Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO.

3, JULY 2003 1079

Review of Harmonic Load Flow Formulations


Sergio Herraiz, Luis Sainz, and Jordi Clua

Abstract—This paper is a review of the different single and During EPS operation, three-phase voltage at terminals of the
three-phase harmonic load flow formulations of the bibliography. loads is expected to be symmetric; for this reason, the harmonic
It presents the data, unknowns, and equations of these formu- load flow problem study, in balanced conditions, was the ha-
lations in balanced network consideration. The influence of the
main harmonic load flow hypothesis (harmonic interaction and bitual procedure, but a more accurate harmonic load flow study
fundamental power consumption consideration) in the final load must consider the network unbalanced conditions.
flow results is studied in an example. The great number of unknowns to solve in the harmonic
Index Terms—Harmonic interaction, network harmonics, power studies leads authors to tackle the problem in several ways
flow studies. in order to reach a compromise between the simplicity and
reliability of the formulation.
The simplest way assumes no harmonic interaction between
NOMENCLATURE network and nonlinear devices [3], [7], [8].
EPS Electric power system. The well-known iterative harmonic analysis is the first mod-
CLF Conventional load flow. ification when considering harmonic voltage influence on the
NR Newton–Raphson. nonlinear device behavior [4], [5], [9]–[12]. There are other
NLD Nonlinear device. studies that aim to improve convergence in the iterative har-
HP Harmonic penetration. monic analysis [13]–[17].
CLF Conventional load flow (modified). A limitation of the method mentioned before is that the fun-
VN Voltage nodes method. damental voltages are assumed to be unaffected by harmonic
IHP Iterative harmonic penetration. voltages; therefore, other formulations are developed to solve
IHA Iterative harmonic analysis. this problem [18]–[21].
GS Gauss–Seidel. Originally, reformulations of the conventional load flow in
SHLF Simplified harmonic load flow. order to include nonlinear devices on it were implemented
HA: Harmonic analysis. [22]–[24]. This formulation is a natural modification of the load
CHLF Complete harmonic load flow (fundamental). flow where the nonlinear device treatment and the harmonic
CHLF Complete harmonic load flow (harmonic). voltage calculation have been included [25]. In this way, it can
NL1 Nonlinear load 1 (6-p ac/dc converter). be assumed that fundamental and harmonic voltages produce
NL2 Nonlinear load 2 (three-phase uncontrolled recti- power consumption.
fier). A comparison between the last two formulations was ana-
lyzed in [26].
I. INTRODUCTION The paper provides a bibliography review of the above formu-
lations under balanced and unbalanced conditions developing
L OAD flow is the procedure used for obtaining the steady
state voltages of electric power systems (EPS) at funda-
mental frequency. Much effort has been expended in research
the data, unknowns, and constraint equations in the balanced
harmonic problem.
An example to show the influence of the harmonic interaction
and development of the formulation of this problem in the bib-
and fundamental power consideration in the final results is also
liography [1]–[4].
analyzed.
In the last few years, there has been a growing interest in
obtaining steady state network voltages at harmonic frequen-
cies due to the increase of nonlinear devices in electric power II. CONVENTIONAL LOAD FLOW
networks. The procedures for analyzing the harmonic problem
could be classified into frequency domain [3]–[5] and time do- Steady state network voltage calculation at fundamental fre-
main [6]. Frequency domain methods are the most widely used quency from the constraints on power and/or voltage is essen-
for the harmonic problem formulation. They are a reformulation tial to determine the static operating condition of an EPS. This
of the conventional load flow in order to include the nonlinear method is known as conventional load flow (CLF).
device treatment and the calculation of harmonic voltages. The CLF is performed in power-system planning, operational
planning, and operation/control; therefore, it has been studied in
the bibliography widely [1]–[4].
Manuscript received December 7, 2001. The resolution of the CLF aims to obtain the fundamental bus
The authors are with the Department of Electrical Engineering (Barcelona voltages of network from generation and load (slack, PV, and PQ
Division) of the Universitat Politècnica de Catalunya, Barcelona 08028, Spain
(e-mail: herraiz@ee.upc.es; sainz@ee.upc.es; jordi.clua@upc.es). buses). The data and unknown variables for a bus system are
Digital Object Identifier 10.1109/TPWRD.2003.813604 summarized in Table I.
0885-8977/03$17.00 © 2003 IEEE

Authorized licensed use limited to: Yonsei Univ. Downloaded on April 28,2020 at 08:08:30 UTC from IEEE Xplore. Restrictions apply.
1080 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 3, JULY 2003

TABLE I
CLF FORMULATION

The PV bus constraints are

(1)
The PQ bus constraints are
Fig. 1. HP flowchart.

