Professional Documents
Culture Documents
Zero-Sequence Current Distribution Along Transmission Lines
Zero-Sequence Current Distribution Along Transmission Lines
Zero-Sequence Current Distribution Along Transmission Lines
6, JUNE 1969
for the same basic reasoni; rapid discharge of the local space charge. Mr. Chowdhuri's analysis of the reason for Dr. Berger's recordings
The study reported in [15] covered 50 effectively shielded trans- of initially coneave fronts is plausible. There are two possible ex-
mission lines from 115 to 230 kV over a sample size of 52 000 mile- planations why the Mount San Salvatore records do not show the
years. fast rising pip. One is the great height of the lightning target. The
It would be of interest to know what fractioin, if any, of the other is that the inistrumentation may not record it. The a,uthors'
103 strokes recorded were of positive polarity. investigations on transmission-line towers with an instrument of
The data presented by the authors constitute exceedinigly impor- fast response, the kineklydonograph, definitely show t,he st,eep rate of
tant bench marks which should serve to give impetuis to the study of rise.
voltages on transmission lines caused by electr ic and magnetic The strike distance h in Fig. 8 was chosen based on Schonland's
indtuction. data of 20-70-m step length, with the larger values occurrinig niearest
the earth. We call attention to Fig. 8 in which are plotted the calcu-
REFERENCES lated potentials at the point p for heights h of 25 and 75 m in addition
[15] E. R. Whitehead, "Lightning performance of EHYA. lines," to 50 m. In the regions of separations of 150-250 feet, the height of
CIGRE Lightning and Surges Committee, Auigtust 1968. the charge makes little difference in the poteiitials calculated.
Mr. Chowdhuri states that the calibrationi process used for the
KGR distorts the field somewhat and implies that this introduces
an error in the recordings. The authors wish to point, ouit that any
distortion of the field at the KGR is included in the calibration and
Edward Beck, Harold R. McNutt, Jr., Derrill F. Shankle, and does not introduice an error.
Charles J. Tirk: The authors wish to thank the discussers for their We thank Mr. Griscom for the poinit brotught out ill his discussion
comments on this paper. on the effect of charge distribuited along the leader relative to the
Referring to Mr. Chowdhuri's disculssion, the authors are glad charge in the leader head.
to note that he agrees that the data in the paper present a strong Mr. Stoelting's discutssion is very pertinenit to the performance
case for the Griscom prestrike theory. of arresters on overhead distribution systems. It is quite likely that
With regard to the electromagnetic potential induiced in the KGR, arresters on meditum voltage tranismission systems also are operated
it is difficult to calculate with mathematical rigor because the light- by potentials induced by nearby strokes.
ning-stroke channel is variable in diameter and direction. Likewise, Dr. Whitehead's discussion emphasizes the interestiig point that
the charge in the leader head is also diffictilt to calcutlate with the matter of potentials induced by nearby strokes has been much
mathematical rigor. However, based on the electrostatic component neglected for about 40 years and needs attention. Regarding the
alone, the KGR records produced gradients reasonably close to those polarities of strokes mentioned in the paper, the authors estimate
caleulated. It is possible that the electromagnietic potential com- from the records that less than 4 percent were positive.
ponents may be a factor, but their magnituides canniiot be deter- Over the years many theoretical studies have been made concern-
mined since the stroke eurrent characteristics were niot available in ing lightning and its effects. Mlany of the conclusions drawn from
these field tests. these studies are cointroversial. The authors feel that the best way to
resolve these controversies is to collect good field data t,o establish
facts. To this enid the authors are continuing their investigations and
Manuscript received M/larch 21, 1969. will report the results to the industry.
