Installation of Foundation Grounding

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 6

Installation of Plant 5 Foundation Grounding

Work Order Number


Trade:
Duration (estimated):
Number of people:

1. Safety Procedures
a. Submit all documents as required by our Safety department prior to
safety orientation.
b. Ensure all contractor employees working on electrical equipment and
installations are qualified, competent, electricians.
c. Ensure all contractor employees attend the plant safety orientation
sessions.
d. Ensure safe mobilization of equipment to and from plant.
e. Issue all employees with the correct PPE for each task and ensure that
they are worn at all times.
f. Supply correct and quality tools to its employees to enable safe,
effective, efficient and high quality workmanship.
g. Each welding machine shall comply with EN ISO 60974-1, or be fitted
with a Voltage Reducing Device
h. Portable electrical equipment shall be double insulated (no metal drilling
machines, or angle grinders, etc.)
i. All welding machines and portable electrical equipment shall be
connected to a power socket that is protected by a Residual Current
Device (RCD). If the existing installations are not fitted with RCDs,
portable RCDs shall be supplied and used by the contractor.
j. Ensure that its employees comply with all Holcim Safety Regulations
and carry out their tasks in a safe and efficient manner.
k. Prohibit the use of substandard tools by its employees.
l. Obtain all necessary work and safety permits prior to commencement of
works.
m. All tools and equipment to be used, must be inspected, approved and
tagged by the Safety Department prior to commencement of work.
n. All works shall comply with the Holcim Design Criteria. A copy will be
furnished by the project proponent during the conduct of pre-bidding.
o. LOTO procedure at main breaker to be applied by Proponent.
Contractor to be equipped personal lock per equipment. Padlock shall
have identification tag (contractor's name and contact number)
p. Assess surroundings for safe conduct of the activity
2. Specific Required tools
Safety PPE’s
 Safety helmet
 Dust mask
 Safety Goggles
 Safety Shoes
 Reflectorized shirt/vest

Tools and Equipment


 Standard Electrician tools
 Set of socket wrenches, combination wrenches, Allen, spanners, pipe
wrenches, and Torque wrench.
 Spirit level
 Welding Machine
 Electric Drill, Grinder
 Set of drill bits, hand taps, and file
 Multi-tester, grounding tester, insulation resistance tester
 Hydraulic and manual crimping tools
 Pipe threader, Hacksaw, pipe cutter, Rimmer, and tri-pod for pipe
holders
 Portable blower and vacuum cleaner
 Jackhammer and Cement Cutter
 Power tools extension cord (Inspected and tagged by Safety Officer)
 Service truck (Inspected and passed by the Guard)

3. Scope of Supply:
Contractor shall supply the following materials required to complete the job
but not limited to:
 1 lot - Solid barricades, caution tapes
 40 pieces - Galvanized steel bracket (size depends on the length and
width until reaching the 3 main members of rebar)
 1 lot - grout
 1 lot - Exothermic Welding materials
 30 pieces - IMC pipes, 25mm diameter
 20 length - unit strut channels, galvanized iron material
 200 meters - 95mm2 x 1C, bare copper
 1 assembly - Potential Equalization Box (PEB) with 25mm x 5mm x
200mm bus bar
 3 pieces - 25mm diameter grounding rod (quantity may vary based on
the 2 ohms grounding resistance measurement)
 30 pieces - UPVC pipes, 25mm diameter
 2 boxes - 14mm2 x 1C, THHN cable, green
 1 lot - brass glands
 1 lot - bus bars for LVD grounding
Holcim supply to the following materials to complete the job:
 Cement and aggregates

4. Scope of Work

4.1 Installation of Foundation Grounding:

 1 set of foundation grounding for every steel structure.


