25 3.25 0.99 3.15 3.15 1.07 2.92 2.92 1.17 2.73 2.73 1.29
24°C 3.66 2.25 0.85 3.53 2.19 0.92 3.40 2.13 1.00 3.27 2.07 1.08 3.00 1.93 1.17 2.78 1.82 1.29
27°C 3.66 2.57 0.85 3.53 2.52 0.92 3.40 2.46 1.00 3.27 2.40 1.08 3.01 2.24 1.17 2.78 2.13 1.29
242 19°C
30°C 3.67 3.18 0.85 3.54 3.11 0.92 3.42 3.04 1.00 3.29 2.97 1.08 3.03 2.77 1.17 2.81 2.63 1.29
33°C 3.71 3.71 0.85 3.59 3.59 0.92 3.47 3.47 1.00 3.36 3.36 1.09 3.10 3.10 1.18 2.90 2.90 1.30
27°C 4.03 2.20 0.86 3.89 2.15 0.94 3.75 2.09 1.02 3.60 2.04 1.10 3.31 1.90 1.19 3.06 1.79 1.32
30°C 4.03 2.68 0.86 3.89 2.63 0.94 3.75 2.57 1.02 3.60 2.51 1.10 3.31 2.35 1.19 3.06 2.22 1.32
22°C
33°C 4.03 3.13 0.86 3.89 3.07 0.94 3.75 3.01 1.02 3.60 2.95 1.10 3.31 2.77 1.19 3.07 2.63 1.32
36°C 4.04 3.55 0.87 3.91 3.48 0.94 3.77 3.41 1.02 3.64 3.34 1.10 3.35 3.13 1.20 3.12 2.97 1.32
21°C 3.45 2.51 0.84 3.33 2.45 0.91 3.20 2.38 0.99 3.07 2.32 1.07 2.82 2.16 1.16 2.60 2.03 1.28
24°C 3.46 3.05 0.84 3.34 2.98 0.91 3.21 2.91 0.99 3.08 2.84 1.07 2.83 2.65 1.16 2.62 2.50 1.28
16°C
27°C 3.51 3.47 0.85 3.39 3.39 0.91 3.27 3.27 0.99 3.15 3.15 1.08 2.91 2.91 1.17 2.71 2.71 1.29
30°C 3.65 3.65 0.85 3.55 3.55 0.92 3.44 3.44 1.00 3.33 3.33 1.09 3.08 3.08 1.18 2.88 2.88 1.30
24°C 3.80 2.38 0.86 3.67 2.32 0.93 3.53 2.26 1.01 3.39 2.20 1.09 3.11 2.05 1.18 2.88 1.93 1.30
27°C 3.81 2.74 0.86 3.67 2.68 0.93 3.54 2.62 1.01 3.40 2.56 1.09 3.12 2.39 1.18 2.88 2.26 1.30
298 19°C
30°C 3.83 3.38 0.86 3.70 3.31 0.93 3.56 3.23 1.01 3.43 3.15 1.09 3.16 2.95 1.19 2.93 2.79 1.31
33°C 3.89 3.89 0.86 3.77 3.77 0.93 3.65 3.65 1.01 3.53 3.53 1.10 3.27 3.27 1.19 3.06 3.06 1.32
27°C 4.18 2.33 0.87 4.03 2.27 0.95 3.88 2.22 1.02 3.73 2.16 1.11 3.43 2.01 1.21 3.17 1.90 1.33
30°C 4.18 2.86 0.87 4.04 2.80 0.95 3.89 2.74 1.03 3.73 2.67 1.11 3.43 2.50 1.21 3.17 2.37 1.33
22°C
33°C 4.19 3.35 0.87 4.05 3.28 0.95 3.90 3.22 1.03 3.74 3.15 1.11 3.45 2.95 1.21 3.19 2.80 1.33
36°C 4.22 3.79 0.87 4.08 3.71 0.95 3.94 3.64 1.03 3.80 3.55 1.12 3.50 3.32 1.21 3.27 3.14 1.34
21°C 3.58 2.62 0.85 3.45 2.56 0.92 3.32 2.49 1.00 3.18 2.42 1.08 2.92 2.25 1.17 2.69 2.12 1.29
24°C 3.60 3.19 0.85 3.47 3.11 0.92 3.34 3.04 1.00 3.20 2.96 1.08 2.94 2.76 1.17 2.72 2.60 1.29
16°C
27°C 3.66 3.65 0.85 3.54 3.54 0.92 3.42 3.42 1.00 3.30 3.30 1.09 3.05 3.05 1.18 2.84 2.84 1.30
30°C 3.84 3.84 0.86 3.73 3.73 0.93 3.61 3.61 1.01 3.49 3.49 1.10 3.24 3.24 1.19 3.02 3.02 1.32
24°C 3.94 2.52 0.86 3.80 2.45 0.94 3.65 2.39 1.01 3.51 2.33 1.10 3.22 2.17 1.19 2.97 2.05 1.31
27°C 3.95 2.91 0.86 3.81 2.85 0.94 3.67 2.78 1.01 3.52 2.71 1.10 3.23 2.53 1.19 2.99 2.40 1.31
355 19°C
30°C 3.99 3.58 0.87 3.84 3.50 0.94 3.71 3.42 1.02 3.57 3.34 1.10 3.28 3.12 1.20 3.05 2.94 1.32
33°C 4.07 4.07 0.87 3.95 3.95 0.94 3.83 3.83 1.02 3.70 3.70 1.11 3.43 3.43 1.21 3.21 3.21 1.33
27°C 4.33 2.46 0.88 4.17 2.41 0.95 4.01 2.35 1.03 3.85 2.29 1.12 3.54 2.13 1.22 3.27 2.01 1.34
30°C 4.33 3.03 0.88 4.18 2.98 0.95 4.02 2.91 1.03 3.86 2.85 1.12 3.55 2.67 1.22 3.28 2.53 1.34
22°C
33°C 4.35 3.56 0.88 4.20 3.49 0.96 4.04 3.42 1.04 3.89 3.35 1.12 3.57 3.14 1.22 3.31 2.98 1.34
36°C 4.39 4.02 0.88 4.25 3.94 0.96 4.10 3.86 1.04 3.96 3.76 1.13 3.66 3.51 1.22 3.41 3.30 1.35

Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling Capacity (kW)
SC: Sensible Cooling Capacity (kW)
PI: Power Input (kW)

Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) without pressure trip.

15
Performance Data

Model: FTV50C - RV50C


Cooling Mode
Outdoor temperature
AFR
EWB EDB 19°C 25°C 30°C 35°C 40°C 46°C
(CFM)
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
21°C 4.98 3.48 1.38 4.80 3.39 1.49 4.62 3.29 1.61 4.44 3.20 1.75 4.08 2.98 1.89 3.76 2.80 2.09
24°C 4.99 4.16 1.38 4.81 4.07 1.49 4.63 3.97 1.61 4.45 3.87 1.75 4.08 3.62 1.90 3.78 3.41 2.09
16°C
27°C 5.02 4.72 1.38 4.86 4.61 1.49 4.69 4.50 1.61 4.51 4.39 1.75 4.16 4.08 1.90 3.87 3.84 2.10
30°C 5.18 5.18 1.38 5.03 5.03 1.50 4.88 4.88 1.63 4.72 4.72 1.76 4.38 4.38 1.92 4.09 4.09 2.12
24°C 5.49 3.25 1.40 5.30 3.16 1.51 5.10 3.08 1.64 4.90 2.99 1.78 4.51 2.79 1.93 4.17 2.62 2.12
27°C 5.50 3.71 1.40 5.30 3.63 1.51 5.11 3.55 1.64 4.91 3.46 1.78 4.51 3.24 1.93 4.17 3.07 2.13
422 19°C
30°C 5.50 4.58 1.40 5.31 4.48 1.51 5.13 4.39 1.64 4.93 4.28 1.78 4.54 4.00 1.93 4.21 3.79 2.13
33°C 5.57 5.57 1.40 5.39 5.39 1.52 5.21 5.21 1.65 5.04 5.04 1.79 4.66 4.66 1.94 4.36 4.36 2.14
27°C 6.04 3.18 1.42 5.83 3.10 1.54 5.62 3.02 1.67 5.40 2.94 1.81 4.97 2.74 1.97 4.60 2.58 2.17
30°C 6.04 3.87 1.42 5.84 3.79 1.54 5.62 3.70 1.67 5.40 3.61 1.81 4.97 3.38 1.97 4.60 3.21 2.17
22°C
33°C 6.05 4.52 1.42 5.84 4.44 1.54 5.63 4.35 1.67 5.41 4.26 1.81 4.97 4.00 1.97 4.61 3.80 2.17
36°C 6.07 5.13 1.42 5.87 5.02 1.54 5.66 4.92 1.67 5.46 4.81 1.82 5.03 4.51 1.97 4.68 4.28 2.17
21°C 5.18 3.62 1.39 4.99 3.53 1.50 4.80 3.44 1.63 4.61 3.34 1.76 4.23 3.11 1.91 3.90 2.93 2.11
24°C 5.20 4.40 1.39 5.01 4.30 1.50 4.82 4.19 1.63 4.63 4.09 1.76 4.25 3.81 1.91 3.93 3.60 2.11
16°C
27°C 5.26 5.00 1.39 5.08 4.88 1.51 4.91 4.76 1.63 4.73 4.61 1.77 4.37 4.29 1.92 4.07 4.01 2.12
30°C 5.48 5.48 1.40 5.32 5.32 1.52 5.16 5.16 1.65 4.99 4.99 1.79 4.62 4.62 1.94 4.32 4.32 2.14