(2) TABLE II
HP FORMULATION

where is the element of network fundamental admittance


matrix .
The numerical resolution of the above set of nonlinear equa-
tions provides us with the unknown variables. The algorithm of
Newton–Raphson (NR) being the most generally used proce-
dure in the bibliography.

III. HARMONIC LOAD FLOW


The “recent” appearance of nonlinear devices (NLD) in the This fact leads authors to tackle the harmonic problem in the
EPS provoked harmonic distortion in the network voltages. frequency domain in several ways in order to reach a compro-
This fact and the increasing number of applications with NLD mise between the simplicity and reliability of the formulation.
has led us to analyze the steady state harmonic problem. CLF
must be replaced to calculate A. Harmonic Penetration
• the fundamental bus voltages; The first and simplest method is harmonic penetration (HP)
• the harmonic bus voltages; [Fig. 1], which assumes no harmonic interaction between net-
• the parameters which characterize the NLD state. work and NLD (i.e., it considers that harmonic voltages have no
starting from CLF and NLD behavior data. influence on the NLD behavior [3], [7], [8]). This consideration
The procedures used for analyzing the harmonic problem is extended to the power definition (i.e., ).
could be classified into two groups: time domain methods and The no interaction hypothesis allows the NLD treatment to
frequency domain methods. be approached considering the fundamental voltages and NLD
There are hybrid methods too. They work in both domains to data dependence, thus facilitating their incorporation to the
benefit from the advantages of each one of them. CLF. Once the fundamental steady state network and the NLD
Time domain methods, such as the EMTP [6], are based on behavior are characterized with the modified CLF (CLF , the
the numerical resolution of the differential equations that rep- harmonic voltages can be calculated with the voltage nodes
resent the system behavior. These methods are very useful for method (VN).
the NLD treatment but the calculation effort necessary to reach The HP data and unknown variables for an bus system are
the steady state solution could be considerable and they do not summarized in Table II, where
allow the inclusion of power consumption in the definition of • and with are generic NLD data and
the problem. parameters, respectively;
Frequency domain methods are a reformulation of CLF, • and with are the reactances of the slack
which includes NLD. They are the most widely used methods and PV bus generators at fundamental frequency.
for the harmonic problem resolution [3]–[5]. CLF is based on the simultaneous resolution of the PV bus
First, a nonlinear set of equations must be outlined to obtain and PQ bus constraint (1) and (2) with the expression (2) ap-
the unknown variables as in CLF. plied to the NLD buses and the expressions that define the NLD
The resolution of these equations could present several dif- behavior
ficulties such as long execution time, numerical convergence
problems, and considerable PC-memory effort due to the ele-
vated number of unknowns. (3)

Authorized licensed use limited to: Yonsei Univ. Downloaded on April 28,2020 at 08:08:30 UTC from IEEE Xplore. Restrictions apply.
HERRAIZ et al.: REVIEW OF HARMONIC LOAD FLOW FORMULATIONS 1081

The current consumed by the NLD can be calculated as a


function, which depends on the fundamental bus voltage and
the NLD parameters

(4)

thus allowing the NLD consumed power and


the harmonic currents injected by the NLD with
to be obtained.
Finally, the PQ load admittances can be determined from the
CFL solution too

Fig. 2. IHP flowchart.


