Professional Documents
Culture Documents
Estrategia de Compensación de Corriente Armónica Flexible Aplicada en Inversores Fotovoltaicos Monofásicos y Trifásicos.
Estrategia de Compensación de Corriente Armónica Flexible Aplicada en Inversores Fotovoltaicos Monofásicos y Trifásicos.
A R T I C LE I N FO A B S T R A C T
Keywords: Non-linear loads connected to power system have increased considerably in the recent decades. Traditional
Ancillary services generation based on hydro and thermal power plants cannot mitigate harmonic currents. However, due to the
Harmonic current detection method increased connection of photovoltaic into the power system, its power electronic converter can be used to
Harmonic current compensation perform ancillary services such as harmonic current compensation. This work presents a dynamic method based
Single and three-phase PV inverters
on the Second Order Generalized Integrator coupled with a phase locked loop structure to detect and compensate
the most predominant harmonic current components from the power system. It is also presented an extension to
detect multiple harmonics, according to the amplitude. Technical issues related with the harmonic current
compensation strategy, and its implementation for both single and three-phase PV inverters are explored to
demonstrate the functionality and efficiency of the method. The results show the harmonic current compensa-
tion being compensated by a PV inverter. Finally, a losses analysis were performed in the LCL filter. The
magnetic and damping resistor losses are more impacted due to high harmonic current compensation.
1. Introduction be used to improve the power quality [8,9]. Ancillary services, such as
reactive power compensation [10,11], reactive injection during faults
The classic infrastructure of electrical power systems consists on [12], voltage and frequency regulation [12] and harmonic current
large scale centralized generation, distributed over long transmission compensation [6,10] are some of the contributions that PV inverters
lines [1]. Nowadays, distributed generation (DG) systems have changed can aggregate to improve the power system stability.
this traditional conception. DG systems are receiving more attention Current total harmonic distortion (THD) level is an important index
whereas environmental concerns and energy demand grow over the in power systems harmonic analysis. Some standards define that the
world [2]. Furthermore, DG systems may be installed inside consumer current THD level must be below 5% [13,14]. Some methods to reduce
units, which reduces losses over distribution and transmission systems the grid harmonic current distortions can be found in literature. The
[3]. Such benefits brought huge development in renewable energy most conventional ones use passive [15] and active [16,17] filters, or
sources in recent years, especially photovoltaic (PV) energy, whose cost associations of both to decrease the THD level. However, once the PV
was reduced in 75% in less than 10 years [4]. plant is already installed, the use of the inverter in multifunctional
Compared with hydro and thermal power plants, PV systems have operation is an economic alternative more viable than passive or active
electronic converters that inject high order harmonic current compo- filters [18].
nents into the power system. [3,5]. These high order harmonic com- The detection method is an important issue to compensate harmonic
ponent can be minimized using passive filters. On the order hand, the current components. Some of the methods commonly found in litera-
growing presence of nonlinear loads, generally, injecting low order ture realize the harmonic current detection through second order gen-
harmonic current components, can reduce the distribution system eralized integrators (SOGI) [1], instantaneous power theory [11,17],
power quality [6]. conservative power theory [3,7,18], Fourier transform [19] and de-
Since solar irradiance varies during the day, inverters usually work layed signal cancellation [20]. Nevertheless, most of these strategies
below their nominal operation point [7], as illustrated in Fig. 1. Thus, detect the whole harmonic content from the load, increasing the con-
whenever the inverter current does not exceed its nominal value, it can troller tuning complexity.
⁎
Corresponding author.
E-mail addresses: heverton.pereira@ufv.br (H.A. Pereira), lucas.xavier@ufv.br (L.S. Xavier), afcupertino@ieee.org (A.F. Cupertino).
https://doi.org/10.1016/j.ijepes.2018.07.017
Received 26 October 2017; Received in revised form 19 June 2018; Accepted 10 July 2018
0142-0615/ © 2018 Elsevier Ltd. All rights reserved.
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
This paper is structured as follows: Section 2 describes the main 2.2. Control strategies
parts of the PV system, including the control strategies used in both
single-phase and three-phase systems. Section 3 describes the harmonic The PV inverter control strategies have two forms, the dc/dc stage,
detection topology and its extension for multiple harmonic components with boost converter, and the dc/ac stage, with the inverter.
detection. Section 4 presents the case studies for both single and three-
phase systems. In Section 5, the proposed harmonic detection method is 2.2.1. Dc/dc stage
verified through simulation results. Finally, the conclusions are stated The dc/dc stage converter is commonly used for booster the input
in Section 6. voltage level of the inverter, ensuring the acceptable voltage level for
startup and extending its operation range during low irradiance con-
2. Grid connected PV system ditions. In single-phase system, the use of dc/dc is even more important
due to power oscillation in the 2nd harmonic frequency. This power
In this work, two PV systems are analyzed: a single-phase and a oscillation results in dc-link voltage fluctuation and reduces the MPPT
three-phase. Fig. 2 presents a general connection scheme between the efficiency, when the PV modules are connected directly to the dc-link.
