VRF Smart Gateway Install

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

VRF Smart Gateway Installation Instructions

Part No. 24-10143-1183 Rev. E

2019-06-06

Update Software North American Emissions


Important: A software update may be available Compliance
for your device. For instructions on how to apply a
software update, see Updating the Software. United States

Applications This equipment has been tested and found to comply


with the limits for a Class A digital device pursuant to
You can use the Johnson Controls® Variable Refrigerant Part 15 of the FCC Rules. These limits are designed
Flow (VRF) Smart Gateway to integrate the Hitachi to provide reasonable protection against harmful
VRF system with a Building Automation System (BAS),
interference when this equipment is operated
such as the Metasys® system. The VRF Smart Gateway
bridges communication between the native H-Link in a commercial environment. This equipment
communications network of the Hitachi VRF system generates, uses, and can radiate radio frequency
and the open building standard BACnet®/IP network. energy and, if not installed and used in accordance
The VRF Smart Gateway transmits the VRF device and with the instruction manual, may cause harmful
point data over the BACnet/IP network in a way that
interference to radio communications. Operation
the BAS can easily discover and process. The VRF Smart
Gateway therefore requires little or no post-integration of this equipment in a residential area may cause
configuration within the BAS. The VRF Smart Gateway harmful interference, in which case the users will
includes a simple web server that provides a wireless be required to correct the interference at their own
mobile user interface for configuring communication expense.
parameters and performing VRF system discovery and
device naming. The wireless connection on the VRF RF Transmitters: Compliance Statement (Part
Smart Gateway allows users of a supported mobile 15.19)
device to be up to 30 m (100 ft, line of sight) away.
The VRF Smart Gateway also includes the following This device complies with Part 15 of the FCC Rules.
features and benefits: Operation is subject to the following two conditions:

• Supports up to 64 VRF systems. 1. This device may not cause harmful interference,
and
• Supports up to 160 Indoor Units, and up to
a combined total of 200 Indoor and Outdoor 2. This device must accept any interference
Units. However, the stability and reliability of received, including interference that may cause
communications across the H-LINK network is undesired operation.
increased if you limit each H-LINK segment to under Warning (Part 15.21)
100 units.
Changes or modifications not expressly approved by
• Integrates with both Metasys and Facility Explorer®
the party responsible for compliance could void the
(FX) building automation systems.
user’s authority to operate the equipment.
• Integrates with third party building automation
systems that support the BACnet IP protocol. RF Exposure (OET Bulletin 65)

• Supports BACnet Gateway (B-GW) and BACnet To comply with FCC RF exposure requirements for
Application Specific Controller (B-ASC) device mobile transmitting devices, this transmitter should
profiles. only be used or installed at locations where there is at
• Supports BACnet IP (Annex J) and BACnet Broadcast least 20 cm separation distance between the antenna
Management Device (BBMD). and all persons.

• Provides BACnet Command Priority enforcement.

*24101431183E*
24-10143-1183, Rev. E
Canada • Mount the VRF Smart Gateway in areas free of
corrosive vapors and observe the environmental
Industry Canada Statement limitations listed in the Technical Specifications
The term IC before the certification/registration section of this document.
number only signifies that the Industry Canada
• Mount the VRF Smart Gateway in a location where
technical specifications were met.
you can connect it to the H-LINK wire that runs
Le terme « IC » précédant le numéro d'accréditation/
between the Indoor Units (IDUs) or between the
inscription signifie simplement que le produit est
Outdoor Units (ODUs). See Wiring the H-Link
conforme aux spécifications techniques d'Industry
Network.
Canada.
• Objects such as ductwork, cabinets, doors, and
glass can impede the wireless signal. Minimize the
Installation number of objects between the connected computer
or mobile device and the VRF Smart Gateway. Use
Parts Included line of sight, if possible.

• VRF Smart Gateway • Metal objects (such as cabinet doors, enclosures,


and pipes) and concrete objects (such as pillars,
• Installation Instructions walls, and ceilings) may limit Wi-Fi service. To
• VRF Smart Gateway Quick Start Guide (Part No. accommodate potential structural obstacles on site,
24-10737-156) you can mount the VRF Smart Gateway flush against
the wall or perpendicular to it.
Note: If your model of the VRF Smart Gateway
• The VRF Smart Gateway is not rated for outdoor
does not include a power adapter, contact your
mounting.
local Johnson Controls representative to order one
separately.
Mounting Locations
Special Tools Needed You can attach the VRF Smart Gateway to a 1-1/8 in.
(35 mm) DIN rail or a flat vertical surface. Mounting the
The unit supports both DIN rail and surface mounting unit on a ceiling or in a way that positions the front of
options. If the unit is permanently mounted to a the unit facing down is not recommended.
vertical surface without a DIN rail, you need screws to
mount the unit. The specific screw types depend upon Although the unit has two mounting clips, only the
the surface to which the unit is mounted. The screw bottom clip snaps inward. The top clip is permanently
holes on the VRF Smart Gateway can accommodate locked in the outward position, and it can be used as
M3.5 and #6 screws. an additional hole for screwing the unit into place. If
not utilized for DIN rail or surface mounting, you can
To configure the VRF Smart Gateway using the remove the top and bottom clips from the unit.
gateway's Wi-Fi access point, you need a mobile device
(tablet or smartphone) or computer (laptop or desktop) DIN Rail Mounting
that supports Wi-Fi. To mount the unit on a DIN rail:

