The document calculates the load current, circuit breaker rating, and wire cross section area for a lighting circuit. It determines the load current is 1.154 Amps, selects a 10 Amp circuit breaker since 1.44 Amps is required, and calculates the minimum wire cross section as 2.5 mm2 to safely carry 14.88 Amps.
The document calculates the load current, circuit breaker rating, and wire cross section area for a lighting circuit. It determines the load current is 1.154 Amps, selects a 10 Amp circuit breaker since 1.44 Amps is required, and calculates the minimum wire cross section as 2.5 mm2 to safely carry 14.88 Amps.
The document calculates the load current, circuit breaker rating, and wire cross section area for a lighting circuit. It determines the load current is 1.154 Amps, selects a 10 Amp circuit breaker since 1.44 Amps is required, and calculates the minimum wire cross section as 2.5 mm2 to safely carry 14.88 Amps.