24°C 5.71 3.43 1.41 5.50 3.34 1.53 5.30 3.26 1.65 5.08 3.17 1.79 4.67 2.95 1.95 4.31 2.78 2.14
27°C 5.72 3.95 1.41 5.51 3.86 1.53 5.31 3.78 1.65 5.09 3.69 1.79 4.68 3.45 1.95 4.33 3.26 2.14
474 19°C
30°C 5.74 4.87 1.41 5.54 4.77 1.53 5.35 4.66 1.66 5.14 4.55 1.80 4.73 4.25 1.95 4.39 4.02 2.15
33°C 5.84 5.84 1.42 5.66 5.66 1.54 5.48 5.48 1.67 5.30 5.30 1.81 4.91 4.91 1.96 4.59 4.59 2.17
27°C 6.27 3.36 1.44 6.05 3.28 1.56 5.82 3.20 1.69 5.59 3.11 1.83 5.14 2.90 1.98 4.75 2.74 2.18
30°C 6.28 4.12 1.44 6.06 4.03 1.56 5.83 3.94 1.69 5.60 3.85 1.83 5.15 3.61 1.98 4.76 3.42 2.19
22°C
33°C 6.29 4.83 1.44 6.07 4.74 1.56 5.85 4.64 1.69 5.62 4.54 1.83 5.17 4.26 1.99 4.79 4.04 2.19
36°C 6.33 5.46 1.44 6.12 5.35 1.56 5.91 5.24 1.69 5.69 5.12 1.84 5.25 4.79 1.99 4.90 4.52 2.20
21°C 5.37 3.78 1.40 5.17 3.69 1.51 4.98 3.59 1.64 4.77 3.49 1.78 4.37 3.25 1.93 4.03 3.06 2.12
24°C 5.40 4.60 1.40 5.20 4.49 1.51 5.01 4.38 1.64 4.81 4.26 1.78 4.41 3.98 1.93 4.08 3.75 2.13
16°C
27°C 5.49 5.27 1.40 5.31 5.13 1.52 5.13 4.99 1.65 4.94 4.83 1.79 4.57 4.48 1.94 4.26 4.18 2.14
30°C 5.76 5.76 1.42 5.59 5.59 1.53 5.42 5.42 1.66 5.24 5.24 1.81 4.85 4.85 1.96 4.53 4.53 2.17
24°C 5.91 3.63 1.42 5.70 3.54 1.54 5.48 3.45 1.67 5.26 3.35 1.81 4.83 3.13 1.96 4.46 2.95 2.16
27°C 5.93 4.20 1.42 5.72 4.10 1.54 5.50 4.01 1.67 5.28 3.91 1.81 4.85 3.65 1.96 4.48 3.46 2.16
531 19°C
30°C 5.98 5.17 1.43 5.77 5.05 1.54 5.56 4.94 1.67 5.35 4.81 1.81 4.92 4.50 1.97 4.57 4.24 2.17
33°C 6.11 6.11 1.43 5.93 5.93 1.55 5.75 5.75 1.68 5.56 5.56 1.83 5.15 5.15 1.99 4.81 4.81 2.19
27°C 6.49 3.55 1.45 6.26 3.47 1.57 6.02 3.38 1.70 5.78 3.30 1.84 5.31 3.07 2.00 4.91 2.90 2.20
30°C 6.50 4.38 1.45 6.27 4.29 1.57 6.03 4.20 1.70 5.79 4.10 1.85 5.32 3.84 2.00 4.92 3.64 2.20
22°C
33°C 6.52 5.13 1.45 6.30 5.04 1.57 6.07 4.93 1.70 5.83 4.82 1.85 5.36 4.52 2.01 4.97 4.29 2.21
36°C 6.58 5.79 1.45 6.38 5.68 1.58 6.16 5.56 1.71 5.93 5.42 1.86 5.48 5.06 2.01 5.11 4.76 2.22

Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling Capacity (kW)
SC: Sensible Cooling Capacity (kW)
PI: Power Input (kW)

Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) without pressure trip.

16
Performance Data

Model: FTV60C - RV60C


Cooling Mode
Outdoor temperature
AFR
EWB EDB 19°C 25°C 30°C 35°C 40°C 46°C
(CFM)
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
21°C 6.08 4.19 1.61 5.87 4.08 1.74 5.65 3.97 1.88 5.42 3.86 2.04 4.98 3.59 2.21 4.60 3.38 2.44
24°C 6.09 5.02 1.61 5.87 4.90 1.74 5.66 4.79 1.88 5.43 4.67 2.04 4.99 4.36 2.22 4.61 4.11 2.44
16°C
27°C 6.14 5.69 1.61 5.93 5.56 1.74 5.73 5.43 1.89 5.51 5.29 2.05 5.08 4.92 2.22 4.73 4.62 2.45
30°C 6.33 6.33 1.62 6.15 6.15 1.75 5.96 5.96 1.90 5.77 5.77 2.06 5.35 5.35 2.24 5.00 5.00 2.47
24°C 6.71 3.91 1.63 6.47 3.81 1.77 6.24 3.71 1.91 5.99 3.61 2.08 5.50 3.36 2.25 5.09 3.16 2.48
27°C 6.71 4.47 1.63 6.48 4.37 1.77 6.24 4.27 1.92 5.99 4.17 2.08 5.51 3.90 2.25 5.09 3.70 2.48
474 19°C
30°C 6.72 5.52 1.63 6.49 5.40 1.77 6.26 5.28 1.92 6.02 5.16 2.08 5.55 4.82 2.26 5.15 4.56 2.49
33°C 6.80 6.80 1.64 6.58 6.58 1.77 6.37 6.37 1.92 6.15 6.15 2.09 5.69 5.69 2.27 5.32 5.32 2.50
27°C 7.38 3.83 1.66 7.12 3.74 1.80 6.87 3.64 1.95 6.60 3.54 2.12 6.07 3.30 2.30 5.62 3.11 2.53
30°C 7.38 4.66 1.66 7.13 4.57 1.80 6.87 4.46 1.95 6.60 4.36 2.12 6.07 4.08 2.30 5.62 3.87 2.53
22°C
33°C 7.39 5.45 1.66 7.13 5.34 1.80 6.87 5.24 1.95 6.60 5.13 2.12 6.08 4.82 2.30 5.63 4.57 2.53
36°C 7.41 6.18 1.66 7.17 6.05 1.80 6.92 5.93 1.96 6.67 5.80 2.12 6.15 5.44 2.30 5.72 5.16 2.54
21°C 6.33 4.37 1.62 6.10 4.26 1.75 5.87 4.14 1.90 5.63 4.03 2.06 5.16 3.75 2.23 4.76 3.53 2.46
24°C 6.35 5.30 1.62 6.12 5.18 1.75 5.89 5.05 1.90 5.65 4.93 2.06 5.19 4.60 2.24 4.80 4.34 2.46
16°C
27°C 6.42 6.02 1.63 6.21 5.88 1.76 5.99 5.73 1.91 5.78 5.56 2.07 5.33 5.16 2.25 4.97 4.83 2.48
30°C 6.69 6.69 1.64 6.50 6.50 1.77 6.30 6.30 1.92 6.09 6.09 2.09 5.65 5.65 2.27 5.28 5.28 2.50
24°C 6.97 4.13 1.65 6.72 4.03 1.78 6.47 3.92 1.93 6.21 3.82 2.10 5.70 3.56 2.27 5.27 3.35 2.50
