Proceedings of the ASME 2011 Pacific Rim Technical Conference & Exposition on

Packaging and Integration of Electronic and Photonic Systems


InterPACK2011
July 6-8, 2011,
Proceedings of the ASME 2011 Pacific Rim Technical Conference & Exposition Portland, Oregon,
on Packaging USA
and Integrati
on of Electronic and Photonic Systems
InterPACK2011
July 6-8, 2011, Portland, Oregon, USA

InterPACK2011-52066
IPACK2011-
InterPACK2011-52066

LIQUID COOLING NETWORK SYSTEMS FOR ENERGY CONSERVATION


IN DATA CENTERS

Mayumi Ouchi Yoshiyuki Abe


AIST AIST
Tsukuba, Japan Tsukuba, Japan

Masato Fukagaya Haruhiko Ohta Yasuhisa Shinmoto


SOHKi Co., Ltd. Kyushu University Kyushu University
Nagoya, Japan Fukuoka, Japan Fukuoka, Japan

Masahide Sato Ken-ichi Iimura


Utsunomiya University Utsunomiya University
Utsunomiya, Japan Utsunomiya, Japan

ABSTRACT comparing with conventional air cooling system was provided


Energy consumption in data center has been drastically in direct cooling technique with single-phase heat exchanger.
increasing in recent years. In data center, server racks are
cooled down by air conditioning for the whole room in a INTRODUCTION
roundabout way. This air cooling method is inefficient in Data center heat loads have increased drastically as more
cooling and it causes hotspot problem that IT equipments are components are squeezed tighter into densely packed server
not cooled down enough, but the room is overcooled. On the racks. Energy consumption is 7 billion kWh in 2009, and it is
other hand, countermeasure against the heat of the IT expected to increase annually by about 7.0%. In this context,
equipments is also one of the big issues. We therefore proposed NEDO (New Energy and Industrial Technology Development
new liquid cooling systems which IT equipments themselves Organization) launched Green IT Project for power saving of
are cooled down and exhaust heat is not radiated into the server IT equipments and reduction of environmental impact.
room. For our liquid cooling systems, three kinds of cooling The data centers are cooled by chilled air that is supplied
methods have been developed simultaneously. Two of them are from CRACs (Computer Room Air Conditioning Units).
direct cooling methods that the cooling jacket is directly Typical air circulation system in data centers consists of bottom
attached to heat source, or CPU in this case. Single-phase heat air intake for the chilled air supplied from perforated tile on
exchanger or two-phase heat exchanger is used as cooling raised floor plenum, and chilled air flows upward. As shown in
jackets. The other is indirect cooling methods that the heat Fig.1, the top part of the server rack is not efficiently cooled
generated from CPU is transported to the outside of the chassis down, and the temperature difference between bottom and top
through flat heat pipes, and condensation sections of the heat part of server rack reaches about 30℃. In data centers, a
pipes are cooled down by liquid. Verification tests have been temperature range of 16 to 24℃ is recommended, so the air
conducted by use of real server racks equipped with these temperature is set to unnecessarily low to keep room
cooling techniques while pushing ahead with five R&D temperature, and it causes high energy consumption in the data
subjects which constitute our liquid cooling system, which centers. Furthermore, excess heat in server room adversely
single-phase heat exchanger, two-phase heat exchanger, high effects equipment performance, shortens equipment life-times,
performance flat heat pipes, nanofluids technology, and plug-in and so on. Therefore, the thermal management in data centers is
connector. As a result, the energy saving effect of 50~60%