Mounting 1. Securely mount a 3 in. (7.5 cm) or longer section of


1-1/8 in. (35 mm) DIN rail in the required space.
We recommend mounting the unit either vertically
(upright and flush) or horizontally (sideways and flush). 2. On the unit, pull the bottom mounting clip
This flexibility allows the unit to be mounted in a way outward to the extended position.
that minimizes spacial constraints and maximizes
placement options for optimal wireless signal strength.
The unit should be mounted in such a way that labels
can be read if they are visible. For example, do not
mount the unit upside down, which puts the labels
upside down.

Location Considerations
Observe the following guidelines when mounting a VRF
Smart Gateway:

2 VRF Smart Gateway Installation Instructions


Figure 1: Positioning the Unit on a DIN Rail Figure 2: Sample Permanent
Mounting, Back-side Screws

To mount the unit on a flat surface (such as a wall):


3. Hang the unit on the DIN rail by the hooks at the 1. Pull the bottom mounting clip outward to the
top of the DIN rail channel (on the back of the extended position.
bracket), and position the unit snugly against the
DIN rail. 2. Mark mounting hole locations on the wall using
the dimensions shown in the following figure; or
4. Push the bottom-mounting clip inward to secure hold the bracket against the wall and mark the
the unit on the DIN rail. hole locations through the mounting clips.
Note: The position of the location holes
depends on whether the bracket is mounted
horizontally or vertically.

Wall Mounting
You can mount the unit using the holes in the DIN
rail clips. This orientation helps accommodate on-site
constraints. Screw hole locations are shown in Figure 3.
The screw types needed to mount the unit depend
upon the surface to which the unit is mounted.
The screw holes on the VRF Smart Gateway can
accommodate M3.5 and #6 screws.
For information on location considerations for
maximizing signal strength, see Mounting.

VRF Smart Gateway Installation Instructions 3


Figure 3: Mounting Holes, Flat Wiring
Mounting, DIN Rail Screws, in. (mm)
Wiring Consideration and Guidelines
Observe the following guidelines when wiring the VRF
Smart Gateway:

• Do not allow the VRF Smart Gateway to hang from a


cable connection.
• Provide some slack in the cable between the VRF
Smart Gateway and the controller or other device to
which you are connecting.

Wiring the H-Link Network


To wire the H-Link Network of the VRF Smart Gateway:

• Connect the two H-Link cable wires to the left


terminals indicated in the following figure.
• If the VRF Smart Gateway is connected at an
intermediate position of the H-Link network as
opposed to the end of the network segment, use
the right terminals shown in the following figure to
continue the H-Link network.

Figure 4: H-Link Cable Insert Position

Note: The screw holes on the VRF Smart


Gateway can accommodate M3.5 and #6
screws.

3. Drill holes in the wall based on the locations


marked in the preceding step, and insert wall
anchors for each hole (if necessary).

4. Hold the unit in place, insert the screws through To insert or remove the H-Link cable wires:
the mounting clips and into the screw holes, and • Push the orange tabs using a small, flat screwdriver
then carefully tighten all screws. or similar tool as indicated in the following figure.
Important: Do not overtighten the mounting • Then, insert or remove the wire and release the tab.
screws. Overtightening the screws may damage
the mounting clips or bracket. Figure 5: Inserting or Removing
the H-Link Cable Wires

4 VRF Smart Gateway Installation Instructions


Ethernet Port
 WARNING
The Ethernet port on the VRF Smart Gateway is an 8-
pin RJ-45 jack. The maximum allowable cable length
is 328 ft (100 m). The Ethernet port on the VRF Smart Risk of Electric Shock
Gateway connects to the BAS by using an Ethernet Disconnect or isolate all power supplies before mak-
switch or similar networking equipment. ing electrical connections. More than one disconnec-
tion or isolation may be required to completely de-en-
External Power Supply Connections ergize equipment. Contact with components carrying
hazardous voltage can cause electric shock and may
To connect the VRF Smart Gateway using the external result in severe personal injury or death.
power source:

1. Connect the 15 VDC output connector of the


power supply to the power supply port of the VRF
Smart Gateway.  WARNING

Risque de décharge électrique


 CAUTION Débrancher ou isoler toute alimentation avant de
réaliser un branchement électrique. Plusieurs iso-
lations et débranchements sont peut-être néces-
Risk of Property Damage
saires pour -couper entièrement l'alimentation de
Do not apply power to the system before checking all l'équipement. Tout contact avec des composants con-
wiring connections. Short-circuited or improperly con- ducteurs de tensions dangereuses risque d'entraîner
nected wires may result in permanent damage to the une décharge électrique et de provoquer des
equipment. blessures graves, voire mortelles.

