LIQUID COOLING NETWORK SYSTEMS FOR ENERGY CONSERVATION Ouchi2011
LIQUID COOLING NETWORK SYSTEMS FOR ENERGY CONSERVATION Ouchi2011
InterPACK2011-52066
IPACK2011-
InterPACK2011-52066
75 300W
T , °C
70
w
65 u , m/s
in
0.17
60 0.22
100W 200W 0.28
55
0.33
50 (b) Liquid cooling with two-phase narrow heat exchanger.
0 0.1 0.2 0.3 0.4
2 6 (heat load: 278W)
q , W/m [x 10 ]
w
Figure 4. Boiling heat transfer performance of two-phase Figure 6. Surface temperature of the circuit board
narrow heat exchanger by using FC-72 as a recorded by thermometer from under the board.
coolant.
0.5
0.4
(a) Spheres (f=40 nm) (b) Flake
0.3
R, K/W
0.2
0.1
0
0 10 20 30 40 50 60 70 80 (c) Wires (d=70~100 nm, l=7~10 mm)
Q, W
Figure 9. SEM images of typical shapes of silver
Figure 8. Thermal performance of thin flat plate-type heat nanoparticles.
pipe (2 mm x 30 mm x 200 mm).
0.2 Fans
0.15
R, K/W
0.1
Single phase narrow heat exchanger
0.05 directly attached to CPU 1
Figure 12. Cooling unit for CPUs in server with single-
phase narrow heat exchanger.
0 consumption of servers. As a result, it is expected that energy
0 10 20
30 40 50
Q, W saving effect of 50 to 60% is realized by means of this system
Figure 11. Thermal performance of plug-in connector comparing with the conventional air cooling systems by
without thermal grease. CRACs.
For heat transfer enhancement, silver nano-water is used as
a coolant instead of water. The concentration of silver
nanoparticles is about 1.3 wt%. Figure 13 gives heat removal
quantity as a function of the coolant temperature for both water
and silver nano-water when the flow rate is 1.1L/min. Heat
removal quantity is estimated from temperature difference
silver nano-water
110
Fan
100
90
80
Aluminum heat spreader attached to CPU 1
70
10 15 20 25 30 Figure 15. Cooling unit for CPUs in server with thin heat
Coolant temperature, °C pipes and heat exchangers.
Figure 13. Comparison of the heat removal quantity Heat exchangers Plate-type flat heat pipes
between water and silver nano-water. Aluminum heat spreader
In addition, we have been working on the verification tests attached to CPU
using server racks that has 36 columns with Pentium 4
2.66GHz 66W CPU for each server, and blade sever, which has
Xeon X5670 2.93GHz 95W x 2, Tesla GPU. These server racks
are shown in Fig. 14.