SINAMICS V20 Inverter: Product Information 03/2018
SINAMICS V20 Inverter: Product Information 03/2018
This document provides supplement to information in the 01/2018 edition of SINAMICS V20 Inverter Operating
Instructions (valid for firmware 3.94 SP5).
Supplement to SINAMICS V20 Smart Access and SINAMICS V20 I/O Extension Module
NOTICE
Equipment malfunctions due to improper installing or removing
Installing or removing SINAMICS V20 Smart Access when the V20 inverter is in power-on state can
cause malfunctions of SINAMICS V20 Smart Access.
• Make sure that the V20 inverter is powered off before installing or removing SINAMICS V20 Smart
Access.
NOTICE
Equipment malfunctions due to improper installing or removing
Installing or removing SINAMICS V20 I/O Extension Module when the V20 inverter is in power-on
state can cause malfunctions of SINAMICS V20 I/O Extension Module.
• Make sure that the V20 inverter is powered off before installing or removing SINAMICS V20 I/O
Extension Module.
SINAMICS V20 Inverter
Note
Observing the limit values for harmonic currents
With respect to the compliance with limits for harmonic currents, the EMC product standard EN 61800-3 for
V20 230 V inverters refers to compliance with standards EN 61000-3-2 and EN 61000-3-12.
V20 230 V inverters with the rated output power ≤ 1 kW and rated input current ≤ 16 A:
It cannot be guaranteed that the limit values are complied with EN 61000-3-2. The installation
person/company or company operating the professionally used device must obtain authorization from the
grid operator to connect the device regarding the harmonic currents. For more information about typical
harmonic currents of V20 230 V inverters, see the following table.
V20 230 V inverters with the rated output power > 1 kW and rated input current ≤ 16 A:
These devices are not subject to any limit values, and as a consequence can be connected to the public
low-voltage grid without any prior consultation.
V20 230 V inverters with the rated input current > 16 A and ≤ 75 A:
It cannot be guaranteed that the limit values are complied with EN 61000-3-12. The installation
person/company or company operating the professionally used device must obtain authorization from the
grid operator to connect the device regarding the harmonic currents. For more information about typical
harmonic currents of V20 230 V inverters, see the following table.