 1 set of bonding jumper to adjacent steel structure.

a. Attend "pre-start" conducted by project proponent and secure General


Work Permit and Excavation permit.
b. Preparation of tools and materials needed for the job at Plant 5
conveying system.
c. Provide solid barricade around the structure post. Precautionary
measures required during execution of work due to presence of loading
trucks.
d. Conduct chipping of concrete post 200mm (center) above the ground
level. Required length and depth shall reach up to the minimum of 3
main members of rebar.
e. Fabricate "L" steel bracket based on the chipped off concrete made of
black iron steel with 5mm thickness. The length of the shorter leg shall
have 50mm measurement outside the concrete surface. Conduct hot
dipped galvanization of support.
f. Weld "L" bracket into the 3 main members of rebar. Plaster re-filled the
remaining opening after installation of connector bracket using grout.
g. Install unit strut support 200mm atop of steel structure base. Install
25mm diameter IMC conduit into the conduit support. The length of
conduit shall be installed nearest to cable ends.
h. Prepare 95mm2 bare copper wire for the connection of steel bracket
and steel structure. The total length of bare copper is the summation of
the length from the steel bracket to the top of concrete post and
500mm leading to the steel structure. Provide compression lug on the 1
end of bare copper and connect to the steel bracket using 16mm
diameter x 32mm bolt complete with tooth washer and nut.
i. Connect the remaining end into the steel structure 500mm away from
the concrete post using exothermic welding materials.
j. Conduct bonding of adjacent steel structures.
k. Conduct housekeeping

4.2 Installation of Potential Equalization Box

a. Install Potential Equalization Box (PEB) below Plant 5 Electrical room


(location to be determined). This is to be installed with 12mm diameter
expansion bolts. Installation of PEB shall be leveled using spirit level.
b. Conduct concrete cutting and chipping of 400mm x 400mm for the 1st
grounding pit (location to be determined).
c. Excavate hand hole and install 1 grounding rod. Conduct measurement
of grounding resistance using ground tester. If the resistance is above
2 ohms, install another rod/rods and conduct measurement.
d. Conduct concrete cutting and chipping of hand hole inter connections.
If the interconnections pass through road underpass, conduit shall be
installed 800mm below the road under pass.
e. Provide concrete 300mm x 300mm x 300mm hand hole for grounding
rods. Covers shall be fabricated with checkered steel plate and hot
dipped galvanized.
f. Route 95mm2 diameter grounding cables along 25mm diameter PVC
connected to hand holes.
g. Grounding rod/rods and cables shall be connected with exothermic
welding connection or listed clamp.
h. Connect the incoming grounding cable into the PEB panel with
compression type terminal lugs. Terminal lugs shall be connected to
bus bar with 16mm diameter x 20mm length bolts complete with flat
washer and nuts.
Note: All PEB cable entry shall be provided with cable brass glands.
i. Layout 2-95mm2 cables from LVD panel grounding and route along
existing cable trays. Installation of grounding bus bars for LVD and
tapping of grounding cables to be done during PM.
j. Connect existing grounding cables of power panels on the new PEB
with compression type terminal lugs using 16mm diameter x 20mm
length bolts complete with flat washer and nuts. Provide labels on all
grounding cables connected to PEB.
k. Conduct housekeeping

5. Terms and condition


The Contractor shall supply:

a. Registered Electrical Engineer (REE), Registered Master Electrician


(RME), TESDA certified, competent labor and sufficient supervision.
b. Contractor to submit manpower line up.
c. All Safety PPE, tools and equipment shall be provided by the contractor
to complete the project.
d. All tools and equipment to be used, must be inspected, approved and
tagged by the Safety Department prior to commencement of work.
e. Contractor employees are only allowed to render 12-hours duty. Report
list of employees who extended 12-hours duty. Prior to extension of
duty shall be coordinated to the project proponent.
f. All materials for this project listed scope of materials will be supplied by
the winning contractor.
g. Holcim will provide the electricity, however the contractor to ensure the
correct plugs are used for their equipment. Contractors are forbidden
from connecting the wires of their equipment directly to Circuit breakers
of electrical source.
h. All work shall be in accordance with the Holcim Design Criteria,
National Regulations and good engineering practices. A copy of the
Holcim Design Criteria shall be given to the contractor
i. The contractors bid shall contain all documents pertaining to warranty
of materials and work executed by the Contractor. (Labor and materials
1 year minimum).
j. All sub-standard work shall be re-done/replaced at contractors cost
prior to turn over of equipment.
k. All Contractors supplied materials shall be inspected and approved by
proponent. All rejected materials shall be replaced with the Contractors
expense.
l. Working area shall always be neat and tidy after every end of shift.
m. Contractor to be responsible for protection of their own equipment and
tools.
n. Conduct housekeeping every after day's work.
o. Contractors Safety violations will be subject to investigation. Penalty
should be imposed to contractors during any delays as per Holcim
Policy.