4000046273-PGCA-EA-C16-001 - 5.2 - 3 - Cause and Eff PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Document Title: CAUSE & EFFECT

Project Doc. 4000046273-PGCA-EA-C16- Revision: 5.2


Number: 001
Vendor Doc. 6074-C05-001 Vendor A
Number: Rev.:
Facility Identifier: PGCA
Discipline: EL Document CED
Type:

Submitted For: Vendor Name:


Review x Approval Info. Certified SIEMENS

Review does not constitute acceptance of design


details, calculations, test methods or materials
developed or selected by vendor nor does it relieve
vendor from full compliance with contractual or other Package Description:
obligations. Gas Turbine Generator Package

A. Approved
(Submit final document in MDR/IOM
only)
P.O. No:
Manufacture may proceed
4000046273
B. Approved with comments
(Revise and resubmit document)
Manufacture may proceed once Model/Serial No.:
comments are incorporated SGT-300-1S
C. Rejected
(Resubmit)
Manufacture may not proceed VDRL Prime Code:
I. For Information Only C16
(Submit final document in MDR/IOM
only) Tag No.:
Name: Xavier Grostabussiat
NA
Signature:
Date: 19 Apr 2019

PEGAGA DEVELOPMENT
PROJECT
The linked image cannot be display ed. The file may hav e been mov ed, renamed, or deleted. V erify that the link
points to the correct file and location.

Comment Response Sheet

Company : MDC Oil & Gas (SK320) Ltd CRS for Doc.: 6074-C05-001

Project Title : Provision Of Engineering, Procurement, Construction, Installation Doc. Title : CAUSE & EFFECT
And Commissioning (EPCIC) for the Pegaga Development
Project Doc. No. : 4000046273-PGCA-EA-C16-001 Rev: 5.1

PO No. : 4000046273

Stat
Commented us
No. Section Comment Response Date Remarks
by O/C
*

Pg.2 Decelerate To Minimum Load (DML)? SEI: Yes TS 03/29/2019 C

Pg.2 Why closed valve should inhibit start? SEI: Before turbine start, vent valve shall TS 03/29/2019 C
be fully opened. Therefore start inhibit
required if not in start position
Pg.2 Why this cause is required? Is it different SEI: It is abnormal condition and requires TS 03/29/2019 C
from the above causes trip if occurs. Start is prevented by off-skid
block valve not closed fault.
Pg.2 Why this cause is required? Is it different SEI: It is abnormal condition and requires TS 03/29/2019 C
from the above causes trip if occurs. Start is prevented by off-skid
block valve not closed fault.
Pg.11 Is there a requirement to trip the GTG? SEI: trip is not required for this condition TS 03/29/2019 C

Pg.12 Water mist activation SEI: will be added in next revision TS 03/29/2019 C

Page 1 of 2
The linked image cannot be display ed. The file may hav e been mov ed, renamed, or deleted. V erify that the link
points to the correct file and location.

Comment Response Sheet

Stat
Commented us
No. Section Comment Response Date Remarks
by O/C
*

Pg.12 It should be 2oo3. Vendor to advise if any SEI: Voting on Fire Detection is not TS 03/29/2019 C
specific reason to design with 1oo3 possible as the flame detectors do not
cover the same area
Pg.12 GDs voting SEI: It will be 2oo3 voting for gas TS 03/29/2019 C
detectors. Will be added in next revision

Pg.12 GDs voting SEI: It will be 2oo3 voting for gas TS 03/29/2019 C
detectors. Will be added in next revision

Pg.12 GDs LEL levels SEI: Siemens design is engineered for TS 03/29/2019 C
LEL levels of 10% & 20% which are more
conservative.
Pg.12 Indicate ventilation trips as appropriate for SEI: will be added in notes section. TS 03/29/2019 C
these causes

Pg.17 SIE to advice why these signals not required SEI: Generator is protected by generator TS 03/29/2019 C
to trip the unit. Excitation fails, rotor earth control panel which open up generator
fault, protection relay fault, syn fail are major circuit breaker. Turbine does not have to
faults. trip for these condition.
Additional Notes (if any)

