~-f~~C6"'l,..</~c..

tt~
SAFETY, STRUCTURES AND FIRE DEPARTMENT
Reactian ta tire

REACTION TO FIRE CLASSIFICATION REPORT

No. RA05-0005A

ACCORDING TO THE EUROPEAN ST ANDARD

NF EN 13501-1

Provided the Ordinance from the Ministry of the interior, November 21,2002.
Pilot laboratory approved by the Ministry of the Interior (Ordinance of February 5, 1959, amended)
Seule la version française fait foi.
Only the French version is legally acceptable.

Valid 5 years as from January Th, 2005

Owner : ALCOA ARCHITECTURAL PRODUCTS


1 rue du Ballon
68500 MERXHEIM
FRANCE

Commercial brand(s) : REYNOBOND@ 55 PE riveted system

Brief description : Double skin aluminium faced panels with polyethylene core.
(see detailed description in paragraph 2)

Date of issue : January 7th, 2005

The indicated classification does not prejudge the conformity of marketed materials with the samples submitled
to the tests and under no circumstances, this document should not be considered as type approval or
certification of the product in the sense of the L 115-27 article of the consumption's code and of the law dated
June 3rd, 1994.
The reproduction of this classification report is only authorised in its integral form, with or without its test report
atlached.
It comprises 4 pages.

PARIS- MARNE-LA-VALLÉE -GRENOBLE -NANTES -SOPHIA ANTIPOLIS


CENTRE SCIENTIFIQUE ET TECHNIQUE DU BÂTIMENT
84, avenue Jean-Jaurès -Champs-sur-Marne -BP 2- F-77447 Marne-Ia-Vallée Cedex 2
Tél. .01 64 6864 12- Fax .01 64 6864 79- Site web dssf.cstbjr
2/4 Classification report
No. RAOS-OOOSA

1. Introduction

This classification report defines the classification assigned to the above-mentioned


product(s) in accordance with the procedures given in the EN 13501-1 standard.

2. Product description

Composite panel consisting of a low density polyethylene core thermally bonded (using a
70 jJm thick polyethylene film) between two precoated aluminium sheets.
Tested system : riveted on metallic substructure.

Nominal thickness : 4 mm.


Nominal thickness of the aluminium sheets : 0.5 mm.
Nominal mass per unit area : 5.5 kg/m2.
Finishing coat : DURAGLOSS@ 5000.
Colour : grey/green.
3/4 Classification report
No. RAOS-OOOSA

3. Tests reports and tests results in support of this classification


3.1 Tests reports

3.2 Tests results

EN ISO 11925-2 REYNOBOND@SSPE


Fs = 150 mm Not reached
305 edge riveted system 6
Filter paper Not ignited
eXpO5Ure (polyethylene core)

REYNOBOND@SSPE
EN 180 11925-2
riveted system Fs = 150 mm Not reached
305 surface 6
(precoated aluminium Filter paper Not ignited
exposure
sheet)

, FIGRAo,2MJ(W/s) 80.1
FIGRAo,4MJ(W/s) 80.1
LFS Nat reached
THR6oos(MJ) 5.3
REYNOBOND@ PE 55
EN 13823 3
riveted system SMOGRA(m2/s2) 7.8

TSP 6005(m2) 58.3

Flaming droplets None


or debris
(-) means : not applicable
4/4 Classification report
No. RAOS-OOOSA

3.2. Classification and direct field of application

4.1 Reference of the classification


This classification has been carried out in accordance with clause 10.6' 10.9.3 and
10.10.1 of the EN 13501-1 standard.

4.2 Classification

Flaming droplets or
Fire behaviour Smoke production
debris

B 52 dO

4.3 Field of application

This classification is valid for the followina croduct carameters :

For a thickness of 4 mm.

Only for the system riveted on any metallic substructure.

This classification is valid for the followina end use conditions :

On any A 1 or A2 substrate with a density ~ 700 kg/m3,

With a minimum air gap of 50 mm,

Champs-sur-Marne, January th, 2005

Technician Head of the Reaction to Fire Laboratory