(5)
TABLE III
where is a function which depends on the harmonic admit- IHP FORMULATION
tance model [7], [8], [25].
The expressions (3)–(5) depend on the fundamental voltages
only because of the hypotheses of no harmonic voltage influence
on power consumption and NLD behavior.
The VN is based on the resolution of the linear system cor-
responding to current continuity expression
for the harmonic frequencies . The VN must be
completed by incorporating NLD injected currents to bus cur-
rent vector , and the load and generator harmonic admittances
to network admittance matrix .
This formulation allows the harmonic problem to be tackled
in a way as simple as CLF but NLD sensitiveness to harmonic
voltages results in an overestimation of their polluting effect.
Therefore, the need to study the problem in a more accu- same structure but the VN method is complemented by iterative
rate way leads us to consider harmonic interaction between net- harmonic analysis (IHA) in IHP (Fig. 2).
work and NLD and to develop a new set of formulations. These In IHA, the ac linear network is reduced to the NLD buses
methods still take into consideration the fundamental wave de- from the CLF solution and voltage pollution and NLD be-
pendence of the power definition. havior are solved by considering NLD harmonic voltage depen-
At present, the majority of harmonic load flow formulations dence. Therefore, the aim of the IHA application is to calculate
are based on both considerations: NLD harmonic voltages as VN and correct the CLF solution
• Harmonic interaction: The expressions (3) and (4) which (i.e., NLD parameters) considering the harmonic influence. For
characterize the NLD behavior and consumed harmonic this reason, IHA must be an iterative procedure between NLD
currents , must be modified to reflect har- harmonic voltages and obtaining the parameters.
monic voltage dependence The IHP data and unknown variables for an bus system are
summarized in Table III.
The CLF is the same as in HP and provides fundamental
(6) voltages and NLD parameters considering no harmonic interac-
tion.
Once the CLF solution is reached, the PV loads are replaced
(7) by their reactances, and the conventional PQ loads by their im-
pedances, (5), in the same way as in HP. The passive harmonic
• Fundamental power: It allows to calculate the load admit- characteristic of generators and PQ loads and the fundamental
tances by expression (5), which decouples the CLF so- power hypothesis allow to be calculated and incorporated into
lution and harmonic interaction holding the HP original network admittance matrix , building matrix .
idea. Subsequently, the system is reduced to NLD buses (Fig. 4) by
Gaussian elimination of the modified admittance matrix “linear”
B. Iterative Harmonic Penetration elements, thus obtaining matrix . This procedure allows
Iterative harmonic penetration (IHP) is the first modification the study to be reduced to buses with NLD .
from the HP which takes into consideration harmonic influence The IHA obtains the unknowns by solving linear system
on NLD behavior [4], [5], [9]–[12]. Both algorithms have the with the Gauss–Seidel algorithm (GS). That

Authorized licensed use limited to: Yonsei Univ. Downloaded on April 28,2020 at 08:08:30 UTC from IEEE Xplore. Restrictions apply.
1082 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 3, JULY 2003

is to say, assuming constant fundamental voltages at each


iteration , the last values of the harmonic voltages ( are
used to update NLD state ( with , (6) and the
injected currents (7)

(8)

The currents are then used to derive the ac voltage harmonics


for the following iteration:

Fig. 3. SHLF flowchart.


(9)

Once the NLD behavior is characterized and their injected


currents are known, VN is applied to obtain the harmonic volt-
ages of linear buses .
The fixed-point iteration technique, GS, used in the IHP
could present convergence problems which different authors
have tried to solve [13], [14]. Nevertheless, the best con-
vergence has been obtained by linearizing the interaction
between the ac and the dc systems. This linearization has been
performed by NLD Norton equivalents [15], [23], [24] and by
the ABCD parameters model [16], [17].
The general limitation of IHP, however, is that CLF condi-
tions (fundamental bus voltages) are assumed to be constant in
IHA (i.e., the CLF solution is assumed to be unaffected by the
introduction of harmonics).
In this way, iterative techniques between both formulations
are therefore necessary to solve the harmonic problem [18],
[19].