1 Copyright © 2011 by ASME

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/pdfaccess.ashx?url=/data/conferences/interpack2011/70214/ on 07/07/2017 Terms of Use: http://www.a


high-priority issue for not only the energy saving but also the In this paper, current status of technology development of
IT equipments. five R&D subjects of our new liquid cooling system is shown.
To improve the cooling efficiency, hot aisle/cold aisle Then, the energy saving effect is demonstrated by verification
approach has been adopted [1]. This method is that every aisle tests with real servers.
between rows of rack is bounded with exclusive hot-air outlets
or exclusively cool-air intakes. Likewise, optimization of the TECHNOLOGY DEVELOPMENTS
server room is in progress based on the measurements and This liquid cooling system is consisted of following five
prediction of airflow in the data centers [2]. R&D subjects;
In response, the authors have proposed the new liquid 1) Single-phase narrow heat exchanger
cooling systems for data centers. This system is of cooling 2) Two-phase narrow heat exchanger
down the CPUs directly or indirectly by liquid at each server 3) High performance thin heat pipes
rack and exhaust heat is controlled intensively using by thermal 4) Nanofluid technology for heat transfer enhancement
cable without radiating into the server room as shown in Fig.2 5) Plug-in connectors
[3]. In this section, current state of these five R&D subjects is
The three liquid cooling systems have been developed shown.
simultaneously depending on the customer’s need and the
performance of the computers. This is because about 50 % of 1) Single-phase narrow heat exchanger
IT customer does not accept intervention of the water to the For this system, the single-phase narrow heat exchanger is
server room even though electrically insulating liquid is used in expected to be adapted to up to 200W/CPU. To cool down the
our system. For the customers who tolerate liquid in server, CPUs, the heat exchanger is directly attached to CPUs. The
direct cooling techniques by single-phase narrow channel heat benefit of cooling capacity of single-phase narrow heat
exchangers and two-phase narrow heat exchangers are offered. exchanger has been well recognized.
In addition, for the customers who recuse liquid in the server The single-phase narrow heat exchanger is made of copper,
racks, indirect liquid cooling technique by using thin heat pipes and its size is 7mm in thickness and 88mm x 88mm with 3mm
is suggested. in depth and 6mm in width channels inside.
Hot air to CRACs
2) Two-phase narrow heat exchanger
server Figure 3 shows the structure of a two-phase narrow heat
exchanger [4]. The two-phase heat exchanger aims to be
adapted up to 300W/CPU for HPCs or Supercomputers. This
Server heat exchanger consists of main channel with V-grooved
DT ~ 30℃
surface and auxiliary unheated channel to supply the liquid into
the main channel. These channels are separated with porous
metal plates. The area of heating surface is 30mm x 30mm.
Figure 4 shows an example of the experimental results in
horizontal configuration for heat transfer performance of two-
Chilled air from CRACs phase narrow heat exchanger with FC-72 as a coolant. The
vertical axis is the temperature of the heating surface and the
Figure 1. Cooling system in server rack for conventional horizontal axis is the heat flux. The inlet liquid temperature is
air cooling technique. 35 ℃ and pressure is 0.15MPa. From this graph, cooling
capacity of 300W can be achieved when the velocity of the
coolant is higher than 0.22m/s.
Demonstration of cooling capacity. Figure 5 shows
the schematic diagram of the test section for the cooling
experiments. Dummy CPU is attached to circuit board, and air
cooling fan (see Fig.5 (a)) or the two-phase narrow heat
exchanger (see Fig.5 (b)) is installed above the dummy CPU. In
this experiment, ceramic heater is used as dummy CPU, and
surface temperature of the circuit board is recorded by
To/From thermography from the bottom of the circuit board. For the
Cooling network cooling experiment with the two-phase narrow heat exchanger,
system the FC-72 is used as a coolant. Flow rate of the coolant is
1.0L/min and inlet temperature is 35℃. Figure 6(a) shows the
Figure 2. Cooling system in server rack for new advanced surface temperature of the circuit board in the case of air
liquid cooling system. cooling, and the surface temperature right under the heater

2 Copyright © 2011 by ASME

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/pdfaccess.ashx?url=/data/conferences/interpack2011/70214/ on 07/07/2017 Terms of Use: http://www.a


exceeds 100℃. In addition, the temperature of the circuit board
is risen in whole. In contrast, by using two-phase narrow heat
exchanger, circuit board right under the heater is cooled to a
temperature below 90℃, and the circuit board temperature is
maintained at the room temperature as shown in Fig.6 (b).