PV plant and the power system. For this reason, it is advisable to perform MPPT algorithm in dc/dc
stage control for single-phase applications. The boost converter is
2.1. Photovoltaic panel, maximum power point tracking and LCL filter widely used for these cited purposes [31].
The connection of the PV array to the boost converter is shown in
Based on the photovoltaic effect, the PV panel transforms sunlight Fig. 3. The PV array model is linearized around the nominal maximum
359
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
360
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
Fig. 8. The algorithm flowchart to select the two highest harmonic components for compensation in single-phase system.
361
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
Fig. 9. Composition of the non-linear load in single-phase simulation: (a) load profile before t = 4 s . (b) load profile after t = 4 s .
Fig. 10. Composition of the non-linear load in three-phase simulation: (a) load profile before t = 4 s . (b) load profile after t = 4 s .
Table 2 Table 4
Physical parameters of the LCL filter inductors. Single Phase Simulation Parameters.
Single-Phase System Value System Parameters Value
kSOGI = 0.8
SOGI-PLL Parameters of the 2nd, 3rd, 4th Stages ξ = 0.707
subtracted from the input current.
ωn = 60π
The next stage of the harmonic component detection extracts the
amplitude, frequency and phase angle information from the pre-
angle θ1 information of the fundamental component. A low-pass filters dominant harmonic component presented in the load current. The
(LPF) in the amplitude and frequency detection are important to avoid current signal iL ̃ (t ) is reconstructed and sent to the control loop to
the effect of the harmonic components that the SOGI-PLL bandwidth perform the harmonic compensation of this predominant load harmonic
cannot suppress. This signal is reconstructed, represented by i1 (t ) , and current.
362
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
Fig. 11. (a) PV panels voltage control. (b) Inverter dc-link voltage control. (c) Boost current control.
363
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
Fig. 12. (a) Load fundamental component detection. (b) Load highest amplitude harmonic component detection. (c) Load 2nd highest amplitude harmonic com-
ponent detection. (d) Load 3rd highest amplitude component detection.
Fig. 13. Inverter current spectra (a) without HC compensation, t < 1 s , (b) compensating the first load profile, 2 < t < 4 s (c) compensating the second load profile,
t > 4 s.
used: one was adjusted to the fundamental frequency of the grid, and first SOGI-PLL structure, with 0.3 s between the initialization of each,
the other two were tuned on the frequency of the two harmonic com- and the harmonic compensation (HC) at 2 s. This procedure aims to
ponents with higher amplitude. allow initial detection stabilization before the compensation starts. The
two harmonic signals with higher amplitude are compensated in the
5. Simulation and results current control loop. The third one is used only in the detector feed-
back, thus, improving precision in the amplitude detection.
5.1. Single-phase system Fig. 12 shows the detected current amplitudes and frequencies. The
detected current compensation can be observed in Figs. 13 and 14.
Fig. 11(a) shows the voltage control of the PV panels. This voltage Fig. 13 shows the inverter harmonic current components and Fig. 14
follows the maximum power point voltage detected by the MPPT al- shows the grid harmonic current components. There is no compensa-
gorithm. Fig. 11(b) shows the inverter dc-link voltage control. This tion before t = 1 s , and the grid current presents all the harmonic
voltage is controlled, with some oscillations observed only in the be- components from the load. The grid current THD at this time is 75%, as
ginning of the harmonic compensation and at the change of the non- shown in Table 6. Compensation occurs at t = 2 s . The 3rd and 5th
linear load. Fig. 11(c) shows the boost inductor current control. harmonics are compensated and these components appear in the in-
The harmonic current detection starts at 1.5 s of simulation in the verter current. The grid current THD at this time is 17%. In t = 4 s , the
364
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
Fig. 14. Grid current spectra (a) without HC compensation t < 1 s , (b) compensating the first load profile 2 < t < 4 s and (c) compensating the second load profile
t > 4 s.
Table 6 impedance changes with different harmonic components, and the losses
Grid current THD in the single-phase case study. in the capacitor tends to grow as the harmonic order increases.
