Serviceabi 193,
5. For an office building, the percentage of live load sus-
tained can be assumed to be approximately 25%,
Therefore, a = 0.25
For long-term deflections, use the creep factor after,
5 years, therefore, £ = 2.0. Since there is no compres
sion steel, p’ = 0, the long-term deflection muttiplier
's
é )- 20
= (Fm) = ang = 29
The total long-term deflection (which excludes the
instantaneous dead load deflection) is calculated as
Arr = Au + Sir
ut Ag(Bou + edu)
16" + 2.0(0.43" + 0.25[0.16"]) = 1.1"
This long-term deflection as well as the instantaneous
live load deflection will now be compared to the ACI
Code deflection limits (ACI 318-14, Table 24.2.2).
fa. For root and floor flexural members not support-
ing deflection sensitive olements, Ary = 1.1"
e281) pee
must be = 6 = 22) — 4.45")
. For roof and floor flexural members support-
Ing deflection sensitive elements, Arr = 1.1"
29(12)
t ‘|
must be = 355 = “gag” = 0.73" (Not Good)
C. For roof and floor flexural members not support-
ing deflection sensitive elements, Ay. = 0.16"
must be = 5 = 7202) _ 193°)
480 ~ 180
. For roof and floor flexural members support-
ing deflection sensitive elements, Ay = 0.16"
must be = 5 = 2202) - 973° 0)
480” 480
‘The deflection in the end span of this continuous beam
satisfies all the ACI Code deflection limits except the
second limit. To reduce the long-term deflections, we
could add compression steel to the beam at the mid
span and recalculate the long-term deflection.
‘Assume d#8 bars are added atthe top of the beam at
‘midspan, thereforethe compression reinforcement ratio,
As _ 3.16 in? _
bad ~ Haryiesy ~ 2118
‘The revised long-term multiplier is
o
r ( é ) 20
(4 sop") ~ 7+ 50(0.0176)
There is a reduction of the long-term multiplier from
2.0 (without compression steel) to 1.27 with compres-
sion steel. To prevent buckling ofthe reinforcement, the
‘compression steel will have to be confined with stierups
in accordance with ACI Code, Section 25.7.2.
With compression steel, the long-term deflection
(excluding the instantaneous dead load deflection is,
Arr = 0.16" + 1.27(0.49" + 0.25(0.16")) = 0.76"
‘The revised long-term deflection still slightly exceeds the
‘ACI Code limit if deflection sensitive elements are sup-
ported by the beam, but tis only about 4% over the limit,
and in practice this small excess deflection (0.03 in) can
bbe ignored,
7-8 DEFLECTION
CONTROL MEASURES
IN REINFORCED
CONCRETE STRUCTURES
‘There are several ways for controlling deflections in
reinforced concrete flexural members, and some are
feasible during the design phase and others are carried
out during the construction phase. The control mea-
sures include the following:
‘+ Add compression steel to the beam, but the com-
pression steel has to be tied with closed stirrups
to prevent buckling, and the tie spacing must con-
form with ACI 318-14, Section 257.2. Note that
compression steel cannot be used to control deflec-
tions in slabs since the compression bars cannot be
confined. The advantageous effect of compression
steel in reducing long-term deflections is reflected
by the compression rebar ratio, p’, being in the de-
nominator of the equation for the long-term deflec-
tion multiplier, As in Section 7-5.
+ Provide additional tension reinforcement which
increases the cracked moment of inertia, lex
which in tun leads to a higher effective moment
of inertia, Ie
‘+ Increase the slab thickness and the beam depth,
Increasing the width of a beam is not as effective
as increasing the beam depth in achieving an in-
crease in the effective moment of inertia.
+ To reduce the impact of incremental long-term
deflections, the installation of the DSEs should be
delayed to allow a significant proportion of the
creep deflection of the member to occur prior to
the installation.
‘+ Deflections can also be controlled through the fol-
lowing construction practices
‘+ Donot load the concrete structure until it reach-
¢s its design strength.