27°C 6.98 4.76 1.65 6.73 4.65 1.78 6.48 4.55 1.93 6.22 4.44 2.10 5.72 4.15 2.27 5.29 3.93 2.51
537 19°C
30°C 7.02 5.87 1.65 6.77 5.74 1.79 6.53 5.62 1.94 6.28 5.48 2.10 5.78 5.12 2.28 5.36 4.84 2.51
33°C 7.13 7.13 1.66 6.92 6.92 1.79 6.70 6.70 1.95 6.47 6.47 2.11 6.00 6.00 2.30 5.61 5.61 2.53
27°C 7.66 4.05 1.68 7.39 3.95 1.82 7.12 3.85 1.97 6.83 3.75 2.14 6.28 3.49 2.32 5.81 3.30 2.55
30°C 7.67 4.96 1.68 7.40 4.86 1.82 7.12 4.75 1.97 6.84 4.64 2.14 6.29 4.35 2.32 5.82 4.13 2.55
22°C
33°C 7.68 5.82 1.68 7.42 5.71 1.82 7.14 5.59 1.97 6.86 5.47 2.14 6.31 5.13 2.32 5.85 4.87 2.56
36°C 7.73 6.58 1.68 7.48 6.45 1.82 7.22 6.32 1.98 6.96 6.17 2.15 6.42 5.77 2.33 5.98 5.45 2.57
21°C 6.56 4.56 1.63 6.32 4.44 1.77 6.08 4.33 1.91 5.83 4.20 2.08 5.34 3.92 2.25 4.93 3.69 2.48
24°C 6.60 5.54 1.64 6.36 5.41 1.77 6.12 5.27 1.92 5.87 5.14 2.08 5.39 4.79 2.25 4.98 4.52 2.48
16°C
27°C 6.70 6.35 1.64 6.48 6.18 1.78 6.26 6.01 1.93 6.04 5.82 2.09 5.58 5.40 2.27 5.20 5.04 2.50
30°C 7.04 7.04 1.66 6.83 6.83 1.79 6.62 6.62 1.95 6.40 6.40 2.11 5.93 5.93 2.29 5.54 5.54 2.53
24°C 7.22 4.37 1.66 6.96 4.26 1.80 6.70 4.15 1.95 6.42 4.04 2.11 5.90 3.77 2.29 5.44 3.55 2.52
27°C 7.24 5.06 1.66 6.98 4.94 1.80 6.72 4.83 1.95 6.45 4.71 2.12 5.92 4.40 2.29 5.47 4.17 2.53
614 19°C
30°C 7.30 6.22 1.67 7.05 6.09 1.80 6.79 5.95 1.95 6.53 5.80 2.12 6.01 5.42 2.30 5.58 5.11 2.54
33°C 7.46 7.46 1.67 7.24 7.24 1.81 7.02 7.02 1.97 6.79 6.79 2.14 6.29 6.29 2.32 5.88 5.88 2.56
27°C 7.93 4.28 1.69 7.64 4.18 1.83 7.36 4.08 1.99 7.06 3.97 2.16 6.48 3.71 2.34 5.99 3.50 2.57
30°C 7.94 5.27 1.69 7.66 5.17 1.83 7.37 5.06 1.99 7.07 4.94 2.16 6.50 4.63 2.34 6.01 4.39 2.58
22°C
33°C 7.97 6.18 1.70 7.69 6.07 1.84 7.41 5.94 1.99 7.12 5.81 2.16 6.55 5.45 2.34 6.07 5.17 2.58
36°C 8.04 6.98 1.70 7.79 6.85 1.84 7.52 6.70 2.00 7.25 6.53 2.17 6.70 6.09 2.35 6.25 5.74 2.60

Remark:
AFR: Air flow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling Capacity (kW)
SC: Sensible Cooling Capacity (kW)
PI: Power Input (kW)

Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) without pressure trip.