Status Indication LEDs


 CAUTION
The behavior of the LEDs on the VRF Smart Gateway
indicate one of the following functional states:
Risque de dégâts matériels
Ne pas mettre le système sous tension avant d'avoir • power
vérifié tous les raccords de câblage. Des fils for-
• fault
mant un court-circuit ou connectés de façon incor-
recte risquent d'endommager irrémédiablement • H-Link bus communication
l'équipement.
• Ethernet communication
• Wi-Fi strength
2. Plug the power cord into a 100 VAC to 240 VAC
outlet. See the following table for a comprehensive list of VRF
Smart Gateway LED functional information.
Important: Only apply and remove power by
connecting and disconnecting the power cord
from the 100 VAC to 240 VAC outlet. Applying or
removing power by connecting or disconnecting
the 15 VDC connector can damage the unit.

VRF Smart Gateway Installation Instructions 5


VRF Smart Gateway LED Designations Table 1: LED Designations and Descriptions
and Descriptions LED Color Normal Descriptions/
Table 1: LED Designations and Descriptions Name Other Conditions
Ethernet Green On solid Off =
LED Color Normal Descriptions/
Communication
Name Other Conditions
not established
Power Green On solid Off = No power
(no On solid =
On solid = Power Communication
flashing)
supplied by established
primary voltage
Flicker = Data
Fault Red Off Off = No faults/
transmission
normal operation
Wi-Fi Yellow On solid Off = No Wi-
On solid = Missing Fi signal or no
hardware, devices currently
missing software, connected over
operating system Wi-Fi
has not yet
initialized, or reset Wi-Fi strength
is in progress. is indicated by
the number of
Slow Flicker (one LEDs that are
blink per second) = lit, with one lit
Software update in LED indicating
progress weak wireless
Medium Flicker signal strength
(two blinks per (between 1% and
second) = Startup 49%) and three lit
sequence LEDs indicating
excellent wireless
Fast Flicker (five signal strength (at
blinks per second) least 75%).
= Fault
H-Link Green On solid Off = No data LED Test Sequence at Startup
Bus transmitting
During startup, the VRF Smart Gateway automatically
Fast Flicker = initiates a self-test to verify proper operation of the
Software update of unit. Immediately after connecting supply power, the
following LED lighting sequence occurs:
second processor
1. The Power LED turns on, and stays on solid.
Slow Flicker (one
blink per second) 2. The Fault LED indicator flashes for approximately
= Discovering VRF 40 seconds and then stays on solid.
devices
3. The H-LINK LED flashes for 5 to 10 minutes
On solid = and then stays on solid. This indicates that the
Discovery discovery of VRF units is complete.
complete
4. The Wi-Fi LEDs light up in succession (scanning),
indicating that the VRF Smart Gateway is waiting
for a device to join its Wi-Fi network.

6 VRF Smart Gateway Installation Instructions


Operation Note: VRF Smart Gateway ships with a
private myvrfsg.com SSL certificate installed
The easiest way to initially configure the VRF Smart for secure communication with the VRF
Gateway is by connecting to the gateway's Wi-Fi Smart Gateway. However, web browsers
network. indicate that the certificate is not trusted.
If you wish to install your own certificate,
Figure 6: Connecting VRF refer to Adding a Private Key and Certificate to
Equipment to the Metasys System VRF Smart Gateway in the VRF Smart Gateway
Network and IT Guidance Technical Bulletin
(LIT-12012341).

4. If a security certificate warning appears, complete


the following steps to browse to the VRF Smart
Gateway:

- In a Google® Chrome™ browser, click Advanced,


then click Proceed to www.myvrfsg.com.
- In a Windows Internet Explorer® browser, click
Continue to this website (not recommended).
- In an Apple® Safari® browser, in the Cannot
Verify Server Identity window, click Continue.

5. Use the default username and password to log in.


The username is Admin, and the default password
is VRFSG- followed by the last 6 characters of the
Connecting to the VRF Smart Gateway Ethernet MAC address of the gateway (see note
Wi-Fi Network above).

Note: The default Wi-Fi SSID, passphrase, and 6. Read and accept the VRF Smart Gateway license
admin password are set to similar values. They agreement.
start with VRFSG- followed by the last 6 characters
of either the Ethernet MAC address or the 7. The first time you log in to the VRF Smart
Wireless MAC address of the gateway. Both Gateway, the Change Password and Passphrase
MAC addresses are printed on a label attached page appears. You must change the admin
to the side of the gateway. The default Wi-Fi password and Wi-Fi passphrase.
SSID, passphrase, and admin password are also
included on a label in the VRF Smart Gateway Quick a. In the New Admin Password field, enter a
Start Guide (Part No. 24-10737-156) that came with new password.
your device.
b. In the Verify New Admin Password field,
1. Use a computer or mobile device to search for reenter the password.
the gateway's Wi-Fi SSID. The SSID is VRFSG-
followed by the last 6 characters of the Wireless c. In the New Wi-Fi Passphrase field, enter a
MAC address of the gateway (see note above). new passphrase.