* O - Open, C - Closed

Page 2 of 2
PROJECT NAME Pegaga

PROJECT NUMBER HI6074

PROJECT TITLE SGT300-1S Gas Turbine Generator Package

DOCUMENT NO 6074-C05-001

TITLE Cause and Effect

REV. DATE DESIGNED CHECKED APPROVED REVISION


A 02/15/2019 T SIDDIQUI X.GROSTABUSSIAT V PARAVASTU Initial Release
Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

6074/C01/001 XV30 Off Skid Block Valve ZS45 - FAULT - NOT OPEN(3)(6) X X
ZS12 FAULT - NOT CLOSED(3)(6) X X X
XV31 Off Skid Vent Valve ZS44 - FAULT - NOT OPEN(3)(4) X X
ZS11 FAULT - NOT CLOSED(3)(4) X X X
ZS11 &
ZS45
2oo2 FAULT - NOT CLOSED X X
XV7 On Skid Block Valve ZS5 - FAULT - NOT OPEN(3)(4) X X
ZS178 FAULT - NOT CLOSED(3)(4) X X X
XV212 On Skid Vent Valve ZS742 - FAULT - NOT OPEN(6) X X X
ZS743 FAULT - NOT CLOSED(3)(4) X X
ZS5 &
ZS743
2oo2 FAULT - NOT CLOSED X X
XV6 On Skid Block Valve ZS208 - FAULT - NOT OPEN(3)(6) X X
ZS207 FAULT - NOT CLOSED(3)(6) X X X
ZS45,ZS5
ZS208
2oo3 FAULT - NOT CLOSED X X
PT2A
XV150 Main Gas Fuel Control Valve Assembly
PT2B
Avg < 6.8(6)(7) BarG X X
rising 0.2(5) X
falling 10(8) % X
> 0.5(9) BarG X
rising 0.2(5)(11) X X
falling 10(8)(11) % X X
> 0.5(9)(11) BarG X X
26 X
28.7 X
2oo2 FAULT - PV SIGNAL(3)(4) X X X
PT181A
PT181B
Avg > 18 BarG X
0.69(1) X
Avg
> 0.1(15) X
2oo2 FAULT - PV SIGNAL(3)(4) X X X
PT2
PT181
< 3.8(14) BarG X
3(12) X
2.7(13) X
2.4 X
1.9(2) X
1.4 X
PT220A
XV149 Pilot Gas Fuel Control Valve Assembly
PT220B
2oo2 FAULT - PV SIGNAL(3)(4) X X X
PT182A
PT182B
Avg > 16 BarG X
0.69(1) X
Avg
> 0.1(15) X
2oo2 FAULT - PV SIGNAL(3)(4) X X X
PT220
PT182
< 3.8(14) BarG X

001 Gas fuel Page 2


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

3(12) X
2.7(13) X
2.4 X
1.9(2) X
1.4 X
6074/C01/001 - Supply Temperature TT6 - < 5 DegC X
2.5(2) X
0 X
> 140 X
145(2) X
150 X
FAULT - PV SIGNAL(3)(10) X X X
- Coalescer PDT140 - > 0.4 Bar X X
FAULT - PV SIGNAL X X
LD103 - LEVEL HIGH X X
FAULT - PV SIGNAL X X
- Flow Transmitter FT1 - FAULT - PV SIGNAL X
Notes
1 Monitoring enabled during ignition sequence only.
2 Automatic change to liquid.
3 Changeover to gas fuel inhibited. If in progress a changeover to gas fuel will be aborted.
4 Trip / start inhibit only active if gas selected.
5 Enabled during gas fuel proving sequence - on-skid block and vent valves closed after void vented.
6 Trip / start inhibit only active if gas selected and the turbine is not lit.
7 Enabled when starting on or changing to gas fuel and gas is supplied to pressure transmitters but not to the engine.
8 Enabled during gas fuel proving sequence - on-skid block and vent valves closed after void pressurised.
9 Enabled during gas fuel proving sequence - on-skid block valves closed, on-skid vent valve open.
10 Trip if still running on gas fuel after 20 min. Will attempt automatic changeover to liquid, if available, prior to trip.
11 Trip monitoring only active during start. On a changeover to gas fuel, the changeover will be aborted.
12 Enabled when generator connected to grid - will prevent further increases in load demand.
13 Enabled when generator connected to grid - will act to decrease load demand while condition exists.
14 Enabled at the beginning of a changeover to gas when gas supplied up to second on-skid block valve. Condition will abort changeover.
15 An excessive rise of the average pressure during ignition will cause a shutdown