17
Outline & Dimension

Outline & Dimension


Indoor Unit

Model: FTV25/35C

FOR ILLUSTRATIVE PURPOSES ONLY


THE MARK SHOWS PIPING DIRECTION

REAR REAR
LEFT RIGHT

TOP VIEW C
A

NAME
PLATE

SIGNAL RECEIVER B

TERMINAL
BLOCK
BOTTOM BOTTOM INDOOR UNIT SIDE VIEW WITH EARTH
LOUVER ON/OFF SWITCH TERMINAL
FRONT GRILLE FIXED SCREWS ROOM TEMPERATURE THERMISTOR
(INSIDE) (INSIDE)
FRONT VIEW

 Recommended mounti ng pl ate retenti on spots


(5 spots in all)
D E

F
F

Through the wall


B

hole Ø 65mm
G
G

H J Drain hose position


L M K I
A

Liquid pipe end Gas pipe end

INSTALLATION PLATE 25/35

Dimension
A B C D E F G H I J K L M
Model
25/35 800 288 206 104 141 30 46 55 56 153 181 207 52

Note: Dimension in mm

18
Outline & Dimension

Model: FTV50/60C
FOR ILLUSTRATIVE PURPOSES ONLY
THE MARK SHOWS PIPING DIRECTION

REAR REAR
LEFT RIGHT

TOP VIEW C
A

NAME
PLATE

SIGNAL RECEIVER B

TERMINAL
BLOCK
BOTTOM BOTTOM INDOOR UNIT SIDE VIEW WITH EARTH
LOUVER ON/OFF SWITCH TERMINAL
FRONT GRILLE FIXED SCREWS ROOM TEMPERATURE THERMISTOR
(INSIDE) (INSIDE)
FRONT VIEW

 Recommended mounti ng pl ate retenti on spots


(7 spots in all)

D E

F
F
B

Through the wall


hole Ø 65mm
G

H J Liquid pipe end Gas pipe end K I Drain hose position


L M
A

INSTALLATION PLATE 50/60

Dimension
A B C D E F G H I J K L M
Model
50/60 1065 310 224 190 173 61 40 45 48 91 219 580 45

Note: Dimension in mm

19
Outline & Dimension

Outdoor Unit

Model: RV25C
FOR ILLUSTRATIVE PURPOSES ONLY
D E F

H
G
C

H
A M L

N
O
B

K
J
P Q
I

Dimension
A B C D E F G H I J K L M N O P Q
Model
25 566 463 256 89 366 111 297 30 22 63 55 70 117 41 167 85 43

Note: Dimension in mm

Model: RV35C
FOR ILLUSTRATIVE PURPOSES ONLY

J H I
O
G

N
Q
P

E F D B C
2.0
A

L
K
M

Dimension
A B C D E F G H I J K L M N O P Q
Model
35 550 658 51 11 273 16 14 470 96 93 94 60 14 133 8 10 299

Note: Dimension in mm

20
Outline & Dimension

Model: RV50/60C
FOR ILLUSTRATIVE PURPOSES ONLY
L K L

N
M

Q
C

N
A
G H
O D

F
T

E
B

S
R
I J
P

Dimension
A B C D E F G H I J K L M
Model
50/60 855 628 328 520 179 46 93 149 101 113 603 126 164

Dimension
N O P Q R S T
Model
50/60 15 34 23 362 73 75 67

Note: Dimension in mm

21
Wiring Diagram

Wiring Diagrams
Cooling Only
Indoor Unit Outdoor Unit
Model: FTV25C Model: RV25C

L
POWER SUPPLY
N
220-240V/1Ph/50Hz
E

22
Wiring Diagram

Indoor Unit Outdoor Unit


Model: FTV35C Model: RV35C

L
POWER SUPPLY
N
220-240V/1Ph/50Hz
E

23
Wiring Diagram

Indoor Unit Outdoor Unit


Model: FTV50/60C Model: RV50/60C

L
POWER SUPPLY
N
220-240V/1Ph/50Hz
E

24
Service & Maintenance

Service & Maintenance

• Disconnect from main supply before servicing the air conditioner.


• The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly
checked and the following items should be given due attention.