2. Connect to the VRF Smart Gateway Wi-Fi network d. Click Save.


using the default passphrase. The default
Important: After you change the Wi-Fi
passphrase is VRFSG- followed by the last 6
passphrase or SSID, the web server restarts
characters of the Ethernet MAC address of the and you must rejoin the VRF Smart Gateway
gateway (see note above). Wi-Fi network using the new passphrase. On
some mobile devices, you must select and
3. Open a web browser, and navigate to
forget the original VRF Smart Gateway Wi-Fi
www.myvrfsg.com. network before rejoining the network with
the new passphrase.

VRF Smart Gateway Installation Instructions 7


After you install a VRF Smart Gateway, verify that the Note: If you attempt to update from release
latest software version is installed. If not you may need 1.0, and the update fails, you may need to
to apply an update. See Updating the Software. clean out temporary files using a Cleanup.bin
file. Ask your VRF technical support team
Verifying VRF Units from the Device for this file. Follow the steps in this section
to apply the file as an update. After the
List Screen gateway restarts, log in and repeat the
After you log in to the VRF Smart Gateway UI, the update process.
Device List screen appears. This screen shows the
discovered VRF units, organized by refrigeration 9. When the upload is complete, click Install. The
system. message shown in the figure below appears and
remains visible during the update. The gateway
Updating the Software takes approximately 15 minutes to complete
the update. The gateway restarts multiple times
To determine if an update is required, identify the
during the update. If the H-LINK LED is either on
current software version of the VRF Smart Gateway
software. On the gateway UI home page, click About, solid or flashes once per second, the update is
then identify the version number listed for VRF Smart complete.
Gateway. If your gateway is at the original factory
version of 1.0.0.249, then you need to update the Figure 7: Notification that
software. an Update is in Progress
You can perform the update using a mobile device
or computer, but you must complete the full process
using the same device.

1. If you are connected to the VRF Smart Gateway


access point, disconnect, then connect to the
Internet.

2. Open a web browser, navigate to the VRFPro.com


web site and then log in. VRFPro.com is the
replacement for UPG net. If you do not have an
account for the VRFPro.com web site, contact your
Johnson Controls VRF sales team to obtain one.

3. Navigate to http://vrfpro.com/Site/
Catalog/ProModelsDetailsTabbed.asp?
id=4266&VRF=1#tabs-36 , and download the latest
software version.

4. Reconnect to the VRF Smart Gateway access point.

5. On the gateway home page, navigate to Settings


> System Utilities > Software Updates.
Note: Upgrading from 1.0 to 1.1 firmware
6. Click Choose File. changes the BACnet instance numbers of
the ODU and IDU devices. If these devices
7. Select the software file the you downloaded in are already mapped into the BAS, you must
step 3. change the device instance numbers in the
BAS. Alternatively, redo the device mapping.
8. Click Upload. If any error messages appear, retry
If this is a Metasys site, you can use the
the upload. Metasys System Configuration Tool (SCT)
to change the BACnet instance numbers.
Perform an upload from the NAE, modify the
device instance numbers one by one, then
perform a download to the NAE.

8 VRF Smart Gateway Installation Instructions


10. After your computer or smart device reconnects The customer, the Facility Manager, or other person
to the VRF Smart Gateway, in the gateway familiar with the BACnet network, must provide an
UI, select the checkbox to confirm that the open BACnet ID range to ensure that the gateway
does not assign BACnet IDs that conflict with existing
connection is established, then click Return. The devices on the same network. The number of BACnet
login screen appears. IDs that you require depends on the size of the system.
You need a range of 700 BACnet IDs for every 10 VRF
11. Log in to the gateway UI. Refrigeration Systems. The Facility Manager must
identify where a range of BACnet IDs is available, for
12. Verify that the version number on the About example, from 1000 to 1700, or 550,000 to 550,700.
screen displays the update version.
1. In the gateway UI, navigate to Settings > BACnet
Configuring the IP Settings for the Gateway > Device Settings.

BAS 2. In the Device ID field, enter the starting number


for the range of available BACnet IDs.
You must set the IP address, Subnet Mask, and Default
Gateway for the VRF Smart Gateway to communicate 3. In the BACnet Network Address and BACnet IP
with the BAS's integration device, such as the Metasys (or UDP) Port fields, enter the corresponding
NAE or the FX80.
settings that display in the BAS integration device.
1. In the gateway UI, navigate to Settings > Ethernet. An example integration device is a Metasys NAE.
The corresponding settings appear on the NAE's
2. Choose one of the following options for IP Focus View shown in the following figure. The
settings, depending on customer preferences, default setting for the network address is 1001.
and whether or not the building network supports The default setting for the BACnet UDP port is
DHCP : 47808.
a. To use DHCP, in the Auto DHCP Configure Figure 8: BACnet settings
list, select On. displayed in the NAE's Focus View

b. To use a fixed IP address, in the Auto


DHCP Configure list, select Off. A Static
IP address, Subnet Mask, and Default
Gateway must be decided on and entered
into the appropriate fields.

3. Optional: For best results, add the gateway and


the NAE on the same IP subnet. If the gateway
and NAE are not on the same IP subnet, you
may need to use a new release 1.1 feature called
BBMD.

4. Leave the DNS settings blank.

5. Click Save. You are prompted to restart the


gateway now or postpone. If you are configuring
the BACnet settings, you can postpone the
restart until after they are configured. If you have
configured both the IP settings and the BACnet
settings, restart now.

