Circuit Breakers For Protection of Low-Voltage Distribution Networks
Circuit Breakers For Protection of Low-Voltage Distribution Networks
Circuit Breakers For Protection of Low-Voltage Distribution Networks
ST-CM1
ST-CM2
ST-CM3
ST-CM electronic trip units can equip all ST-CM1: standard protection of circuits
Compact CM circuit breakers. They are ST-CM2: protection with discrimination
powered by toroids fitted in the circuit ST-CM3: protection with discrimination +
breakers and operate without an external earth-fault protection
source. Settings are made on the front face.
Three models are available.
t t t
1 1 1
T1
3 3 3
4 T2 4
5 5
0 Ir Im I 0 Ir Im I I 0 Ir Im I I
Trip unit ST-CM1 offers the following types Trip unit ST-CM2 offers the following types Trip unit ST-CM3 offers the following types
of protection: of protection: of protection:
■ long time protection against overloads with ■ long time protection against overloads with ■ long time protection against overloads with
adjustable Ir threshold (1) - 6 settings: adjustable Ir threshold (1) - 6 settings: adjustable Ir threshold (1) - 6 settings:
0.5...1 x In; 0.5...1 x In; 0.5...1 x In;
■ short time protection against short-circuits ■ short time protection against short-circuits: ■ short time protection against short-circuits:
with adjustable Im threshold (3) - 4 settings: ■ with adjustable Im threshold (3) - 4 ■ with adjustable Im threshold (3) - 4
3...6 x Ir. settings: 2...8 x Ir; settings: 2...8 x Ir;
■ with adjustable time delay (4) - 4 settings: ■ with adjustable time delay (4) - 4 settings:
0...225 s; 0...225 s;
■ instantaneous protection against short- ■ instantaneous protection against short-
circuits with fixed I threshold (5): 35 kA. circuits with fixed I threshold (5): 35 kA;
■ earth fault protection:
■ with adjustable T1 threshold - 4 settings:
0.2...0.5 x Ir;
■ with adjustable T2 time delay - 4 settings:
0...345 s.
10 Merlin Gerin
trip units ST-CM1 ST-CM2 ST-CM3
for Compact CM1250N/H to 3200N/H
overload protection (long time)
tripping threshold (A) Ir adjustable (6 settings) 0.5…1 x In 0.5…1 x In 0.5…1 x In
tripping time (s) at 1.5 Ir 90…160 90…160 90…160
short-circuit protection (short time)
tripping threshold (A) Im adjustable (4 settings) 3 - 4 - 5 - 6 x Ir 2 - 4 - 6 - 8 x Ir 2 - 4 - 6 - 8 x Ir
accuracy ± 20 % ± 15 % ± 15 %
time delay setting 0 A B C 0 A B C
max. overcurrent 0 35 125 225 0 35 125 225
time before tripping (ms)
total breaking time (ms) 50 120 220 330 50 120 220 330
short-circuit protection (instantaneous)
tripping threshold (kA) I 35 35
earth-fault protection
tripping threshold (A) Ih adjustable (4 settings) 0.2-0.3-0.4-0.5 x Ir
accuracy ± 15 % (1)
time delay(ms) setting 0 0.1 0.2 0.3
max. overcurrent 0 135 235 345
time before tripping (ms)
total breaking time (ms) 130 230 340 460
neutral protection
For networks with an unprotected distributed neutral, a 4th sensor can be supplied separately.
fault indication and reset ■ basic version: the trip unit has a reset ■ on request: the circuit breaker can be
button button on its front face. This button pops out reclosed without pressing the reset button.
in the event of a fault trip. The protection The SDE switch monitors the position of the
system must then be reset by pressing the reset button.
button back in. A normally-open micro-
switch contact (SDE) monitors the position
of the reset button to provide remote
indications.
Merlin Gerin 11