* Provide adequate shoring to the concrete
‘member during construction until it reaches its,
design strength.
‘+ Ensure that the reinforcement in the concrete
‘member is not displaced or misplaced during,
the concrete pour:194 CHAPTER SEVEN
7-9 CRACK CONTROL
With the advent of higher-strength reinforcing steels,
where more strain is required to produce the higher
stresses, cracking of reinforced concrete flexural
members has become more troublesome. Some of the
reasons why crack control is necessary include aes-
thetics considerations and the need to avoid the per-
ception in the public's mind that the structure is in
imminent danger of collapse due to the presence of
noticeable cracks,
It seems logical that cracking would have an
effect on corrosion of the reinforcing steel. However,
there is no clear correlation between corrosion and
surface crack widths in the usual range found in struc-
tures with reinforcement stresses at service load lev-
cls. Further, there is no clear experimental evidence
available regarding the crack width beyond which
2 corrosion danger exists. Exposure tests indicate that
concrete quality, adequate consolidation, and ample
concrete cover may be more important in corrosion con-
siderations than is crack width.
Rather than a small number of large cracks, itis
more desirable to have only hairline cracks and to
accept more numerous cracks, if necessary. To achieve
this, the current ACI Code (Section 24.3) directs that
the flexural tension reinforcement be well distributed
in the maximum tension zones of a member. ACI
Code Section 24.3.2 contains a provision for maximum
spacing s that is intended to control surface cracks to
a width that is generally acceptable in practice. The
maximum spacing (see ACI Code Table 24.32) is
limited to
os, = 2( $2)
fe
where
5 = center-to-center spacing of flexural tension
reinforcement nearest to the tension face, in.
{f= calculated stress, psi. This may be taken as 3
of the specified yield strength.
¢. = clear cover from the nearest surface in
tension to the surface of the flexural tension
reinforcement, in.
ACI 318, Section 24.35, cautions that if a structure is
designed to be watertight or if itis to be subjected to
very aggressive exposure, the provisions of Section
243.2 are not sufficient and special investigations and
precautions are required.
Example 7-4
‘Check the steel distribution for the beam shown in
Figure 7-9 to establish whether reasonable control of flexural
‘cracking is accomplished in accordance with the ACI Code,
Section 24,3, Use f, = 60,000 psi. Assume d = 30 it
| —'5 stirrup
clear (yp.) —-}
reat
ie a
FIGURE 7-9 Sketch for Example 7-3.
Solution:
49
1. Calculate the centro-conter spacing between the
No.9 bars
1
18 ~ 2(18) ~ 2(0878) - o{ 8)
ee ET sat,
2. Assume postive moment and calculate the eoncreta
clear cover from the bottom (tension) face of the beam
foi surface of the nearest onsionrlforcoment
c= 18 + 0375 = 1.875in
2. Calulate fusing off:
4<3
8
4, Calculate maximum spacing allowed for deformed bars
using ACI Code Table 24.3.2:
19(220) 25
= 1031 in,
Check the upper limit of the equation for deformed
bars from ACI Code Table 24.3.
1290) «1 1229) -sain.> oats (0X)
= 2(¢0,000) = 40,000 pi
) = 2.611.875)
40,000,
‘And lastly:
887 in. <10.31in. (O.K.)
When beams are relatively deep, there exists the
possibility for surface cracking in the tension zone areas
away from the main reinforcing. ACI 318-14, Section
9.7.23, requires, for beams having, depths ft in excess of
36 in, the placing of longitudinal skin reinforcing along
bboth side faces for a distance h/2 from the tension face
of the beam, The spacing s between these longitudinal
bbars or wires shall not exceed the spacing as provided in
ACI3I8-14, Table 24.3.2. Bar sizes ranging from No. 3 to
No. 5 (or welded wire reinforcement with a minimum
area of 0.1 in. per foot of depth) are typically used.
Example 7-5
Select skin reinforcement for the cross section shown in
Figure 7-10a. Flexural tension reinforcement is 5 No. 9 bars,
and f, = 60,000 psi