Configuring the BACnet Settings for


the BAS
You must set the BACnet device settings for the
VRF Smart Gateway to communicate with the BAS
integration device over BACnet IP. The gateway
assigns each VRF IDU and ODU a unique BACnet ID.

VRF Smart Gateway Installation Instructions 9


4. In the BACnet IP Virtual Network Address Table 2: Reset Button Operation and Descriptions
field, enter a unique value for each VRF Smart
Gateway on the BACnet network. 65001 is the Reset Reset Operation
default. The only time this is a concern is when Function
you have multiple VRF Smart Gateways on the Reset Wi-Fi 1. Press and hold the reset button
same network. Each VRF Smart Gateway requires (SSID and for 2 seconds.
a different number in this field. For example, enter passphrase)
2. When the Fault LED displays a
65001 in this field in the first gateway, and enter and
slow flicker behavior, release the
65002 in this field in the second gateway. Ethernet
reset button and immediately press
Settings
5. Click Save. You are prompted to restart the and release it once more.
gateway now or postpone. If you have configured Reset 1. Press and hold the reset button
both the IP settings and the BACnet settings, all unit for 6 seconds. After 2 seconds the
restart now. settings Fault LED displays a slow flicker,
to Factory but continue to hold the reset
Reset Button Operation and Defaults button.
Descriptions (resets
2. When the Fault LED displays a fast
all unit
flicker behavior, release the reset
You can perform two levels of factory reset on the VRF settings,
Smart Gateway, as shown in Table 2. button and immediately press and
including
release it once more.
Important: To use a unit that is reset to factory user
defaults, you must have the default login profiles)
information supplied in the Quick Start Guide
that shipped with the unit. The Reset to Factory
Note:
Defaults function does not change the version
of the application. If you update the software, • For information on LED designations and
the VRF Smart Gateway remains at the updated flicker behavior, see Table 1.
version, rather than resetting to the version that it
was running when it left the factory. • If you press the reset button, anyone
connected to the VRF Smart Gateway is
The reset button is on the side of the device, and it is disconnected.
embedded into the VRF Smart Gateway housing so
that it cannot be activated by accident. To reach the • If you press the reset button for more than 9
reset button, use a paper clip, pin, or similar tool. seconds, the reset operation is cancelled.
• If you do not press the reset button a second
Figure 9: Using the Reset Button time within 5 seconds of releasing it, the reset
operation is cancelled.
• If a fault condition already exists, the reset
button is disabled.

Repair Information
If the VRF Smart Gateway fails to operate within its
specifications, replace it. You can apply software
updates to the VRF Smart Gateway to enable feature
enhancements. For a replacement unit, software
updates, or accessories, contact the nearest Johnson
Controls representative.
Do not open the VRF Smart Gateway housing. The VRF
Smart Gateway has no user-serviceable parts inside.
The VRF Smart Gateway does not require periodic field
maintenance.

10 VRF Smart Gateway Installation Instructions


Troubleshooting

Table 3: Launch Issues Troubleshooting Information

Problem Resolution
The H-LINK LED continues The VR Smart Gateway cannot find VRF units. Check the H-LINK wiring
flashing for longer than 15 connections and termination.
minutes.
Confirm VRF operation is stable and responsive, and use the Hitachi Service
Checker to verify the H-LINK network is healthy.
The H-LINK LED does not start There may be a communication error on the H-LINK network, or the VRF Smart
flashing after the VRF Smart Gateway may be defective.
Gateway is powered on.
Confirm VRF operation is stable and responsive, and use the Hitachi Service
Checker to verify the H-LINK network is healthy.

If you confirm that the VRF Smart Gateway is defective, see Repair Information.
You are not directed to the VRF Reason
Smart Gateway login page when
Device behavior can vary based on the device and Internet browser in use. For
you launch a web browser.
instance, some devices cache browser information and do not automatically
redirect users to the VRF Smart Gateway login page when the browser is
launched.

Resolution

Make sure that your device is connected to the VRF Smart Gateway's Wi-Fi
network.

Direct your browser to www.myvrfsg.com.


Every time you install the SSL Resolution
certificate on your device, it asks
Check your web browser settings and verify that cookies are enabled.
you to re-install it.
When you install the SSL key When an SSL key or certificate is corrupted, the SSL page detects it and alerts
or certificate, you receive the you to the corrupted key or certificate.
message Error Saving SSL
However, if the corruption is minor, for example, an extra space was copied
Settings.
while installing the certificate or a character was missed, the UI does not detect
the problem and allows the corrupted key or certificate to be saved. The server
detects the error and returns the Error Saving SSL Settings message. While
this correctly prevents the bad key or certificate from being used, it does not
inform you as to the source of the problem.

In this case, reinstall the SSL key or certificate as described in the VRF Smart
Gateway Network and IT Guidance Technical Bulletin (LIT-12012341).
The VRF Smart Gateway cannot Electromagnetic interference can cause communications issues. Connecting
see all VRF units at the same over 100 IDUs or ODUs on the same network segment can increase the chance
time, or behavior is unreliable. for communication errors, and create performance and controls issues.
The stability and reliability of communications across the H-LINK network is
increased if you limit each H-LINK segment to under 100 devices.