C. Simplified Harmonic Load Flow


The above idea is developed and improved in the simplified
harmonic load flow (SHLF) [20], [21]. A fixed-point iteration
of two NR procedures is used: one for CLF and the other for
harmonic analysis (HA) [Fig. 3].
This GS algorithm has two steps that are executed succes-
sively. The first step is the typical CLF in which NLD are in-
cluded as PQ loads. In the second step, HA, the ac linear net- Fig. 4. IHA procedure (h = 3; 5; . . .).
work, is reduced to the NLD buses from the CLF solution as
in IHP and voltage pollution and NLD behavior are solved by • NR numerical method: The HA equations are solved by
taking into consideration NLD harmonic voltage dependence. NR method. It implies the set of equations more complex
There are two important differences between HA and IHA. but process convergence is much better.
• Fundamental voltages consideration: The procedure cor- The SHLF data and unknown variables for an bus system
rects not only harmonic voltages and NLD parameters are summarized in Table IV.
but also fundamental voltages. Then, the convergence of In CLF, the NLD are considered known current sources in
CLF and HA is checked by comparing their fundamental order to calculate their consumed power as .
voltage solutions. Their fundamental currents are determined by (7).

Authorized licensed use limited to: Yonsei Univ. Downloaded on April 28,2020 at 08:08:30 UTC from IEEE Xplore. Restrictions apply.
HERRAIZ et al.: REVIEW OF HARMONIC LOAD FLOW FORMULATIONS 1083

TABLE IV voltage calculation have been included [25]. It is based on the


SHLF FORMULATION simultaneous resolution of power constraints, harmonic current
balance, and NLD equations.
This formulation allows the problem to be tackled as a unique
set of nonlinear equations the numerical resolution of which
provides the unknowns although their number increases when
the harmonic voltages at linear buses are included.
Moreover, this formulation allows the power consumption to
be considered depending on the harmonic and fundamental volt-
ages

(12)

since the ac system reduction is not necessary.


In HA, the ac linear network is represented by a generalized Hence, there exist two possible formulations [25]:
Thevenin equivalent with respect to the NLD buses, obtained
• Complete harmonic load flow considering the power at
from the CLF solution
fundamental frequency (CHLF ).
• Complete harmonic load flow considering the power at
fundamental and harmonic frequency (CHLF ).
The CHLF data and unknown variables for an bus system
are summarized in Table V.
The set of nonlinear equations used to solve the problem is
(10) • The PV bus constraints

Previously, matrix will be built as in IHP thanks to the pas-


sive harmonic characteristic of the generators and PQ loads and
the fundamental power hypothesis (Fig. 5). Note that Thevenin
voltages are equal to zero for since there are not harmonic (13)
generators.
The nonlinear set of equations based on the Thevenin equiv-
alent must be outlined to obtain the unknown variables. • The PQ bus constraints
The voltage constraints are
(14)

(11) • The balance of harmonic currents at linear buses

where is the NLD injected current calculated by expression


(7).
And the expressions which define the NLD behavior, (6). (15)
Once the NLD behavior is characterized and their injected where are the harmonic admittances of generators
currents are known, VN is applied to obtain the harmonic volt- and PQ loads. Load admittances can be calculated by (5)
ages of linear buses . thanks to the fundamental frequency power consideration.
It is observed that SHLF follows to benefit of the power con- • The balance of harmonic currents at NLD buses is
sumption at fundamental frequency consideration in order to
apply the bus reduction in HA.
The GS algorithm could present convergence problems de-
pending on the degree of decoupling between the two NR pro- (16)
cedures CLF and HA [26]. This convergence could be improved where is the NLD injected current which can be calcu-
by the techniques proposed in IHP. lated by expression (7).
• The expressions which define the NLD behavior (6).
D. Complete Harmonic Load Flow The CHLF data and unknown variables for an bus system
Originally, a reformulation of the CLF in order to include are summarized in Table VI. The harmonic and fundamental
NLD was implemented [22]. This formulation is a natural mod- power consideration leads to add the PQ fundamental admit-
ification of the CLF where the NLD treatment and the harmonic tances as unknowns because they cannot be calculated by (5).

Authorized licensed use limited to: Yonsei Univ. Downloaded on April 28,2020 at 08:08:30 UTC from IEEE Xplore. Restrictions apply.
1084 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 3, JULY 2003

Fig. 5. HA procedure (k = 1; 3; 5; . . . and h = 3; 5; . . . ).