Abstract-The zero-sequence current distribution among ground faults supplied from either one or both sides are detailed. A summary
wires and the ground-return path of overhead transmission lines is of field tests is also included. The deviations between the measured
subject to change in the vicinity of a ground fault and the feeding and the computed values are found to be less than 15 percent.
point. This paper introduces the concepts used in connection with Several cases were studied to investigate the effect of factors,
the end-effect phenomena of transmission lines and describes the such as ground-wire material, tower-footing resistance, soil re-
necessity for solving the end-effect current distribution. After sistivity, and distance between feeding point and fault.
dealing with the influential factors and basic assumptions, it describes
a new calculation method which can be extended to develop general-
ized equations. The procedures to be followed in the case of ground INTRODUCTION
Paper 69 TP 61-PWR, recommended anid approved by the Trans- W HEN a grounid fault occurs in a network with an ef-
mission and Distributioii Committee of the IEEE Power Group for fectively grounded neutral, a fault (or zero-sequence)
presentation at the IEEE Winter Power Meetinig, New York, N. Y., current flows through the fault, through the ground-return path
January 26-31, 1969. Manuscript submitted August 29, 1968;
made available for printing November 27, 1968. and, if they are present, through the ground wires (Fig. 1).
The author was with the Department of Electrical Engineering, The distribution of this zero-sequence current among ground
Columbia University, New York, N. Y. He is now with the Depart- wires and ground-return path cau be calculated easily in the
ment of Electrical Engineering, Ohio State University, Columbus,
Ohio. simplest case, n-amely, when the circuit consists of a phase
SEBO: ZERO-S
Ht)+.1FNC CURRENI' DISIURIUNUTION 9) I 1.
Izog 4- Ip- IC
Pg
12
GROUND RETURN
Fig. 5. Graph of the basic equivalent circuit.
Fig. 8. Equivalent circuit otn onte span of a line.
f 1 1~~i 4'^s 1
I
c,nal
=t a tZop,nzog,'n Zoc,n rZog,n-i ZocirZog,
cIc,n Vc,n -1c,n-i lC2 'CI
I t,n (IPIC,n)4 RFP t,n-i4 Rt,n.l It,'n-24 Rt,n_2lIt,4 Rt, Ip-pc,4 4
I > < z 5'~~~ZFL '- F
g,n 0~°
l n _d Aog,n 7iII
Zog,n-.i .oI
41.-
gq,n-i
Fig. 6. Equtivalent circuit of a faulty line section supplied from one side, consisting of n spans
between the feeding point and the fault.
Fig. 6 is the equivalenit circuit of a line section consisting of n -Ip(Zom,n - Zog,n) + Ic,n(Zocn- Zog,n)
spans between the feeding point and the fault. The phase con-
ductor, ground wire, and ground-return path impedances, the - (IC n-l-IC n) R t,n - (I IPc,n)(Zog,n
- + RFP) = 0
tower-footing and station-grouiid resistances, as well as the or
mutual impedance between the phase conductor and the ground
wires are shown. The values can deviate from span to span. The Ip(Zom,n + RFP) -c,n(Zoc,n + Rt,n-l + RFp)
nth span contains the resistance RFP of the station (feeding-
point) ground. The resultant of the impedance of the ladder net- 0. (19) + IC,n_lRt,n-I =
work extending beyond the fault and of the resistance of the Thus, the calculation is simplified in such a way that matrix
faulty tower footing R'fl is ZFL. The impedance of the ladder equation (18) has to be written only for n - 1 spans. The nth
network can be calculated according to the most recent study span is to be considered by loop equation (19).
of Endrenyi [4]. This ladder network consists of ground-wire The five unknown quantities can be computed with the aid of
sections with ground-return paths and of tower-footing resis-
tances. (8), (18), and (19). This means that, in the knowledge of [La-,]
The boundary conditions at the fault are and using (14), the value of all ground-wire currents is readily
obtainable. The currents that flow in the ground-return path
Vp, ZFL(Ip - Idi) and towers can be calculated by means of Kirchhoff's current
law:
vcl ZFL(Ip -Icl)
(15) IV - Ic,k -Ig,k = 0 (20)
[Ri] = I = IP
L- C, _- IC, _i
ic,k 'c/C-I + It,k-l = 0. - (21)
If the values for conductor impedances, soil resistivity, and
The bounidary conditions before the nth span are tower-footing resistances are homogeneous along the line, then
Vp, n the Zop, Zoe) Zomy Zogy Z, and Rt values are uniform and
Vp,n
[S1] = [S2] = ** = [Sn-1] = [S]. (22)
_Rt,n_1(Ic,n-1- Ic,n)2
-
[Ln_1
[Ln-1] = [R]
[Rn] = Vc, n (16) Thus, instead of (18),
= =
IZk-Z k
ic,k+il Zoc,KZog,k Zk k F
c,kk
I
t,k
ig.kx 1 Zog,kI
09
t,k g,kt a)
Z A,k
7
I4k+l
oc ~-'Iv
Zs,k
b)
7ZZ,k
c k SPANS
0l9 P g,k4l (RESULTANT)
Fig. d. Six-ter^minal network which represents the kth span. Fig. 8. The btuilding up of the equivalent circuit of a faulty line
(a) Closed with an impedance star. (b) Resultant. section supplied from both sides. (a) Line sections at the fault.