There may be communication issues when any Hitachi Central Controller is


on the network simultaneously with the VRF Smart Gateway. At this time, it
is recommended to only have one or the other connected to avoid potential
communication errors.

VRF Smart Gateway Installation Instructions 11


Table 3: Launch Issues Troubleshooting Information

Problem Resolution
The Device List screen displays Check the H-LINK LED on the VRF Smart Gateway, and then consult other
the message: No Devices entries in this troubleshooting section.
Discovered.

Refer to the VRF Smart Gateway User's Guide (LIT-12012385) for information on Ethernet settings and SSL settings.

Technical Specifications

Table 4: VRF Smart Gateway

Product Code SI-VRFCBN02-0Sx: VRF Smart Gateway (Last digit [x] represents non-US country
requirements. )
Power Consumption 12 VDC to 15 VDC at 5.2 W maximum
Ambient Operating: 0°C to 50°C (32°F to 122°F)
Temperature
Operating Survival: -30°C to 60°C (-22°F to 140°F)
Conditions
Non-Operating: -40°C to 70°C (-40°F to 158°F)
Ambient Humidity Storage: 5% to 95% RH 30°C (86°F) maximum dew point conditions
Conditions
Operating: 5% to 95% RH, 30°C (86°F) maximum dew point conditions
Transmission Power Wireless Local Area Network (WLAN) Transmission Power:
(Typical)
+14.5 dBm, 54 Mbps

+12.5 dBm, 65 Mbps


WLAN Receiver -76 dBm, 10% packet error rate (PER ), 54 Mbps
Sensitivity (Typical)
-73 dBm, 10% PER, 65 Mbps
Transmission Wireless Communication:
Speeds
2.4 GHz ISM bands, 802.11 b/g/n, 11/22/54 Mbps

Channel 6 preconfigured, supported CH 1 to 11 for United States and Canada, and CH 1 to


12 for all other countries

Serial Communication (H-Link Bus):

9600 bps

Ethernet Communication:

10 Mbps, 100 Mbps

12 VRF Smart Gateway Installation Instructions


Table 4: VRF Smart Gateway

Transmission Range Ethernet Communication:


(Typical)
100 m (328 ft) cable length

H-Link Bus Communication:

1,000 m (3,280 ft) cable length

Wireless Communication:

30 m (98 ft) line-of-sight indoors

91 m (299 ft) line-of-sight outdoors

Channel 6 preconfigured, supported CH 1 to 11 for United States and Canada, and CH 1 to


12 for all other countries

WLAN Range Performance:

0 ft to 50 ft = Excellent

50 ft to 100 ft = Good

100 ft to 300 ft = Weakest, approaching out of range


Wireless Security WPA2-PSK TKIP (Wi-Fi Protected Access Pre-Shared Key mode Temporal Key Integrity
Protocol)

WPA2-EAP-PEAP

WPA2-EAP-TLS
Network and Serial One H-Link port (4-pin port)
Interfaces
Dimensions 145.4 mm x 85.4 mm x 40.1 mm (5.72 in. x 3.36 in. x 1.58 in. when used vertically)

(H x W x D)
Weight 0.21 kg (0.46 lb)

Note: Weights do not include an external power supply.


Web Browser Computer:
Requirements for Windows® Internet Explorer® 10 and Windows Internet Explorer 11, Apple®Safari® 6.1
Computers and and later, and Google®Chrome™
Handheld Devices
Handheld Device:
The handheld device must be running either Internet Explorer Mobile for Windows Mobile
version 5 or version 6 operating system (OS); Apple®iPhone® and iPod touch® iOS version
7.0 or greater; Android™ 4.0.3, 4.0.4, and 4.1+, or Google Chrome. Other web browsers
may display the UI, but the functionality is not guaranteed.

Purpose of Control Operating control


Construction of Electronic Independently Mounted Control
Control
TYPE 1 or TYPE 2 TYPE 1
Action
External Pollution Pollution Degree 2
Situation

VRF Smart Gateway Installation Instructions 13


Table 4: VRF Smart Gateway

Rated Impulse 330 V


Voltage
Ball Pressure 100ºC (212ºF)
Temperature
Compliance
United States UL Listed File E107041, ANSI/UL 60730-1, UL Standard for Automatic
Electrical Controls for Household and Similar Use.

Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
Transmitters

Transmitter FCC Identification: OEJ-MAPWIFI

FCC Compliant to CFR 47, Part 15, Subpart B, Class A


Canada: cUL Listed File E107041, CAN/CSA-E60730-1, Canadian Standard for Automatic
Electrical Controls for Household and Similar Use

Industry Canada IC: 279A-MAPWIFI

IC: RSS-210, ICES-003


Europe: CE Mark – Johnson Controls declares that this product is in compliance with
the essential requirements and other relevant provisions of the RED Directive, the EMC
Directive, and the Low Voltage Directive (LVD).

CE Emission: EN61000-6-3; Generic standards for residential, commercial, and light-


industrial environments. ETSI EN 301 489-1, ETSI EN301 489-3 (Class 2), IEC 60730-1/ EN
60730-1
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant.
Oman:

UAE:

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages
resulting from misapplication or misuse of its products.