TABLE V TABLE VI
CHLF FORMULATION CHLF FORMULATION

• The PQ bus constraints

The set of nonlinear equations used to solve the problem is


• The PV bus constraints (18)
• The balance of harmonic currents at linear and nonlinear
buses (15) and (16).
• The expressions which define the NLD behavior (6).
• The relationships between the PQ load and their admit-
tances
(17) (19)

Authorized licensed use limited to: Yonsei Univ. Downloaded on April 28,2020 at 08:08:30 UTC from IEEE Xplore. Restrictions apply.
HERRAIZ et al.: REVIEW OF HARMONIC LOAD FLOW FORMULATIONS 1085

TABLE VII
DATA AND UNKNOWNS OF THE EXAMPLE

Fig. 6. Studied system.

where . These relationships must be


included in the set of nonlinear equations in order to obtain
fundamental admittance.
The numerical resolution of the CHLF and CHLF set of
nonlinear equations provides us with the unknown variables, NR
being the most generally used procedure in the bibliography.
Further, other complete formulation based on the NLD
Norton equivalents and the separate NR resolution for each
harmonic was proposed in [23], [24]. • HP: A nonlinear system with eight unknowns and a linear
Recently, a study that compares and discusses about the con- system with six unknowns;
vergence properties of the decoupled method SHLF and the uni- • CHLF : A nonlinear system with 8 6 unknowns;
fied Newton method CHLF has been presented in [26]. Ac- • CHLF : A nonlinear system with 10 6 unknowns.
cording to this study, SHLF could present convergence prob- It can be noticed the considerable difference between the HP
lems owed to the GS technique and the CHLF is faster and formulation and the other two formulations owed to the nonin-
displays a more robust convergence. teraction hypothesis. In another way, the possibilities of calcu-
lating the fundamental admittance of the PQ-load according to
(5) (i.e., ), in the CHLF allows a
IV. EXAMPLE reduction of the number of unknowns with respect to CHLF .
The parameters of the six-pulse ac/dc converter are the ac
The example studies the two main hypotheses of the harmonic
short-circuit reactance , the dc side converter current ,
load flow formulations
which is assumed to be perfectly smooth, and the firing angle .
• consideration of the harmonic interaction between NLD The parameters of the three-phase uncontrolled rectifier are
and network; the ac short-circuit impedance , the
• consideration of the power consumption at fundamental dc capacitor , and the load .
frequency only. The unknowns of the single-phase converter are the zero
On this way, the three-bus system presented in Fig. 6 is solved crossing of the commutation voltage and the overlap angle
by three different formulations: of the ac line current. They are obtained from the commutating
• HP which considers no-harmonic interaction and power voltages and the ac line current condition.
consumption at fundamental frequency only; The unknowns of the three-phase uncontrolled rectifier are
• complete harmonic load flow considering the power at the commutation times and , which are obtained from the
fundamental frequency CHLF ; change conditions of the dc capacitor voltage and the ac line
• Complete harmonic load flow considering the power at current.
fundamental and harmonic frequencies CHLF . These constraints depend on the NLD parameters and the
The comparison between HP and CHLF results allows fundamental voltage in HP or the harmonic and fundamental
a study of the first hypothesis and the comparison between voltage in CHLF and CHLF .
CHLF and CHLF allows a study of the second hypothesis. The obtained results with HP and CHLF are compared in
The data and unknown variables of the studied system are Figs. 7–9. Figs. 7 and 8 show the harmonic distortion and the
summarized in Table VII for the three different formulations. total harmonic distortion of the nonlinear device currents. In
Considering , the number of harmonics in the system, the these figures, the nonlinear load parameters (zero crossing of
number of unknowns to obtain in the different formulations is the commutation voltage and overlap angle for the ac/dc

Authorized licensed use limited to: Yonsei Univ. Downloaded on April 28,2020 at 08:08:30 UTC from IEEE Xplore. Restrictions apply.
1086 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 3, JULY 2003

• The influence of harmonic interaction depends on the non-


linear load (i.e., three-phase uncontrolled rectifier is more
sensitive to the distortion than the ac/dc converter).
The results between CHLF and CHLF are quite similar.
It can be explained with the ratio of the load harmonic power
consumption to the load fundamental power consumption. The
small value of this ratio (i.e., 100( % for the 6p
ac/dc converter) indicates that the harmonic power consumption
is negligible in front of fundamental power consumption, and
the hypothesis of CHLF is acceptable.