(b) Resultant (last step).
If the process beginS at the fault, then
(24) Ipi
ZA,O = 0 ZB,O O0 ZZC,0 = ZFL. 0.6
- CALCULATED VALUES
If the process begins at the feeding point, then - MEASURED VALUES
The method can be checked by means of the voltage equations LINE SECTION
TOWARDS
LINE SECTION
BEYOND
from which relations (1) and (2) can again be obtained. It can FEEDING
POINTI
FAULT
ances are obtainable. Proceeding back from the fault toward the 10 5 0
SPANS
5 Io
feeding point with the knowledge of the resultant impedances,
all currents are readily obtainable. Fig. 9. Deviations between measured and computed values.
TABLE I
DATA FOR EXAMINED TRANSMISSION LINES AND THEIR GROUND WIRES
Transmission Line
Number of
Voltage Circuits Number of Ground Wires
Class and Towers
Case (kV) Arrangement per Mile Number Material Size
one, 3/8 in
I 120 horizontal 6.5 2 steel (50 mm1)
one, 475 kemil
II 220 wishbone 4.5 1 ACSR (250/40 mm2)
I'ci
Ip
10.6
P = 100 OHM METERS I7I A
I U
FEEDING
IPOINT IFAULT O
0 -
2 4 3 2 0 - b
DISTANCE IN MILES SPANS
Fig. 10. Ground-wire currents, effects of the ground-wire materials Fig. 11. Ground-wir e ctilrrents, effect of soil resistivity.
and of the tower-footing resistances.
j'IC
-0.8
lIcl P = IOO OHM METERS e 0
|iIp Rt = 5 OHMS DISTANCES BETWEEN FEEDING
v.v RFPA = 0.1 OHM d / 0.6 POINTS (FPA,FPB) AND FAULT (F)
P =100 OHM METERS 2-3/81N, STEEL GROUND WIRES RFPS = 0.1 OHM a FPA - F 25 SPANS,
Rt = 5 OHMS DISTANCE BETWEEN FEEDING b: FPA - F 10 SPANS,
RFP= 0.1 OHM POINT AND FAULT: C FPA - F 5 SPANS,
a 50 SPANS 475 MCM, ACSR GROUND WIRE c d: FPA - F 3 SPANS,
b 20 SPANS e: FPA - F SPAN,
c 10 SPANS
d 6 SPANS 0.4
e; 3 SPANSe
d 0.2
a ~~~~~~~~~~~~b
Fig. 12. Ground-wire currents, effect of the location of the fault Fig. 13. Ground-wire currents, effect of the location of the fault
and the distance between the feeding point and the fault, in the and the distance between the feeding point and the faullt, in the
case of a fault fed only from one side. case of a fault fed from both sides.
For the cases shown in Figs. 10-13, the data for the two ex- TABLE II
amined transmission lines and their ground wires are compared LENGTH OF END-EFFECT SECTIONS AND SELECTED FACTORS
in Table I. WIIICH INFLUENCE IT
Ahmed H. El-Abiad (Purdue University, Lafayette, Ind. 47907): are satisfied, and therefore the circuit is correct.