3) High performance thin heat pipes


Thin heat pipes are used to avoid liquid intervention in the
server rack. The heat evolved from CPU is moved by heat
pipes, and the condensation part of the heat pipes is cooled
down with liquid. This cooling system with thin heat pipes is (a) Air cooling.
expected to guarantee cooling capacity up to 100W/CPU.
The authors have focused their attention to working fluid
to enhance heat transfer in the course of liquid/vapor phase
change due to Marangoni effect induced by surface tension
gradient [5]. Instead of pure water, the authors employed the
so-called “self-rewetting” fluid, which is dilute high carbon
alcohol aqueous solution, to improve the thermal performance
of the heat pipes [6]. In addition, the nanofluids are also used
as working fluids. (b) Two-phase heat exchanger.

Figure 5. Schematic diagram of test section for cooling


experiments by air cooling and liquid cooling
with two-phase narrow heat exchanger.

Figure 3. Schematic diagram of narrow channel for two-


phase heat exchanger. (a) Air cooling (heat load: 231W).
90
85 T = 35 °C
in
P = 0.15 MPa
80 in

75 300W
T , °C

70
w

65 u , m/s
in
0.17
60 0.22
100W 200W 0.28
55
0.33
50 (b) Liquid cooling with two-phase narrow heat exchanger.
0 0.1 0.2 0.3 0.4
2 6 (heat load: 278W)
q , W/m [x 10 ]
w

Figure 4. Boiling heat transfer performance of two-phase Figure 6. Surface temperature of the circuit board
narrow heat exchanger by using FC-72 as a recorded by thermometer from under the board.
coolant.

3 Copyright © 2011 by ASME

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/pdfaccess.ashx?url=/data/conferences/interpack2011/70214/ on 07/07/2017 Terms of Use: http://www.a


Thin flat heat pipes. The thin flat heat pipes are made kinds of wick structures and four kinds of working fluids have
by flattening out the tube-type heat pipes. Its dimensions are been examined. All experiments were carried out in horizontal
1.5mm in thickness, 15mm in width, and 200mm in length. configuration. As a result, the thermal transport rate of about
Figure 7 shows an example of thermal performance in 70W is achieved and the thermal resistance of 0.2K/W is
horizontal configuration of the thin flat heat pipes depending obtained when the temperature at the condensation section
on the working fluids. The vertical axis is thermal resistance reaches upper limit as shown in Fig. 8. Note that the dryout did
between the evaporation section and the condensation section, not occur at this condition yet.
R, and the horizontal axis is the thermal input, Q. All
experiments are carried out in horizontal configuration and in a 4) Synthesis and optimization of nanofluids for heat
vacuum. As compared in Fig. 7, self-rewetting fluid enables transfer enhancement
higher heat transfer rate. Benefits of the inclusion of nanoparticles into working
Plate-type heat pipes. To aim at simplification of the fluids in heat transfer have been extensively demonstrated [7].
cooling system, the prototype plate-type heat pipes were Although most of researchers prepare nanofluids by
developed by heat rolling of two copper films. The size of this mechanical mixing of nanoparticles in solvent, the authors have
plate-type heat pipe is 2mm in thickness, 30mm in width, and consistently employed so-called microwave polyol method
200mm in length. At this stage, the thermal performances of which allows for a direct and rapid synthesis of nanofluids by
this plate-type heat pipes with the combination between eight means thermo-chemical reaction in liquid state assisted by
microwave irradiation [8]. Nanofluids prepared by this method
1 show outstanding stability, and it can be controlled the size and
the shape of nanoparticles by adjusting the synthesis conditions
Water of the thermo-chemical reaction.
0.8 Self-rewetting fluid
Typical silver nanoparticles, spheres, flakes, and wire are
Nano self-rewetting fluid
shown in Fig. 9. From the view point of heat transfer
0.6 enhancement, nanoparticles with a larger aspect ratio, such as
R, K/W

nano wire, are considered to be more promising because of a


0.4 larger contribution in the increase in thermal conductivity [9].
At this stage, the shape of nanoparticles can be controlled and
primary thermophysical properties, such as density, surface
0.2 tension, thermal conductivity, viscosity, have been
experimentally evaluated.
0
0 20 40 60 80 100 120 140 160
Q, W
Figure 7. Comparison of the thermal performances of thin
flat heat pipe (1.5mm x 15mm x 200mm)
among three working fluids.