Simulation Time (seconds) Grid Current THD To illustrate this fact, it is made a study to verify the filter core and
cooper losses for four harmonic current components and the funda-
t<2 75% mental component (1st component), considering five different ampli-
2⩽t<4 17% tude values. The system compensates the 5th, 7th, 11th and 13th har-
t⩾4 19%
monic current components, each one with amplitude varying of 0.2 pu,
0.4 pu, 0.6 pu, 0.8 pu and 1 pu. The results obtained are shown in
non-linear load composition changes and the 5th and 7th harmonics are Fig. 15. This figure shows the LCL filter losses when the PV system
compensated. After 4 s, the grid current THD is 19%. injects only the fundamental current component (active power) and
Once harmonic current compensation is an ancillary service exe- only compensating one harmonic current component. It is important to
cuted by the inverter, an important issue to be verified is the losses in note that only one harmonic order is injected at a time.
the LCL filter, including core losses and copper losses. Once, the in- Fig. 15(a) shows the total filter copper losses. It is possible to note
verter filter is composed of inductors and capacitors, the filter that, for each harmonic order, the power losses increase with the RMS
Fig. 15. Losses in the single-phase LCL filter during harmonic compensation (a) Total copper losses (b) Total core losses (c) Damping resistor losses (e) Total LCL filter
losses.
365
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
Fig. 17. Amplitude and frequency detection dynamics of the load current (a) Load current fundamental component detection. (b) Harmonic detection of the 1st stage.
(b) Harmonic detection of the 2nd stage. (c) Harmonic detection of the 3rd stage. (d) Harmonic detection of the 4th stage.
366
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
Fig. 18. Inverter current spectra (a) without harmonic current compensation t < 2 s , (b) compensating the first load profile 2 < t < 4 s and (c) compensating the
second load profile t > 4 s .
Fig. 19. Grid current spectra (a) without harmonic current compensation t < 2 s , (b) compensating the first load profile 2 < t < 4 s and (c) compensating the second
load profile t > 4 s .
367
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
Fig. 20. Losses in the three-phase LCL filter during harmonic compensation (a) Total copper losses (b) Total core losses (c) Damping resistor losses (e) Total LCL filter
losses.
method presented good results for both single and three-phase con- 2015–2019, Technical Report. SolarPower Europe; 2014.
verters. [5] Y. Yang, F. Blaabjerg, H. Wang, Low voltage ride-through of single-phase trans-
formerless photovoltaic inverters, in: IEEE Energy Conversion Congress and
Losses analysis showed that during harmonic current compensation, Exposition, 2013, pp. 4762–4769.
the LCL total losses is directly related with the harmonic order. Thus, [6] He J, Li YW, Blaabjerg F, Wang X. Active harmonic filtering using current-con-
the compensation of high order harmonic current components implies trolled, grid-connected dg units with closed-loop power control. IEEE Trans. Power
Electron. 2014;29:642–53.
in higher losses. It is highlighted that the magnetic losses can increase [7] L.S. Xavier, A.F. Cupertino, H.A. Pereira, Adaptive saturation scheme for a multi-
almost four and five times during high order harmonic current com- functional single-phase photovoltaic inverter, in: Int. Conf. on Ind. Appl., 2014,
pensation for single and three-phase systems, respectively. Moreover, pp. 1–8.
[8] J.P. Bonaldo, J. Antenor Pomilio, Multi-functional use of single-phase power con-
the losses in the damping resistor is more than 20% of the total losses,
verters, in: IEEE PES Conf. on Innovative Smart Grid Technologies Latin America,
thus, it is recommended other control strategies based on active 2013, pp. 1–6.
damping techniques. [9] J.P. Bonaldo, H.K.M. Paredes, J.A. Pomilio, Flexible operation of grid-tied single-
phase power converter, in: Brazilian Power Electronics Conf., 2013, pp. 987–992.
Therefore, the trade-off identified is the use of a PV inverter to re-
[10] H.A. Pereira, L.S. Xavier, A.F. Cupertino, V.F. Mendes, Single-phase multifunctional
duce the grid current THD, increasing the inverter losses. Since har- inverter with dynamic saturation scheme for partial compensation of reactive
monic current compensation is an ancillary service, it is recommended power and harmonics keywords, European Conf. on Power Electronics and
that the distribution network should to incentive the use of inverters Applications (2015) 1–10.
[11] Akagi H, Kanazawa Y, Nabae A. Instantaneous reactive power compensators com-
with harmonic current compensation capacity, with focus to improve prising switching devices without energy storage components. IEEE Trans. Ind.
the overall power system. Appl. 1984;IA-20:625–30.
[12] Yang Y. Advanced Control Strategies to Enable a More Wide-Scale Adoption of
Single-Phase Photovoltaic Systems Ph.D. thesis Aalborg University; 2014.
Acknowledgments [13] IEEE Standard for Interconnecting Distributed Resources with Electric Power
Systems, IEEE Std 1547–2003 (2003) 1–28.
This work has been supported by the Brazilian agencies CNPq [14] Photovoltaic (PV) systems - Characteristics of the utility interface, CEI/IEC Std
61727–2004 (2004) 1–23.
(431478/2016-3), FAPEMIG (APQ-03555-16) and CAPES. [15] Fujita H, Akagi H. A practical approach to harmonic compensation in power sys-
tems-series connection of passive and active filters. IEEE Trans. Ind. Appl.