Prof. Sebo is to be highlv congratuilated for an excellent paper on I have used in CESI the equivalent circuit of Fig. 16 for the same
a subject that deserves more attention, particularly because of the problem as the author's and also, with the addition of capacitances,
accelerating expansion of EHV systems. Evaluation of ground wire for the study of transients in cables [14].
and tower currents is needed not only under fault conditions, but With respect to the equivalent circuits of Figs. 7 and 8, 1 think
also due to normal operation as a result of not transposing EHV lines that my equivalent circuit allows a faster computation of the for-
and unbalanced operating conditions, such as during single-pole mation of the equivalent impedance stars and of the proceeding
switching. back from the fault to obtain all the currents.
The assumptions made by the author in developing his methods
are reasonable, and there should be no objection to their practical REFERENCES
application except in the case of the first two. These objections are
1) neglecting mutual coupling between circuits on the same right-of- [14] A. Clerici and R. -_Manara, ''Transient network analyser study
way and 2) assuming that all circuits are symmetrically transposed. of overvoltages in cross-bonded ac cables," presented at the
To overcome these difficulties in problems involving the analysis IEE Conf. on Progress in Overhead Lines and Cables for 220 kV
and Above, Lonidon, England, September 1968.
of network of multiconductor elements, Purdue University re-
searchers have developed several programs [9], [10] based on the
methods in [11, chs. 5 and 6]. In these applications, the charac- 1 And in general in the case of two parallel wires with ground-return
teristics of multiconductor lines are computed according to the path.
method published by Coleman et al. [12] and later by Hesse [ 13].
REFERENCES
[9] A. H. El-Abiad, M. K. Cheney, Jr., W. N. Keene, and D. C.
Tarsi, "Three-phase analysis of unbalanced distribution
circuits," 1967 PICA Conf. Rec., pp. 411-419.
[10] A. H. El-Abiad and D. C. Tarsi, "Load flow solution of un-
transposed EHV networks," 1967 PICA Conf. Rec., pp. 377-
384. K. H. Feist (Siemelns AG, Erlanigen, Germany): As a conitribu-
[111 G. W. Stagg and A. H. El-Abiad, Computer Methods in Power tion to the interesting paper of Prof. Sebo, I should like to submit a
System Analysis. New York: McGraw-Hill, 1968. short discussion about studies and tests that I have made myself.
[12] D. Coleman, F. Watts, and R. B. Shipley, "Digital calculation Earth electrode potentials of towers, ground-wire currents, and
of overhead-transmission-line constants," AIEE Trans. current flowing through ground-return paths can easily be estimated
(Power Apparatus and Systems), vol. 77, pp. 1266-1270, 1958
(February 1959 see.). by the solution of an equiation of differences. A mean value of
[13] NI. H. Hesse, "Electromagnetic and electrostatic transmission- the length of the spans and a mean value of tower-footing resistance
line parameters by digital computer," IEEE Trans. Power must be used. I have explained this in a theoretical study completed
Apparatus and Systems, vol. 82, pp. 282-291, June 1963. in 1958 [15, pp. 56, 60 - 64]. In this connection tests were made
oIn several transmission lines [16, Fig. 10], [15, Figs. 36, 37, Appen-
dix, Fig. 25, pp. 94-95].
Manuscript received February 24, 1969. The symbol ks denotes the screenin-g factor [18] in the middle of a
longer line section betweeni the substation with neutral grounded
at the one line end and the fault location. If IF is the ground-fault
current, an upper limit of the earth electrode potential at the fault
tower is given by
A. Clerici (CESI, Milan, Italy): This paper gives a very clear picture
of the influence of different factors on the zero-sequence current VS = IF AS . W.
distribution along transmission lines and on the possible calculation
where the factor c represents the influence of the other tower-footing Stephen A. Sebo: I wish to thank the discussers for their efforts and
resistances. c varies between 1.05 and 1.20 and is dependent on the for their valuable contributions to this study. I am most grateful for
material, number, and size of the grotunid wires and the length of the the kind remarks made by the distinguiished discussers.
spans. With regard to Dr. El-Abiad's discussion, I certainly agree that it
The above formula could easily be applied because lists of the is necessary to develop programs that do the more sophisticated
spans and the tower-footing resistances were available. types of calculations. The programs presented here are valid only for
From the theory of zero-sequence current distribution along trans- single-circuit three-phase overhead transmission lines. With mod-
mission lines it is possible to develop measuring circuits, which ifications the same principle is also applicable for multiconductor
simulate in the earth an electromagnetic field proportional to that lines and cables. This additional research is only too welcome by me.