0.5

0.4
(a) Spheres (f=40 nm) (b) Flake

0.3
R, K/W

0.2

0.1

0
0 10 20 30 40 50 60 70 80 (c) Wires (d=70~100 nm, l=7~10 mm)
Q, W
Figure 9. SEM images of typical shapes of silver
Figure 8. Thermal performance of thin flat plate-type heat nanoparticles.
pipe (2 mm x 30 mm x 200 mm).

4 Copyright © 2011 by ASME

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/pdfaccess.ashx?url=/data/conferences/interpack2011/70214/ on 07/07/2017 Terms of Use: http://www.a


5) Plug-in connectors INTEGRATION AND DEMONSTRATION OF COOLING
A prototype plug-in connector for the single-phase heat SYSTEMS
exchanger and the thin heat pipes is shown in Fig. 10. Two thin The authors have constructed prototype server racks
heat pipes are supported by a copper conductive attachment as equipped with real servers. In this section, the results of the
shown in Fig. 10(a). In Fig. 10(b), the assembly of the verification tests of our liquid cooling systems by using real
conductive attachment and heat pipes is inserted into a narrow server racks are shown, especially direct cooling technique
channel single-phase heat exchanger. Figure 11 shows the with single-phase narrow heat exchanger and the indirect
thermal resistance between the single-phase heat exchanger and cooling technique with high performance thin heat pipes.
the copper attachment. The horizontal axis indicates heat input
to the heat pipes by ceramic heater. As shown in Fig. 11, the Direct liquid cooling technology with single-phase
thermal resistance is about 0.12K/W, and it gradually decreases narrow heat exchangers
as increasing heat load. However, this experiment is conducted Figure 12 gives the cooling unit with single-phase narrow
without thermal grease, so the thermal resistance must be heat exchangers. The CPUs are Intel Xeon E5540 2.53GHz
improved if the contact condition is ameliorated. 80W. CPU utilization of each server is controlled by software,
Various types of plug-in connectors, both fluidic and the surface temperature of CPU is measured by K-type
connectors and thermal connectors, for liquid/vapor lines, heat thermocouples. FC-72 is used as a coolant and its inlet
exchangers, manifolds, heat pipes, and so on are necessary to temperature and the flow rate is 20 ℃ and 1.0L/min,
construct the cooling network system. These connectors must respectively. All experiments were carried out in the ambient
be drip free structure, and have low thermal resistance. temperature of 32℃. Table 1 shows an example of surface
temperature of CPUs when the CPU utilization is 100%. Air
cooling indicates that the CPUs are cooled by only six fans. In
the case of the liquid cooling-1, both six fans and single-phase
narrow heat exchanger are used for cooling of CPUs, and liquid
cooling-2 indicates only the single-phase narrow heat
exchanger is used. By using the liquid cooling system, the
surface temperature of CPUs is much lower than the air cooling
case. At this stage, heat removal rate from CPUs achieved 95%,
which is estimated to correspond to 67% of the total energy
(a) Before insertion (b) After insertion
Single-phase narrow heat exchanger
Liquid manifold
Figure 10. Prototype plug-in connector for thin heat pipes directly attached to CPU 2
and single-phase narrow heat exchanger.