References 1991;27:1020–5.
[16] Y. Haiwen, G. Xin, M. Hanguang, Research on harmonic compensation effects for a
kind of isolated power system, in: Int. Conf. on Electronic Measurement
[1] Rodriguez P, Luna A, Candela I, Mujal R, Teodorescu R, Blaabjerg F. Multiresonant Instruments, 2009, pp. 4–686.
frequency-locked loop for grid synchronization of power converters under distorted [17] Watanabe EH, Aredes M. Active and reactive instantaneous power theory and ap-
grid conditions. IEEE Trans. Ind. Electron. 2011;58:127–38. plications – active filters and facts. Brazilian Congress of Automatic 1998:81–122.
[2] Conti JJ. Annual Energy Outlook 2015 with projections to 2040, Technical Report. [18] Bonaldo JP, Paredes HKM, Pomilio JA. Control of single-phase power converters
U.S. Energy Information Administration; 2015. connected to low voltage distorted power systems with variable compensation
[3] D.I. Brandão, F.P. Marafão, H.K.M. Paredes, A. Costabeber, Inverter control strategy objectives. IEEE Trans. Power Electron. 2016;31:2039–52.
for DG systems based on the Conservative power theory, in: IEEE Energy Conversion [19] McGrath BP, Holmes DG, Galloway JJH. Power converter line synchronization
Congress and Exposition, 2013, pp. 3283–3290. using a discrete fourier transform (dft) based on a variable sample rate. IEEE Trans.
[4] Rekinger M, Thies F, Masson G, Orlandi S. Global Market Outlook: For Solar Power/ Power Electron. 2005;20:877–84.
368
H.A. Pereira et al. Electrical Power and Energy Systems 104 (2019) 358–369
[20] Wang YF, Li YW. Three-phase cascaded delayed signal cancellation pll for fast se- [27] Kaura V, Blasko V. Operation of a phase locked loop system under distorted utility
lective harmonic detection. IEEE Trans. Ind. Electron. 2013;60:1452–63. conditions. IEEE Trans. Ind. Appl. 1997;33:58–63.
[21] W. Yanfeng, S. Rongyan, G. Xinhua, L. Yan, Y. Hua, The comparative analysis of pi [28] A.P.L. Cota, R.C. Abrantes, P.C. Cortizo, R.A.S. Santana, W.C. Padro, Comparison of
controller with pr controller for the single-phase 4-quadrant rectifier, in: Conf. and three 3-phase converter topologies for ups applications, in: Brazilian Power
Expo Transp. Electrifi. Asia-Pacific, 2014, pp. 1–5. Electronics Conf., 2015, pp. 1–6.
[22] L.S. Xavier, A.F. Cupertino, V.F. Mendes, H.A. Pereira, A novel adaptive current [29] Powder Cores, Magnetics International Pittsburg P A Catalog, 2006.
harmonic control strategy applied in multifunctional single-phase solar inverters, [30] J. Mhlethaler, J.W. Kolar, A. Ecklebe, Loss modeling of inductive components
in: Braz. Power Elec. Conf., 2015, pp. 1–6. employed in power electronic systems, in: Int. Conf. on Power Electronics, 2011, pp.
[23] M. Ciobotaru, R. Teodorescu, F. Blaabjerg, A new single-phase pll structure based 945–952.
on second order generalized integrator, in: IEEE Power Electronics Specialists Conf., [31] Blaabjerg F, Teodorescu R, Liserre M, Timbus AV. Overview of control and grid
2006, pp. 1–6. synchronization for distributed power generation systems. IEEE Trans. Ind.
[24] Villalva MG, Gazoli JR, Filho ER. Comprehensive approach to modeling and si- Electron. 2006;53:1398–409.
mulation of photovoltaic arrays. IEEE Trans. Power Electron. 2009;24:1198–208. [32] Villalva MG, Siqueira TGD, Ruppert E. Voltage regulation of photovoltaic arrays:
[25] Sera D, Mathe L, Kerekes T, Spataru SV, Teodorescu R. On the perturb-and-observe small-signal analysis and control design. IET Power Electron. 2010;3:869–80.
and incremental conductance mppt methods for pv systems. IEEE J. Photovoltaics [33] Yepes AG, Freijedo FD, Lopez O, Doval-Gandoy J. Analysis and design of resonant
2013;3:1070–8. current controllers for voltage-source converters by means of Nyquist diagrams and
[26] Liserre M, Blaabjerg F, Hansen S. Design and control of an lcl-filter-based three- sensitivity function. IEEE Trans. Ind. Electron. 2011;58:5231–50.
phase active rectifier. IEEE Trans. Ind. Appl. 2005;41:1281–91.
369