under the faulty line [16, Figs. 6, 9, and 12]. I thank Dr. Clerici for presenting a view on how to form another
Such a simulation is also possible for lines with varying soil equivalent circuit. I agree with him on the possibility of different
resistivity or a varying number of ground wires along the line [18]. equivalent scheme arrangements. Nevertheless, the advantage of the
Tests made with the measuring circutits mentioned also show the equivalent scheme shown by Figs. 3 and 4 is that the identity of each
influence of other compensating conductors. For instance, it is often circuit (each conductor, ground-return path, and tower-footing
possible in this manner to determine that certain grounding measures resistance) was retained. Concerning his second suggestion, I would
or installation of gas discharge tubes at the end of telecommunication like to remark that rather simple equations can be derived in the
lines can be dispensed. course of the use of my second proposed solution with equivalent
impedance stars. That means that there should not be too much
REFERENCES difference between the computational speeds using the different
[15] K. H. Feist, "Die Erderspannung geerderter stromdurch- equivalent schemes.
flossener Leiter bei Wechselstrom niedriger Frequenz und ihr It is very valuable to have Dr. Feist's discussion. His method
elektrisches Str6mungsfeld im Erdreich," dissertation, Tech- represents another approach to the problem, and his results are well
nische Hochschule, Hanover, Germany, 1958. known internationally. I think one of the differences between our
[16] ,"Der Einfluss der Sternpunktbehandlung auf die Be- approaches is that his method uses the mean value of the length of
messung der Erdungsanlageni in Hochspannungsnetzen," the spans and the mean value of the tower-footing resistances. The
Elektrizitatswirtschaft, pp. 105-112, 1958. programs presented here are based on the assumption that values
[17] "Bestimmungen fuir Massnahmeni bei Beeinflussung von Fern- for the conductor impedance (or length of the span), the soil re-
meldeanlagendurch Drehstromanlageni," VDE Publ. 0228/4.65, sistivity, and the tower-footing resistances can be either homo-
paragraph 23e, 4, 1965.
[18] K. H. Feist, "Einflussgr6ssen der Drehstromhochspannungs- geneous or inhomogeneous along the line.
netze fuir die Induzierung unid ohmsche Einkopplung von
Spannungen in Fernmeldekreisen,' ETZ-A, vol. 85, pp. 641-
646, 1964. MIanuscript received April 2, 1969.
Abstract-This paper reports the results of field tests conducted This paper documents the effectiveness of the resistor preinsertion
on the Northern States Power Company's 345-kV transmission breaker in reducing switching-surge transients and compares this
system which investigated the effects of various system switching breaker with one having direct closing contacts (on a single-phase
operations on transient overvoltages. Following the field tests a basis). Phase-to-phase transient overvoltages are discussed, and
transient network analyzer was used to duplicate the field tests and voltage distribution curves are presented.
then explore the maximum switching transients which system pa-
rameters could produce.
INTRODUCTION
ALMIOST ALL EHV transmission systems are thoroughly
Paper 69 TP 62-PWR, recommended and approved by the Trans- analyzed in the design stages, but the urgent need to place
mission and Distribution Committee of the IEEE Power Group for them in service upon completion often precludes field testing.
presentation at the IEEE Winter Power Meeting, New York, N. Y.,
January 26-31, 1969. Manuscript submitted October 31, 1966; made While field testing is concerned with electrical characteristics,
available for printing November 25, 1968. such as switching-surge overvoltages, there are additional
G. W. Alexander is with the General Electric Company, Pittsfield,
Mass. 01201. benefits in obtaining operating confidence in the system addition.
J. E. Mielke is with Northern States Power Company, Minne- In view of this, the Northern States Power Company scheduled
apolis, Minn. field testing prior to placing their initial 345-kV system in
H. T. Trojan is with the General Electric Company, Schenectady,
N. Y. 12305. operation.