14 VRF Smart Gateway Installation Instructions


BACnet Points
The following table lists the available BACnet points for the VRF indoor units (IDUs) as exposed by the VRF Smart
Gateway.

Table 5: BACnet Points for VRF Indoor Units


BACnet Object Name Object Description Object Type Contents of Information
Instance
Number
4 UNIT-CAP Indoor Unit Capacity Code AI Value 0 to 255
5 UNITEN-MODE Unit Enable Mode BO Setting Shutdown Enable – – –
6 SYSTEM-MODE Command System Mode MO Setting Cool Dry Fan Heat Auto
7 HtClg-REQ Heat/Cool Required BI Status False True – – –
8 SF-SPEED-C Commanded Supply Fan MO Setting Low Medium High Auto –
Speed
9 EXPV-% Expansion Valve Position AI Value 0.0% to 100.0%
10 LIQ-PIPE-T Liquid Pipe Temperature AI Value -50°C to 99°C (-58°F to 210°F)
11 GAS-PIPE-T Gas Pipe Temperature AI Value -50°C to 99°C (-58°F to 210°F)
12 RA-T Return Air Temperature AI Value -50°C to 99°C (-58°F to 210°F)
13 DA-T Discharge Air Temperature AI Value -50°C to 99°C (-58°F to 210°F)
14 DIFF-T Coil Differential AI Value -127°C to 127°C (-196°F to 260°F)
Temperature
15 ZN-SP Zone Temperature AO Setting 17°C to 30°C (62°F to 86°F)
Setpoint
16 RZN-T
1
Remote Zone Temperature AI Value -50°C to 99°C (-58°F to 210°F)

17 COMP to REQ Requested Compressor AI Value 0 Hz to 255 Hz


Speed
18 UNIT-STOP-CODE Unit Stop Code AI Value 0 to 255
For information about individual code numbers, refer
to the VRF equipment service manual.
19 ALARM-CODE Alarm Code AI Value 0 to 255
For information about individual code numbers, refer
to the VRF equipment service manual.
20 RMT-OPT Optional Room BI Status False True – – –
Thermostat
21 DEFROST-S Defrost Status BI Status False True – – –
22 REM-CON Remote Control Connected BI Status False True – – –
23 SF-S Supply Fan Status BI Status Off On – – –
24 ALARM-S Unit Alarm Status BI Status Normal Alarm – – –
25 SYSTEM-S Actual System Mode MI Status Cool Dry Fan Heat –
26 SF-SPD Actual Supply Fan Speed MI Status Low Medium High – –
27 ZN-T
2
Zone Temperature AI Value -50°C to 99°C (-58°F to 210°F)

28 FILT-S Filter Status BI Status Clean Dirty – – –


29 FILT-S-RESET Filter Status Reset BO Setting Clean Dirty – – –
30 UNIT-LO Unit Lockout BO Setting Unlock Lock – – –
31 FANCMD-LO Fan Command Lockout BO Setting Unlock Lock – – –
32 SYSMODE-LO System Mode Lockout BO Setting Unlock Lock – – –
33 ZNSP-LO Zone Temperature BO Setting Unlock Lock – – –
Setpoint Lockout
34 FANSPD-LO Fan Speed Lockout BO Setting Unlock Lock – – –
35 LOUVER-LO Louver Position Lockout BO Setting Unlock Lock – – –

1 RZN-T is the temperature reading from the Remote Controller, if one is connected to the IDU. If no Remote Controller is connected
to the IDU, this value is marked Unreliable and has a reading such as -65 degF. Therefore, if no Remote Controller is connected,
you can delete this point from the BAS or not map it in.

VRF Smart Gateway Installation Instructions 15


2 ZN-T is the temperature reading from the inlet temperature of the IDU. It is the same reading as RA-T (return air temperature). This
temperature reading is always available under normal operating conditions.

The following table lists the IDU multi-state values for SYSTEM-MODE and SYSTEM-S.

Table 6: IDU System Mode

State Value State String


1 Cool
2 Dry
3 Fan
4 Heat
5 Auto

The following table lists the IDU multi-state values for SF-SPEED-C and SF-SPD.

Table 7: IDU Fan Speed

State Value State String


1 Low
2 Med
3 High
4 Auto

The following table lists the available BACnet points for the VRF outdoor units (ODUs) as exposed by the VRF Smart
Gateway.

