Water connections
• Water connections have to be done on site.
• Heating and condensate connections of flex
ible pipes with external thread (R).
Condensate connection
• The drain pipeline is to be made with suffici
ent incline and without change of the cross
section.
• The water connections and the drain pipeli
nes must be protected against frost on site.
• Siphon on site.
Heat source connections
(Air intake or air outlet)
• Air intake from the sides .
• Air outlet on the top.
Electrical connections
Part N°
• Connection from the bottom to the left or to
the right. Hoval Everest Heat Output
A20W55
Installation Type kW
• Variable and cost efficient installation pos si
bilities. (10) 10 everest010
(20) 20 everest020
Delivery (37) 37 everest037
• Complete, packed (62) 62 everest062
(72) 72 everest072
(108) 108 everest108
Service
Commissioning
Everest
Type (10) (20) (37) (62) (72) (108)
Electrical data
• Voltage V 3 x 400 3 x 400 3 x 400 3 x 400 3 x 400 3 x 400
• Oper ating current Imax. A 7.5 14.5 25 41 49 74
• Exter nal protection, Fuse A 16 20 30 50 60 80
• F requency Hz 50 / 60 (on request)
Range of application
• Ambient Temperature °C 5...45
• Max. Water Temperature °C 60
2
Dimensions
Hoval Everest (10)
Dimensions in mm
3
Dimensions
Hoval Everest (20)
Dimensions in mm
3