0.2 Fans

0.15
R, K/W

0.1
Single phase narrow heat exchanger
0.05 directly attached to CPU 1
Figure 12. Cooling unit for CPUs in server with single-
phase narrow heat exchanger.
0 consumption of servers. As a result, it is expected that energy
0 10 20
30 40 50
Q, W saving effect of 50 to 60% is realized by means of this system
Figure 11. Thermal performance of plug-in connector comparing with the conventional air cooling systems by
without thermal grease. CRACs.
For heat transfer enhancement, silver nano-water is used as
a coolant instead of water. The concentration of silver
nanoparticles is about 1.3 wt%. Figure 13 gives heat removal
quantity as a function of the coolant temperature for both water
and silver nano-water when the flow rate is 1.1L/min. Heat
removal quantity is estimated from temperature difference

5 Copyright © 2011 by ASME

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/pdfaccess.ashx?url=/data/conferences/interpack2011/70214/ on 07/07/2017 Terms of Use: http://www.a


between inlet and outlet temperature of the coolant. As a result,
the improvement of the heat removal quantity is seen by using
silver nano-water. Moreover, decreasing trend of the heat
removal quantity is shown with increasing temperature of the
coolant when this experimental condition.

Table 1. Comparison of the surface temperature of CPUs


between air cooling and liquid cooling with
single-phase narrow heat exchangers.
[unit: ℃]
Air cooling Liquid cooling-1 Liquid cooling-2
Fan: 6/6 Fan: 6/6 Fan: 0/6
CPU 1 57 29.4 30.5
CPU 2 58 28.3 30.3
Ave. 57.5 28.8 30.4 (a) 36U server rack (b) Blade server rack
 CPU Utilization: 100% Pentium4 2.66GHz 66W Xeon X5670 2.93GHz
 Coolant: FC-72 CPU 95W x 2 CPUs, Tesla
 Flow rate: 1.0L/min GPU
 Inlet temperature: 20℃
Figure 14. 36U and the blade server racks with single-
phase heat exchanger.
130 Heat exchangers
Thin flat heat pipes Aluminum heat spreader
120 water attached to CPU 2
Heat removal quantity, W

silver nano-water
110
Fan
100

90

80
Aluminum heat spreader attached to CPU 1
70
10 15 20 25 30 Figure 15. Cooling unit for CPUs in server with thin heat
Coolant temperature, °C pipes and heat exchangers.
Figure 13. Comparison of the heat removal quantity Heat exchangers Plate-type flat heat pipes
between water and silver nano-water. Aluminum heat spreader
In addition, we have been working on the verification tests attached to CPU
using server racks that has 36 columns with Pentium 4
2.66GHz 66W CPU for each server, and blade sever, which has
Xeon X5670 2.93GHz 95W x 2, Tesla GPU. These server racks
are shown in Fig. 14.

Indirect liquid cooling technology with high


performance thin heat pipes
Aluminum heat spreader attached to CPU 1
For this verification test, the CPUs are Intel Xeon E5540
2.53GHz 80W. HFE-7200 was used as a coolant and its inlet Figure 16. Cooling unit for CPUs in server with plate-type
temperature and flow rate is 14℃ and 0.7L/min, respectively. heat pipes and heat exchangers.
As far as air cooling is concerned, the experiment was carried condensation section of the heat pipes. For this system, two
out at room temperature of 27℃. fans are also used to cool the other devices.
Figure 15 shows the cooling unit with thin heat pipes. As Figure 16 shows the cooling unit with plate-type heat
shown in Fig. 15, four heat pipes are used to cool down each pipes. One CPU is cooled by one plate-type heat pipe, and the
CPU. A single-phase heat exchanger is used in the

6 Copyright © 2011 by ASME

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/pdfaccess.ashx?url=/data/conferences/interpack2011/70214/ on 07/07/2017 Terms of Use: http://www.a


system is simplified. For this system, three fans are used the blade server with plate-type heat pipes will be demonstrated
subsidiarily. while modifying the property of the heat pipes to suit cooling
Table 2 shows an example of the surface temperature of capacity we expected.
CPUs when the CPU utilization is 100%. On the averaged
temperature of both CPUs, there is no significant difference ACKNOWLEDGMENTS
between air cooling and liquid cooling with thin heat pipes. In We would like to thank Mr. Takashi Kitagawa, Kawamura
contrast, higher temperature is shown for the cooling technique electric Inc., for technical support for the server racks and the
with plate-type heat pipes. Thereafter, plate-type heat pipes will CPU utilization program. The present work has been conducted
be adapted to the blade servers. under the Green IT Project sponsored by NEDO.

