Professional Documents
Culture Documents
SiemensFirefinderXLS DeviceLoopCard (DLC) PDF
SiemensFirefinderXLS DeviceLoopCard (DLC) PDF
Model DLC
Device Loop Card
INTRODUCTION The SIEMENS Model DLC Device Loop Card is the interface
DLC
for connection of FireFinder-XLS smoke detectors, manual
stations, monitor devices, and control devices to the RESET
ZONES STATUS
Ground fault detection is provided by loop. Z
O CLASS A OPEN
N
CLASS A RETURN
All field devices connected to the DLC are addressed and E
1 SHORT
tested using the Device Programming Unit (DPU). Z CLASS A OPEN
O
N CLASS A RETURN
E
SHORT
2
HNET
controls the on-board isolator to isolate either zone from the
loop if one of them is shorted. When one zone is isolated
from the loop, the other zone will still work.
The LEDs follow the reset switch and their functions are defined as follows:
A three-position switch at the bottom of the front panel is used to set the HNET
network address of the DLC. All field devices connected to the DLC are addressed
and tested using the Device Programming Unit (DPU). Refer to the DPU Manual,
P/N 315-033260 for further information.
INSTALLATION The DLC plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin DIN
connectors and can occupy any slot in the card cage.
(Refer to Figure 2.)
Verify that the DIN connectors of the card and the card-
cage aligned properly. The card can only plug in one
direction to the card cage, if it does not align, DO NOT
FORCE the card.
WIRING
All field wiring to the DLC is connected to the terminal blocks of the CC-5 card cage
slot in which it is installed.
Connect +24V from the PSC-12 to terminal 17 and -24V from the PSC-12 to terminal
18 of the slot in the CC-5 where the DLC will be installed. (Refer to Figure 3.)
LINE 2 (RETURN)
LINE 2 (RETURN)
LINE 1 (RETURN)
LINE 1 (RETURN)
LINE 1 (OUT)
LINE 1 (OUT)
LINE 2 (OUT)
LINE 2 (OUT)
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
DO NOT USE
17 18 19 20 21 22 23 24
24V+ 24V-
DO NOT USE
Figure 3
Wiring The 24VDC Power Lines To The DLC Slot In The CC-5
INITIATING
DEVICE
INITIATING
DEVICE
LINE 1 (RETURN)
LINE 1 (RETURN)
LINE 2 (RETURN)
LINE 2 (RETURN)
LINE 2 (OUT)
LINE 2 (OUT)
LINE 1 (OUT)
LINE 1 (OUT)
NOT USED
NOT USED
NOT USED
NOT USED
LINE 1
LINE 1
LINE 2
LINE 2
CC-5 CC-5
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16
*OPERATES IN FULL CONFORMANCE WITH STYLE 6 **OPERATES IN FULL CONFORMANCE WITH STYLE 4
NOTES:
1. NO END OF LINE DEVICE REQUIRED.
2. BOTH CIRCUITS SUPERVISED AND POWER LIMITED PER NEC 760.
Figure 4
DLC Wiring Diagram
Electrical connections for the two zones are shown in Figure 4. The wiring style is set
in the Zeus Programming Tool without using external jumpers. Once the wiring style
is set, both zones will be set to the same style.
COMPATIBILITY 1. The DLC supports only FireFinder-XLS intelligent devices. The compatibility
identifiers for the compatible devices are the model numbers listed in Table 1.
TABLE 1 Use any combination of those listed.
DLC Compatible Devices
Compatible Installation 2. The DLC supports one loop (with 2 isolated zones) of up to 252 FireFinder-
Devices Instructions XLS intelligent field devices. Up to 252 devices can be distributed in either
AD-11P P/N 315-095659-9 zone, but the total number is limited. For example, if 100 devices are in Zone
ADBH-11 P/N 315-033210-3
AD-HR P/N 315-033280-3 1, then the number of the devices in Zone 2 must be 152 or less.
DB-11 P/N 315-094193-7
DB-HR P/N 315-033220-2
3. All circuits are power limited to NFPA 70 per NEC 760. The DLC supports
HFP-11 P/N 315-033290-3 the use of 18 AWG min non-shielded, non-twisted, thermoplastic fixture
HFPT-11 P/N 315-033290-3
HLIM P/N 315-033170-2 wire without conduit, if permitted by local building codes.
HMS-2S P/N 315-033430-2
HMS-M P/N 315-033450-2
4. No end of line device is required.
HMS-S P/N 315-033200-2
HMS-SA P/N 315-033430-2
5. Total circuit resistance of each zone must not exceed 50 ohms when 252
HMS-D P/N 315-033200-2 devices are loaded into one zone. (Refer to the chart on page 6.)
HTRI-D P/N 315-033300-2
HTRI-M P/N 315-034000-2 Maximum capacitance: 0.5µF between line+ and line-
HTRI-R P/N 315-033300-2
HTRI-S P/N 315-033300-2 1.0µF between line and chassis
HZM P/N 315-034850-2
ILED-HC P/N 315-048637-1 6. T-tapping is not allowed on Class A loops.
ILED-HW P/N 315-048637-1
RL-HC P/N 315-033230-2
RL-HW P/N 315-033230-2
ELECTRICAL RATINGS
24V Back Plane Current 0
250
240
230
220
210
200
190
Line Resistance (ohm)
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260
Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. Siemens Gebäudesicherheit
8 Fernwood Road 2 Kenview Boulevard GmbH & Co. oHG
Florham Park, New Jersey 07932 Brampton, Ontario L6T 5E4 CN D-80930 München
P/N 315-033090-5