Components Maintenance Procedures Period


1. Remove any dust adhering to the filter by using a vacuum cleaner At least once every 2
or wash in lukewarm water (below 40˚C) with a neutral cleaning weeks.
Air Filter detergent. More frequently if
(Indoor Unit) 2. Rinse the filter well and dry before placing it back onto the unit. necessary.
3. Note: Never use gasoline, volatile substances or chemicals to
clean the filter.
1. Clean any dirt or dust on the grille or panel by wiping it with a At least once every 2
soft cloth soaked in lukewarm water (below 40˚C) and a neutral weeks.
Indoor Unit detergent solution. More frequently if
2. Note: Never use gasoline, volatile substances or chemicals to necessary.
clean the indoor unit.
Condense Drain 1. Check the cleanliness and clean it if necessary. Every 3 months.
Pan & Pipe 2. Check the condensate water flow.
Indoor Fan Check if there is any abnormal noise. If necessary.
1. Check and remove the dirt between the fins. Every month.
Indoor / Outdoor
2. Check and remove any obstacles which hinder air flow through
Coil
the indoor or outdoor.
1. Check the running current and voltage for indoor and outdoor Every 2 months.
unit.
Power Supply
2. Check the electrical wiring and tighten the wire onto the terminal Every year.
block if necessary.
No maintenance needed if refrigerant circuit remains sealed. How- Every 6 months.
Compressor
ever, check for refrigerant leak at joint and fitting.

Indoor Models Recess on


main unit
1. Open the front panel
• Hold the panel at the recesses on the main unit
(2 recesses on right and left sides) and lift it until
it stops.
2. Remove the front panel
• While lifting the front panel further, slide it to the
right and pull it to the front side. The left rotating
shaft is detached. Slide the right rotating shaft to
the left and pull it to the front side to remove it. Rotating
shaft
3. Attach the front panel
• Align the right and left rotating shafts of the front
panel with the grooves and push them all the
way in.
• Gently close the front panel. (Push both ends
and the center on the front panel.)

• Don’t touch the metal parts of the indoor unit. It may cause an injury.
• When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully.
• When removing or attaching the front panel, support the panel securely with hand to prevent from it falling.
• For cleansing, do no use hot water above 40°C, benzene, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff.
• After cleaning, make sure that the front panel is securely fixed.

25
Service & Maintenance

Pre Start Up Maintenance


(After Extended Shutdown)

- Inspect thoroughly and clean indoor and outdoor units.


- Clean or replace air filters.
- Clean condensates drain line.
- Clean clogged indoor and outdoor coils.
- Check fan imbalance before operation.
- Tighten all wiring connections and panels.
- Check for refrigerant leakage.

Outdoor Models
The design of the RV-C outdoor series allows servicing to be carried out easily. The removal of the top, front
and side panels makes almost every part accessible.

FOR ILLUSTRATIVE PURPOSES ONLY

Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface
once every 3 months. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must
be regularly cleaned by qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and
proper operation. Otherwise, the systems life span may be shortened.

• Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit when
performing a leakage test or an airtight test. These gases could cause severe explosion and damage if exposed to
high temperature and pressure.
• It is recommended that only nitrogen or refrigerant be charged when performing the leakage or airtight test.

26
Troubleshooting

Troubleshooting
Indicator Lights

IR Signal Receiver
When an infra red remote control operating signal has been transmitted, the signal receiver on the indoor unit
will respond as below to confirm acceptance of the signal transmission.

ON to OFF 1 Long Beep


OFF to ON
2 Short Beep
Pump down/Cool force on
Others 1 Short Beep

Cooling Unit
The table below shows the LED indicator lights for the air conditioner unit under normal operation and fault
conditions. The LED lights are located at the middle of the air conditioner unit.

IR Receiver

Cool
Timer
Sleep
ON/OFF ON/OFF switch

IR Receiver

LED Indoor Lights: Normal Operation and Fault Conditions for Cooling Unit

Error Normal Operation /


Action
Code Fault Indication
COOL
(GREEN)

- Cool mode -
Green

- Timer on -
- Sleep mode on -
- Fan mode on -
- Dry mode on -

Blink E1 Room air sensor contact loose / short Call your dealer
1 time

Blink E2 Indoor coil sensor open Call your dealer


2 times

Compressor overload /
Blink E4 Call your dealer
1 time indoor coil sensor short

Blink E8 Hardware error (tact switch pin short) Call your dealer
6 times

Blink E9 No feedback from indoor fan Call your dealer


4 times

ON ON or OFF Blinking

27

You might also like