001 Gas fuel Page 3


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

ZS15
6074/C01/002 XV75 Off skid Liquid Block Valve
ZS10
- FAULT - NOT OPEN(1) X X
FAULT - NOT CLOSED(2) X X X
FAULT - BOTH SET X
- Liquid Fuel Filter PDT6 - > 0.75 Bar X
- Liquid fuel supply pressure PT10 - FAULT - PV FAULT X X X
> 3(3) BarG X
5(5) X
8 X
8.5 X
< 0.21(2)(4) X X
< 0.5(22) X X
0.5 pk-pk
>
freq>1Hz X
XV213 Liquid fuel Primary Stream Control Valve ZC2 - FAULT - CV SIGNAL(16) X X X
ZT13 FAULT - POSITION FB SIGNAL
(16)
X X X
ERROR FROM
DEMAND > 5(16)
% X X X
XV214 Liquid Fuel Secondary Stream Control Valve ZC20 - FAULT - CV SIGNAL(16) X X X
ZT108 FAULT - POSITION FB SIGNAL(16) X X X
ERROR FROM
DEMAND > 5(16)
% X X X
- Liquid Fuel Primary Stream Pressure PT279 - > 100 BarG X
(1)
0.3
< During X X X
Prime
- Liquid Fuel Secondary Stream Pressure PT351 - > 80 BarG X
0.3(1)
< During X X X
Prime
PT279
- Liquid Fuel Primary/Secondary Stream Pressure
PT351
2oo2 FAULT - PV SIGNAL(1)(6)(15) X X X
> 10(1)(6)(15) BarG X X X
XV425A ZS984
XV425B
Liquid Fuel Priming Valve
ZS983
- FAULT - NOT OPEN (16) X X
FAULT - NOT CLOSED (16) X X X
FAULT - BOTH SET X
XV423A ZS980
XV423B
Ganged Purge / Block valves
ZS979
- FAULT - NOT OPEN X
FAULT - NOT CLOSED X X X
FAULT - BOTH SET X
ZS982
XV424 Liquid Burner Purge / Drain Valve
ZS981
- FAULT - NOT OPEN X X X
FAULT - NOT CLOSED X X X
FAULT - BOTH SET X
ZS988
XV427 Purge Air Selector Valve
ZS987
- FAULT - NOT OPEN X X X
FAULT - NOT CLOSED X X X
FAULT - BOTH SET X
ZS990
XV147 Air Purge Block/Vent Valve
ZS989
- FAULT - NOT OPEN X X X
FAULT - NOT CLOSED X X X
FAULT - BOTH SET X

002 Liq fuel N Pkg Page 4


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

- Air Assist Pressure PT238 - FAULT - PV SIGNAL(1) X X X


> 0.3(8) BarG X X
2.5(9)(12)(17) X
< 0.5(9) X X
1.1(9) X
2.5 (9)(11) X
4.0(10) X
XV585 Air Assist Control Valve ZT165 FAULT - POSITION FB SIGNAL X X
ERROR FROM
DEMAND > 5
% X
ERROR FROM
DEMAND > 10 (11) X X
< DEMAND - 10 X
- Cooled P2 Air Temperature TT133 - > 170 DegC X X
> 150 X
< 40 (10) (19) X
ZS992
XV148 Burner Purge Block Valve
ZS991
- FAULT - NOT OPEN (1) X X X
FAULT - NOT CLOSED (18) X X X
FAULT - BOTH SET X
ZS383
XV152 GF Pilot Burner P2 Block Valve
ZS382
- FAULT - NOT OPEN X X
FAULT - NOT CLOSED (7) X X X
FAULT - BOTH SET X
ZS927
XV388 Ignition/Purge Gas Block Valve
ZS926
- FAULT - NOT OPEN X X
FAULT - NOT CLOSED X X X
FAULT - BOTH SET X
- Liquid Fuel Coalescing Filter Differential Pressure PDT69 - > TBD