V. CONCLUSIONS
The increase of nonlinear devices in power systems led us to
Fig. 7. Harmonics currents of the 6-p converter. consider their influence on conventional load flow studies. In the
same way, the authors tried to develop different formulations in
order to reach a compromise between simplicity and reliability.
A review of harmonic load flow formulations is presented in
this paper. Frequency domain procedures can be classified as
• No harmonic interaction

Harmonic Penetration (HP)


• Harmonic interaction

Fundamental power consideration


Iterative Harmonic Penetration (IHP)
Simpli ed Harmonic Load Flow (SHLF)
Complete Harmonic Load Flow CHLF
Harmonic and fundamental power consideration
Fig. 8. Harmonics currents of the three-phase rectifier.
Complete Harmonic Load Flow CHLF
A complete review of data, unknowns and equations is pre-
sented for the above formulations considering balanced sys-
tems.
The hypotheses of harmonic interaction and fundamental
power consumption are studied in an example to analyze their
influence in the load flow results.

REFERENCES
[1] B. Stott, “Review of load-flow calculation methods,” Proc. IEEE, vol.
62, no. 7, pp. 916–929, July 1974.
[2] A. Keyhani, “Evaluation of power flow techniques for personal com-
puters,” IEEE Trans. Power Syst., vol. 4, pp. 817–826, May 1991.
[3] G. T. Heydt, Electric Power Quality, 1991. Ed. Stars in a Circle Publi-
cations.
[4] J. Arrillaga and C. P. Arnold, Computer Analysis of Power Sys-
tems. New York: Wiley, 1990.
[5] J. Arrillaga, D. A. Bradley, and P. S. Bodger, Power System Har-
Fig. 9. Voltage harmonic distortion at bus 3. monics. New York: Wiley, 1983.
[6] H. W. Dommel, Electromagnetic Transients Programs—Reference
Manual. Portland, OR: EMTP Theory Book, 1986.
converter and the zero crossing of the current and for the [7] T. J. Densen, P. S. Bodger, and J. Arrillaga, “Three-phase transmission
three-phase uncontrolled rectifier) are also shown. Fig. 9 shows system for harmonic penetration studies,” IEEE Trans. Power Apparat.
Syst., vol. PAS-103, pp. 310–317, Feb. 1984.
the harmonic distortion and the total harmonic distortion of the [8] A. A. Mahmoud and R. D. Shultz, “A method for analyzing harmonic
voltage at bus 3. distribution in AC power systems,” IEEE Trans. Power Apparat. Syst.,
The above figures allow a study of the influence of the har- vol. PAS-101, pp. 1815–1824, June 1982.
[9] B. C. Smith, J. Arrillaga, A. R. Wood, and N. R. Watson, “A review
monic interaction in the results of the harmonic load flow. of iterative harmonic analysis for AC-DC power systems,” IEEE Trans.
• The consideration of no-harmonic interaction leads to Power Delivery, vol. 13, pp. 180–185, Jan. 1998.
[10] R. Yacamini and J. C. Oliveira, “Harmonics in multiple converter sys-
overestimating harmonic voltage and currents if the tems: A generalized approach,” Proc. Inst. Elect. Eng., pt. B, vol. 127,
harmonic distortion is high. no. 2, pp. 96–106, Mar. 1980.

Authorized licensed use limited to: Yonsei Univ. Downloaded on April 28,2020 at 08:08:30 UTC from IEEE Xplore. Restrictions apply.
HERRAIZ et al.: REVIEW OF HARMONIC LOAD FLOW FORMULATIONS 1087