Table 8: BACnet Points for VRF Outdoor Units


BACnet Object Name Object Description Object Type Contents of Information
Instance
Number
3 ALARM-CODE Alarm Code AI Value 0 to 255
For information about individual code
numbers, refer to the VRF equipment service
manual.
6 SYSTEM-MODE System Mode MI Status Heat Cool Auto
7 SYSTEM-S System Status MI Status Several Values (See the Following Tables for
Multi-State Information)
8 HX-STATE Heat Exchanger State MI Status Several Values (See the Following Tables for
Multi-State Information)
9 INV-STATE Inverter State MI Status Several Values (See the Following Tables for
Multi-State Information)
10 FAN-STATE Fan Controller State MI Status Several Values (See the Following Tables for
Multi-State Information)
11 INV-HRS Inverter Compressor 1 AI Value 0 Hours to 655,350 Hours
Runtime

16 VRF Smart Gateway Installation Instructions


Table 8: BACnet Points for VRF Outdoor Units
BACnet Object Name Object Description Object Type Contents of Information
Instance
Number
12 COMP-HRS Compressor 2 Runtime AI Value 0 Hours to 655,350 Hours
13 INV-FREQ Inverter Compressor AI Value 0 Hz to 255 Hz
Frequency
14 TOTAL-FREQ Total Frequency AI Value 0 Hz to 65,535 Hz
15 FAN-% Outdoor Fan Output AI Value 0% to 100%
16 EXPV-% Expansion Valve Position AI Value 0% to 100%
17 BYPEXPV-% Bypass Expansion Valve AI Value 0% to 100%
Position
18 DISCH-P Discharge Pressure AI Value 0 psi to 3,698.5 psi
19 SUCT-P Suction Pressure AI Value 0 psi to 369.8 psi
20 OA-T Outside Air Temperature AI Value -50°C to 99°C (-58°F to 210°F)
21 INV2ND-A Inverter Compressor AI Value 0 A to 127.0 A
Secondary Current
22 INVPRI-A Inverter Compressor Primary AI Value 0 A to 127.0 A
Current
23 COMP2-A Compressor 2 Current AI Value 0 A to 127.0 A
24 INVTOP-T Inverter Compressor Top AI Value 0°C to 99°C (32°F to 210°F)
Temperature
25 COMP2TOP-T Compressor 2 Top AI Value 0°C to 99°C (32°F to 210°F)
Temperature
26 PROT-CODE Protection Code MI Status Several Values (See the Following Tables for
Multi-State Information)
27 DEFROST-S Defrost Status BI Status Off On –
28 EMERGRUN-S Emergency Run Status BI Status Off On –
29 INV-S Inverter Status BI Status Stop Run –
30 FAN-S Fan Status BI Status Stop Run –

The following table lists the ODU multi-state values for SYSTEM-MODE.

Table 9: ODU System Mode

State Value State String


1 Heat
2 Cool
3 Auto

The following table lists the ODU multi-state values for SYSTEM-S.

Table 10: ODU System Status

State Value State String


1 Thermo off
2 Pump down
3 SW on start
4 Thermo on start

VRF Smart Gateway Installation Instructions 17


Table 10: ODU System Status

State Value State String


5 After defrost
6 Start control 1
7 Start control 2
8 Normal
9 Oil return
10 Defrost ready 1
11 Defrost ready 2
12 Differential pressure control
13 Defrost

The following table lists the ODU multi-state values for HX-STATE.

Table 11: ODU Heat Exchanger Status

State Value State String


1 Evaporator Mode Low Pressure
2 Condenser Mode High Pressure
3 Evaporator Mode
4 Condenser Mode

The following table lists the ODU multi-state values for INV-STATE and FAN-STATE.

Table 12: ODU Inverter and Fan Status

State Value State String


1 Normal stop
2 Fault
3 Over current
4 Fin temp
5 Electronic thermal
6 Undervoltage
7 Overvoltage
8 Communication error
9 Current sensor abnormality
10 Instantaneous power failure
12 MPU reset
13 Earth fault voltage
14 Phase loss
16 Driving prohibited area
17 Fan controller retry

18 VRF Smart Gateway Installation Instructions


Table 12: ODU Inverter and Fan Status

State Value State String


18 Control abnormality
21 Loss of synchronism
24 Normal acceleration
25 Normal deceleration
26 Constant speed
27 Overload after the acceleration
28 Overload after the deceleration
29 Overload after constant speed
30 Power supply unbalance
31 Power supply phase loss

The following table lists the ODU multi-state values for PROT-CODE.

Table 13: ODU Protection Code

State Value State String


1 Pressure ratio
2 Pd rise prevention
3 Current protection
4 INV module temp rise prevent
5 Compressor top overheat prevent
6 Ps drop or rise prevention
9 Pd drop prevention
10 Current demand
13 Ps rise prevention

Points of single contact Product warranty


APAC Europe NA/SA This product is covered by a limited warranty, details of which
JOHNSON CONTROLS JOHNSON JOHNSON can be found at www.johnsoncontrols.com/buildingswarranty.
C/O CONTROLS PRODUCT CONTROLS CONTROLS
MANAGEMENT WESTENDHOF 3 507 E MICHIGAN ST
NO. 32 CHANGJIJANG RD 45143 ESSEN MILWAUKEE WI
NEW DISTRICT GERMANY 53202
WUXI JIANGSU PROVINCE USA
214028
CHINA

Software terms
Use of the software that is in (or constitutes) this product,
or access to the cloud, or hosted services applicable to this
product, if any, is subject to applicable terms set forth at
www.johnsoncontrols.com/techterms. Your use of this product
constitutes an agreement to such terms.

VRF Smart Gateway Installation Instructions 19


© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and
are subject to change without notice.

www.johnsoncontrols.com

You might also like