- Level Swicth Liquid Fuel Coalescing Filter LS104A - LEVEL HIGH X


- Level Swicth Liquid Fuel Coalescing Filter LS104B - LEVEL HIGH X
Notes
1 Trip only enabled until turbine is lit
2 Start inhibit / trip only while stopped / starting
3 Enabled if off skid liquid fuel is set up
4 Only enabled while high pressure liquid fuel pump is running
5 Three minute delay on Trip
6 Trip / Start Inhibit only on liquid fuel
7 Failing to close on a changeover to gas will abort changeover rather than shutdown
8 Air assist off
9 Using regulated air
10 Running, using unregulated air
11 Trip only during test
12 Warning only before engine is lit
13 -
14 -
15 Only abort prime / trip if PT279 and PT351 are both high / failed
16 Trip / start inhibit only if not on 100% gas fuel
17 Test not in progress
18 Trip not active on liquid fuel after turbine is lit
19 Fifteen minute delay on Warning
20 -
21 -
22 Enabled on liquid prime prior to on-skid pump starting. Abort prime, or shutdown on a start, if pressure low after 15 seconds

002 Liq fuel N Pkg Page 5


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

6074/C01/005 - Oil Tank LT1 - > 105 % X


< 88 X X
36 X
28(13) X
FAULT- PV SIGNAL(13) X X
TT7 - < 20(4) °C X X
FAULT- PV SIGNAL X X
Pump running
XP3 Emergency Lub Oil Pump Contact DCC5 -
when not required(3) X X
Pump not running
when required(1) X X
Pump Selector In Manual
KS2 -
Mode(2) X X X X
HV57 Oil Filter PDT8 - > 1.4(5) Bar X
TT66A
- Turbine Oil Supply
TT66B
> 5 °C X
1oo2
(Note 17) < 25(18) X
(11)
20
Oil Hot(12)
X X X X
15(11)
Oil Cold(12)
X X X X
> 66 X
74 X X X
2oo2 FAULT- PV SIGNAL X X X
PT6A
PT6B > 0.3 BarG X
1oo2 0.75 (6)
(Note 17) <
Oil required (1st)
X
0.65(6)
Oil required (1st)
X X
0.6
DC pump on X X
(6)(14)
1.5/1.7
Oil required (2nd)
X
1.4(6)(16)
Oil required (2nd)
X X
(7)
1.5
>
Oil required (1st)
X
(7)(15)
3.5/2.3
Oil required (2nd)
X
2.5(9) X X X
(10)
0.6
All pumps off

0.4
All pumps off X
2oo2 FAULT- PV SIGNAL X X X
- Lub Oil Cooler Fan A US9 - VIBRATION HIGH X
Lub Oil Cooler Fan B US10 - VIBRATION HIGH X

005 Lube Oil N Pkg Page 6


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

Notes
1 Trip only applicable during emergency pump test
2 Trip only applies during a start or spinning on the starter
3 Trip only applicable during auxiliary pump test
4 3 second delay on actions
5 Monitoring will only be enabled once the turbine running. Monitoring is disabled when lub oil is not required
6 The first set of levels are used below 8000 rpm (300 rpm hysteresis) otherwise the second levels are used
7 The first set of levels are used below 4000 rpm (300 rpm hysteresis) otherwise the second levels are used, 10 second delay on monitoring
8 Level varies depending on turbine state. 10 second delay on monitoring
9 Monitoring disabled on a start at the end of turbine spin and remains disabled until a shutdown occurs, 10 second delay on action
10 High oil pressure detected for 5 seconds will cause labyrinth seal air to be required
11 Start hold to allow the oil to warm up. If the oil temperature fails to warm up the engine will shutdown
12 The lub oil is deemed as hot 10 minutes after the turbine has lit and then until the engine is shut down with no requirement for shutdown spin
13 Condition will cause lubrication oil tank heaters to be inhibited
14 Lower level used if the unit is stopped or starting, higher level if running
15 First value used during a start from the end of turbine spin until running
16 Shutdown spin is only disabled if pressure drops below 0.65 barG
17 If two sensors are healthy, 1oo2 monitoring is used if a difference warning is present, otherwise an average reading of the two sensors is used
18 Monitoring enabled once engine has been lit for 10 minutes

005 Lube Oil N Pkg Page 7


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

6074/C01/012 - Starter motor winding TD5 - TEMPERATURE HIGH(4) X X


TD6 TEMPERATURE VERY HIGH X X
SD1
6074/C01/007 - Gas Generator
SD3
> 50 rpm X
<> SPIN SPEED (5)
X X X
IGNITION SPEED(6) X
STARTER OFF(7)
<
SPEED X X
2oo2 FAULT - PV SIGNAL X X X
UD10X1
- GG drive end journal bearing
UD10Y1
1oo2 > 66 µm pp X
79 X
89 X X
2oo2 FAULT- PV SIGNAL X X X X
TC23
TC91
1oo2 > 74(10) °C X
110 (11)
X
115 (9)
X
120(12) X X X
2oo2 FAULT- PV SIGNAL X

