SERVICEABILITY
7-1 Introduction 7-6 Procedure for 7-8 Deflection Control
‘ Calculating the Deflection Measures in Reinforced
7-2 Deflections of Simply Supported Conerete Structures
7-8 Calculation of ler fend Contnuaie Beane 7-9 Crack Control
7-4 Immediate
Deflection 7-7 Procedure for Calculating | 710 Floor Vibrations
the Deflection of 7-11 Gross and Cracked Section
7-5 Long-Term Continuous Girders Properties of Concrete
Deflection Sections
7-1 INTRODUCTION to be more stringent than those given in ACI Code
The ACI Code requires that bending members have
structural strength adequate to support the antici-
pated factored design loads (ACI Code Sections 4.4.4
and 4.6) and that they have adequate performance at
service load levels (ACI Code Section 4.7). Adequate
performance, or serviceability, relates to deflections and
‘racking in reinforced concrete beams and slabs. It is
important to realize that serviceability is to be assured
at service load levels, not at ultimate strength. At ser-
vice loads, deflections should be held to specified
limits because of many considerations, among which
are aesthetics, effects on nonstructural elements such,
as windows and partitions, undesirable vibrations,
and proper functioning of roof drainage systems.
Any cracking should be limited to hairline cracks for
reasons of appearance and to ensure protection of
reinforcement against corrosion.
7-2 DEFLECTIONS
‘The deflection of concrete flexural members is affected
by the following factors: the magnitude and distri-
bution of the load on the member; the span of the
member and support conditions; the percentage of
reinforcement; member section properties; properties
of the concrete material; and the degree and extent
of flexural cracking in the member. Guidelines for
the contzol of deflections are found in the ACI Code,
Section 24.2. In addition, Table 242.2 of the Code indi-
‘ates the maximum permissible deflections. Note that
the permissible live load deflections for spandrel or
edge beams supporting exterior cladding may need
Table 2422, depending on the span of the beam
and the performance requirements of the exterior
cladding. A specific live load deflection limit of say
3/8-inch for spandrel beams regardless of the span
is recommended to ensure adequate performance
of the cladding [4]. For the purpose of following the
Code guidelines, either of two methods may be used:
(@) using the minimum thickness (or depth of mem-
ber) criteria as established in Tables 7.3.1.1 and 9.3.1.1
of the Code, which will result in sections that are suf-
ficiently deep and stiff so that deflections will not be
‘excessive; and (2) calculating expected deflections
using standard deflection formulas in combination
with the Code provisions for moment of inertia and
the effects of the load /time history of the member.
‘Minimum thickness (depth) guidelines are simple
and direct and should be used whenever possible.
Note that the tabulated minimum thicknesses apply
to non-prestressed, one-way members that do not sup
port and are not attached to partitions or other con-
struction likely to be damaged by large deflections.
For members not within these guidelines, deflections
‘must be calculated.
For the second method, in which deflections are
calculated, the ACI Code stipulates that the members
should have their deflections checked at service load
levels. Therefore, the properties at service load levels
must be used. Under service loads, concrete flexural
members still exhibit generally elastic-type behavior
(Gee Figure 1-1) but will have been subjected to crack-
ing in tension zones at any point where the applied
moment is large enough to produce tensile stress in
‘excess of concrete tensile strength. The cross section
183