Table 2. Comparison of the surface temperature of REFERENCES


CPUs between air cooling and liquid cooling [1] Techreport, 2009. Fundamentals of data center power and
with high performance thin flat heat pipes cooling efficiency zones. White Paper #21, The Green
technique. [unit: ℃] Grid, March.
[2] Cho, J., Lim, T., and Kim, B. S., 2009. “Measurements and
Liquid cooling
Air Liquid cooling predictions of the air distribution systems in high compute
Plate-type heat
cooling Thin heat pipes density (Internet) data centers”. Energy and Buildings, 41,
pipes
Fan: 6/6 Fan: 2/6 pp. 1107-1115.
Fan: 3/6
[3] Abe, Y., Fukagaya, M., Kitagawa, T., Ohta, H., Shinmoto,
CPU 1 60.4 56.7 64.7
Y., Sato, M., and Iimura, K., 2009. “Advanced integrated
CPU 2 54.2 58.3 67.8
cooling systems for thermal management in data centers”.
Ave. 57.3 57.5 66.3 Proc. IPACK2009, IPACK2009-89009.
 CPU Utilization: 100% [4] Ohta, H., Shinmoto, Y., Ishikawa, Y., and Ariki, K., 2006.
 Coolant: HFE-72 “High heat flux cooling of large areas by improved liquid
 Flow rate: 0.7L/min supply for flow boiling in narrow channels”. Proc. 13th
 Inlet temperature: 16℃ International Heat Transfer Conference, BOI-32, p.12.
[5] Abe, Y., 2009. “Applications of self-rewetting fluids as a
CONCLUSION working fluid in heat transfer”. Int. J. Transport
New liquid cooling systems for data centers were proposed Phenomena, 11(1), pp.1-18.
for energy saving. To establish the systems, five R&D subjects, [6] Abe, Y., Tanaka, K., Mochizuki, M., Sato, M., di
which are single-phase heat exchanger, two-phase heat Francescantonio, N., and Savino, R., 2006. “Heat pipes
exchanger, high performance thin heat pipes, nanofluids with self-rewetting fluids”. Proc. 8th Int. Heat Pipe
technique, and plug-in connector, have been developed. With Symposium, pp. 76-81.
demonstration of cooling capacity with real servers, the energy [7] Godson, L., Raja, B., Lal, D. M., and Wongwises, S., 2010.
saving effect of 50~60% was expected by means of the direct “Enhancement of heat transfer using nanofluids –An
liquid cooling with single-phase heat exchanger comparing overview”. Renewable and Sustainable Energy Reviews, 14,
with the conventional air cooling system by CRACs. As far as pp. 629-641.
the indirect liquid cooling system with high performance thin [8] Tsuji, M., Nishizawa, Y., Hashimoto, M., and Tsuji, T.,
heat pipes, cooling capacity comparable to the air cooling 2004. “Syntheses of silver nanofilms, nanorods, and
system was obtained as property improvement of heat pipes is nanowires by a microwave-polyol method in the presence
in progress. of Pt seeds and polyvinylpyrrolidone”. Chem. Let. 33(4),
As the next step, quantitative advantage of the present pp. 370-371.
liquid cooling systems over conventional air cooling system [9] Zhang, X., Goo, H., and Fujii, M., 2006. “Measurements of
will be clarified in its very own server room. In the meanwhile, effective thermal conductivity and thermal diffusivity of
integration of this system with two-phase heat exchanger in real nanofluids”. Netsu bussei, 20(1), pp.14-19.
servers will be conducted. Moreover, the verification test for

7 Copyright © 2011 by ASME

Downloaded From: http://proceedings.asmedigitalcollection.asme.org/pdfaccess.ashx?url=/data/conferences/interpack2011/70214/ on 07/07/2017 Terms of Use: http://www.a