[11] R. Yacamini and J. C. Oliveira, “Comprehensive calculation of converter [24] W. Xu, J. E. Drakos, Y. Mansour, and A. Chang, “A three-phase con-
harmonics with system impedances and control representation,” Proc. verter model for harmonic analysis of HVDC systems,” IEEE Trans.
Inst. Elect. Eng., pt. B, vol. 133, no. 2, pp. 95–102, Mar. 1986. Power Delivery, vol. 9, pp. 1724–1731, July 1994.
[12] J. P. Tamby and V. I. John, “Q’HARM—A harmonic powerflow program [25] L. Sainz, “Study of the harmonic load flow formulation and resolution,”
for small power systems,” IEEE Trans. Power Syst., vol. 3, pp. 949–955, Ph.D. dissertation (in Spanish), Universitat Politècnica de Catalunya,
Aug. 1988. Barcelona, Spain, 1995.
[13] C. D. Callaghan and J. Arrillaga, “Convergence criteria for iterative har- [26] B. C. Smith and J. C. Arrillaga, “Power flow constrained harmonic anal-
monic analysis and its application to static convertors,” in Proc. Int. ysis in AC-DC power systems,” IEEE Trans. Power Syst., vol. 14, pp.
Conf. Harmonics Power Syst., Romania, Oct. 1990, pp. 38–43. 1251–1261, Nov. 1999.
[14] R. Carbone, M. Fantauzzi, F. Gagliardi, and A. Testa, “Some consid-
erations on the iterative harmonic analysis convergence,” IEEE Trans.
Power Delivery, vol. 8, pp. 487–493, Apr. 1993.
[15] J. Arrillaga, A. Medina, M. L. V. Lisboa, M. A. Cavia, and P. Sánchez,
“The harmonic domain. A frame of reference for power system harmonic Sergio Herraiz was born in Barcelona, Spain, in 1972. He received the in-
analysis,” IEEE Trans. Power Syst., vol. 10, pp. 433–440, Feb. 1995. dustrial engineering degree and a doctorate in engineering from the Universitat
[16] E. V. Larsen, D. H. Baker, and J. C. McIver, “Low order harmonic in- Politècnica de Catalunya, Barcelona, Spain, in 1997 and 2002, respectively.
teraction on AC/DC systems,” IEEE Trans. Power Delivery, vol. 4, pp. Currently, he is a Professor in the Department of Electrical Engineering at
493–501, Jan. 1989. the Universitat Politècnica de Catalunya. His research interest is in the area of
[17] S. G. Jalali and R. H. Lasseter, “A study of nonlinear harmonic inter- power system harmonics.
action between a single-phase line commutated converter and a power
system,” IEEE Trans. Power Delivery, vol. 9, pp. 1616–1624, July 1994.
[18] J. Arrillaga and C. D. Callaghan, “A double iterative algorithm for the
analysis of power and harmonic flows at AC-DC converter terminals,”
Proc. Inst. Elect. Eng., pt. C, vol. 136, no. 6, pp. 319–324, Nov. 1989.
[19] J. Arrillaga and C. D. Callaghan, “Three phase AC/DC load and har- Luis Sainz was born in Barcelona, Spain, in 1965. He received the industrial
monic load flows,” IEEE Trans. Power Delivery, vol. 6, pp. 238–244, engineering degree and a doctorate in engineering from the Universitat Politèc-
Jan. 1991. nica de Catalunya, Barcelona, Spain, in 1990 and 1995, respectively.
[20] M. Valcárcel, “Steady-state analysis of electrical power systems with Currently, he is a Professor in the Electrical Engineering Department at the
nonlinear elements by means of an harmonic power flow method,” Universitat Politécnica de Catalunya. His research interest is in the area of power
Ph.D. dissertation (in Spanish), Universidad Politécnica de Madrid, systems harmonics.
Spain, 1991.
[21] M. Valcárcel and J. G. Mayordomo, “Harmonic power flow for unbal-
anced systems,” IEEE Trans. Power Delivery, vol. 8, pp. 2052–2059,
Oct. 1993.
[22] D. Xia and G. T. Heydt, “Harmonic power flow studies. Part I and II,” Jordi Clua was born in Barcelona, Spain, in 1970. He received the industrial
IEEE Trans. Power Apparat. Syst., vol. PAS-101, pp. 1257–1270, June engineering degree from the Universitat Politècnica de Catalunya, Barcelona,
1982. Spain, in 1997.
[23] W. Xu, J. R. Marti, and H. W. Dommel, “A multiphase harmonic load Currently, he is a Professor in the Department of Electrical Engineering at the
flow solution technique,” IEEE Trans. Power Syst., vol. 6, pp. 174–182, Universitat Politècnica de Catalunya. His research interest includes the area of
Feb. 1991. power systems harmonics.

Authorized licensed use limited to: Yonsei Univ. Downloaded on April 28,2020 at 08:08:30 UTC from IEEE Xplore. Restrictions apply.

You might also like