007 Rotating system Page 8


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

TC21
TC22
1oo2 > 74(10) °C X
115(11) X
140(9) X
145 (12)
X X X
2oo2 CIRCUIT FAULT X
UD11X1
- GG non drive end journal bearing
UD11Y1
1oo2 > 66 µm pp X
79 X
89 X X
2oo2 FAULT- PV SIGNAL X X X X
TC24
TC92
1oo2 > 74(10)
°C X
125(11) X
140(9) X
145(12) X X X
2oo2 FAULT- PV SIGNAL X
TC261
- GG reverse thrust bearing
TC262
1oo2 > 74(10) °C X
115(9) X
145(12) X X X
2oo2 FAULT- PV SIGNAL X
- Vibration monitoring system US5 - FAULT X
Turbine vibration US6 - HIGH X
US7 - VERY HIGH X X
- All cold end bearing thermocouples - - ALL FAILED(10) X
All hot end bearing thermocouples - - ALL FAILED (10)
X
Notes
4 Start hold if passed hold 1 but not passed hold 2 AND starter is not enabled
5 This check is carried out on a start when going to spin speed. Warning will occur after 40s and shutdown after a further 10s if speed is not achieved.
6 This check is carried out on a start when going to ignition speed. Shutdown will occur after 25s if speed is not achieved.
7 This check is carried out on a start after the engine has lit. Warning will occur after (120s) and shutdown after a further (30s) if speed is not achieved.
8 This check is carried out on a start after the engine has lit. Warning will occur after 300s and shutdown after a further 75s if dwell speed is not achieved.
9 Monitoring enabled when engine is running.
10 Maximum start hold time for bearing to cool set at two minutes; after this the start will continue.
11 Warning enabled on a start just before the starter is activated and until the turbine has been stationary for 10 minutes.
12 Trip enabled on a start just before the starter is activated and until the unit stops and shutdown spin complete or disabled.

007 Rotating system Page 9


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

6074/C01/008 XF33 Enclosure ventilation air filter PDT27 - > 4.9 mBar X
10(4) X X
0.98(2)(5) X
< 1.25(4) X X
- Enclosure PDT138 - FAULT - PV SIGNAL(3) X X
> 10(1) mBar X X
< 1.25(1) X X
> 0.98(2) X
- Exhaust PDT133 > 40(11) mBar X X X
> 55 mbar X X
FAULT- PV SIGNAL X X X
Notes
1 Monitoring enabled when ventilation fans running. Warning after 5 seconds. Trip after 30 seconds if unit active.
2 Monitoring enabled when the unit has stopped and the ventilation fans have not run for 60 seconds (30s on E package).
3 A trip can only occur when PDT27 is also in fault or not fitted
4 Only applies when PDT138 has failed. Warning only applies on vent fan fail. Trip applies on flow fail
5 Only enabled when PDT138 has failed

008 Package Page 10


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

PS328 BOTTLE RELEASE


6074/C01/017 - Extinguishant Bottle Rack
PS329
1oo2
PRESSURE HIGH(2) X X
1oo2 FAULT- PV SIGNAL(1) X X X
SOL630
SOL631
SOL603
1oo2 FAULT- PV SIGNAL(1) X X X
SOL565
ZS2011/
ZS2014 1oo2 BOTTLE WEIGHT LOW X
2oo2 BOTTLE WEIGHT LOW (1) X X X
PS282/
PS283 1oo2 BOTTLE PRESSURE LOW X
2oo2 BOTTLE PRESSURE LOW (1) X X X
ZS384
HV142 Extinguishant Isolation Valve ZS235 - ISOLATION VALVE CLOSED X X
- ISOLATION VALVE NOT OPEN X

Notes
1 15 minute delay on trip
2 Shutdown will isolate power to the auxiliary oil pump, enclosure ventilation fans and damper control solenoids

017 Extinguishant Bottle Rack Page 11


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

YD5
6074/C01/009 - Turbine Enclosure YD7 1oo3 FIRE(2)(3) X X
YD8
1oo3 FAULT- PV SIGNAL(1) X X X
TD2A
TD2B 1oo2 HEAT(2) X X
1oo2 FAULT- PV SIGNAL(1) X X X
MAC1
MAC2
1oo2 MANUAL ACTIVATION(2) X X
MAC5 - MANUAL ACTIVATION(2) X X
GISIG1082 - GROUND FAULT X
YV2 Enclosure vent exit damper ZS17 - FAULT - NOT OPEN(6) X X X
ZS76 FAULT - NOT CLOSED(7) X X
FAULT - BOTH SET X
YV1 Enclosure vent inlet damper ZS16 - FAULT - NOT OPEN(6) X X X
ZS99 FAULT - NOT CLOSED(7) X X
FAULT - BOTH SET X
GD1
- Turbine Enclosure Ventilation Air Exit
GD2
1oo3 > 10(1) %LEL X X X
GD14 20 X X
1oo3 FAULT- PV SIGNAL X X X
GD3
- Turbine Enclosure Ventilation Air Inlet
GD4
1oo3 > 10(1) %LEL X X X X
GD13 20 X X X
1oo3 FAULT- PV SIGNAL X X X X
GD6
- Turbine Combustion Air Inlet
GD11
1oo3 > 10(1) %LEL X X X X
GD12 20 X X X
1oo3 FAULT- PV SIGNAL X X X X

Notes
1 15 minute delay on trip
2 Fire shutdown will isolate power to the auxiliary oil pump, enclosure ventilation fans and damper control solenoids
3 In manual mode and with isolation valve closed shutdown will be inhibited
6 Trip if open test fails on a start or trip/start inhibit if damper indicated closed (N only). Trip only if both dampers not open while unit active (E only)
7 Trip during a start if damper close test fails (N only). Warning 5s after C02 detected (E only)

009 Fire & Gas Page 12


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Slow Unload

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

6074/C01/008 - Combustion inlet filter PDT1 - > TBD mBar X


TBD(3) X X X
TBD X X
PDT97 - > TBD mBar X
TBD(3) X X X
TBD X X
RTD1
6074/C01/007 - Combustion Air Inlet
RTD48
∆ > 10 ºC X
2oo2 FAULT - PV SIGNAL X
Avg(27) < -41(28) ºC X X
< -60 X
> 56(29) X X X
> 75 X
6074/C01/032 - Inlet Guide Vanes ZC4 - FAULT - CONTROL VALUE X X X
ZT9 - FAULT - OUT OF POSITION X X X
FAULT - CALIBRATION X X X
FAULT- PV SIGNAL X X X
> HIGH LIMIT º X X X
< LOW LIMIT X X X

Gas path Page 13


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Slow Unload

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

TC255
6074/C01/007 - Turbine Burner Tips
TC256
∆ > 50(17) ºC X
TC257
TC258
Any 1 > 860 ºC X X
TC259
TC260
880 X X
Any 2 FAULT- PV SIGNAL X X
Any mBar
Turbine Burner Dynamic Pressure PT200
Band
> 70
(rms) X
103 X X
- FAULT- PV SIGNAL(6) X X X
PT8 - FAULT- PV SIGNAL X
6074/C01/007 - Turbine Interduct / PT Exit TC1 to TC13 Any 1 > AVG + X(24) ºC X
< AVG - X(24) X
(24)
AVG - X -
30(26)
X
Any 2 Deviation/Fault - Adjacent X X
3 or
more
FAULT- PV SIGNAL X X
Avg > 570 ºC X
580(25) X
650 X
PT259 - SIGNAL DRIFT X
Notes
1 Trip if already stopped / shutdown. If starting / running, TRL after 10s, DML after 30 minutes. DML immediately if TRL disabled, Trip if DML disabled.
3 Start inhibit unless engine starting or running in which case get warning followed 1 hour later by trip if condition persists
6 One hour delay on trip
26 Very low deviation limit - thermocouple is removed from the mean calculation.
27 If a disparity (see ∆) between the two readings exists then the lower value is used. If one probe fails then value from healthy probe is used.
28 Turbine running. Warning after inverse time delay of 100ºC.seconds. Trip after inverse time delay of 1200ºC.seconds.
29 Warning after inverse time delay of 500ºC.seconds. Slow unload after inverse time delay of 1200ºC.seconds. Trip after inverse time delay of 1500ºC.seconds.

Gas path Page 14


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

6074/C01/031 - Hydrocarbon drain tank LT45 - > 80(2) Litres

120 X
160(1)(9) X X
DEVICE FAULT(1)(11) X X
- Turbine underbase LT46 - > 60 mm X
100(3)(4) X X
DEVICE FAULT(3) X X
ZS955
- SOL601 Auto drain valve
ZS956
- FAULT - NOT OPEN(5) X X
FAULT - NOT CLOSED X
- Instrument air supply PT185 - > 7.5 BarG X
< 3.1(7) X X
4(8) X
5(8) X
FAULT - PV SIGNAL X X
- Labyrinth seal PT172 - > 0.14(14) BarG X
< 0.21(10)(16) X
0.14(16) X X X
CIRCUIT FAULT(17) X X X X
Notes
1 Start inhibit applied only if liquid fuel is selected
2 Prevents an offline or online wash/rinse being initiated
3 Start inhibit applied only if liquid fuel is fitted
4 Prevents an offline wash/rinse being initiated
5 Warning when offline wash or rinse not active AND the turbine is spinning or is not active. Trip enabled on not closed fault or offline washing or rinsing
7 Only enabled when air purge is on
8 Only enabled when air purge is off
9 Aborts an offline wash/rinse
10 Aborts an offline wash/rinse after 30s or immediately if fluid release in progress
11 Prevents an offline wash/rinse being initiated until operator confirms drains tank is empty
14 Monitoring enabled when turbine is stopped and lab seal air is not required
16 Monitoring enabled when seal air is required
17 Trip enabled if instrument air is required

031 Auxiliaries Page 15


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

PDS11
6074/C01/018 TH9 Generator cooling air flow
PDS13
- DIFFERENTIAL HIGH X
- Generator phase 'U' winding RTD25 - > Note 4 °C X
Note 4 X
Note 4 X
- Generator phase 'V' winding RTD27 - > Note 4 °C X
Note 4 X
Note 4 X
- Generator phase 'W' winding RTD29 - > Note 4 °C X
Note 4 X
Note 4 X
- Generator cooling air inlet RTD39 1oo2 > Note 4 °C X
RTD44 Note 4 X
Note 2
Note 4 X
- Generator cooling air outlet RTD40 - > Note 4 °C X
Note 4 X
Note 4 X

Generator cooling air inlet to outlet


RTD39 - Note 4 X
temperature difference
RTD44 Note 4 X
RTD40 Note 4 X

018 Generator Page 16


Pegaga SGT300-1S Cause and Effects

EFFECT

Shutdown Spin Disabled


Trip To Minimum Load
Trip To Reduced Load

Unit Tripped
Start Inhibit

Trip To Idle
Start Hold
Warning
CAUSE
P&ID Item or Location Signal(s) Vote Limit

- - Generator control panel GCP3 - COMMON FAULT X X


- - Excitation GCP4 - TRIP TO MANUAL X
- - Generator rotor GCP7 - ROTOR EARTH FAULT X
- - Generator high voltage switchgear GCP14 - EARTHED X
Synchronisation GCP48 - FAILED X
Generator protection relay GCP132 - HV TRIP CIRCUIT FAULT X
Generator circuit breaker GCP429 DISCREPANCY X
- - Generator circuit breaker MCB1 - CLOSED X
6074/C01/018 - Generator driven end bearing RTD23 - > Note 4 °C X
Note 4 X
Note 2
Note 4 X
UD51X1
UD51Y1
1oo2 > 66(5) µm pp X
85 X
90(5) X X
- Generator non driven end bearing RTD24 - > Note 4 °C X
Note 4 X
Note 2
Note 4 X
UD52X1
UD52Y1
1oo2 > 66(5) µm pp X
85 X
90(5) X X
- Gearbox casing UD39 - AC > 140 m/s² X
VL > 2.5(3) mm/s X
4(3) X X
Notes
2 Trip only enabled when turbine is passed start hold 2
3 For all engines except SGT-400, during a start level is multiplied by 3 until 60 seconds after passing min gov
4 Contract specific level
5 For generators with a flexible rotor, during a start level is multiplied by 1.5 until 60 seconds after passing min gov

018 Generator Page 17