Professional Documents
Culture Documents
Saudi Aramco Test Report: MV Cablebus High-Potential Withstand Testing SATR-P-3235 3-Jul-18 Elect
Saudi Aramco Test Report: MV Cablebus High-Potential Withstand Testing SATR-P-3235 3-Jul-18 Elect
00 30-Apr-18
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
MV Cablebus High-Potential Withstand Testing SATR-P-3235 3-Jul-18 ELECT-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
SAES-P-116
A5 Thoroughly clean the cable bus before starting the test.
Sec. 3.2
All ends under test shall be guarded from accidental contact as well as SAES-P-104
A6
separation from all ends or elements not being subject to test. Sec.13.2d
Prior to high potential test, perform a shield continuity test by ohm meter SAES-P-116
A8
method. (NETA ATS, 2009 Sec. 7.4) Sec. 3.2
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Insulation resistance
Bus Phases Applied Voltage Pass Fail Remarks
(Mega-ohms)
Phase 1 to Ground
Phase 2 to Ground
Phase 3 to Ground
Phase 1 to Phase 2
Phase 2 to Phase 3
Phase 3 to Phase 1
Notes:
1-Hi-pot test shall not be proceeded unless the insulation resistance test above is found to be satisfactory.
3-Test voltages shall not exceed 80 percent of cable manufacturer's factory test value or the maximum test voltage in the table below.
Insulation 80% Test 65% Test Rated Insulation 80% Test 65% Test
Rated Voltage
thickness Voltage Voltage Voltage thickness Voltage Voltage
Notes:
80% and 65% refer to the percentages of the factory test voltages specified in AEIC CS5 and CS6. AEIC CS5 and CS6
1
permit testing at 65% test voltage at any time during the period of the guarantee.
AEIC CS5 and CS6, and ANSI/IEEE Standard 400 do not differentiate cables based upon insulation thickness and,
2
consequently, list differing test voltages.
Insure the maximum test voltage does not exceed the voltage limits for potheads and terminators specified in IEEE Std. 48
(IEEE Standard Test Procedures and Requirements for High Voltage AC cable Terminations) or for molded rubber
3
terminations specified in IEEE std.386 ( IEEE Standard for Separable Insulated Connector Systems for Power Distribution
Systems Above 600V), or manufacturer's published data.
In accordance to SAES-P-104, Section 13.2 (e), if separable connectors (elbows) conforming to ANSI/IEEE std. 386 are
used, the high potential test on medium voltage cables may, at the request of the cable Proponent, be performed after
4
installation of the elbows. For new 15 kV cable, when tested with elbows, the test voltage is reduced from 64 kV to 53 kV; for
35 kV cable it remains unchanged at 100 kV DC ( the ICEA cable test value).
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
The D.C. high voltage shall be applied in a minimum of four steps ( each
of an order of the rated ac rms voltage of the cable) of one (1) minute
SAES-P-116
B2 duration each except for the final test voltage which shall be maintained
Sec. 3.2
for fifteen (15) minutes.
(NETA ATS, 2009 Sec. 7.4)
At the end of each step, allow the charging currents to decay, and time the
SAES-P-116
B4 interval of decay.
Sec. 3.2
(NETA ATS, 2009 Sec. 7.4)
Read the leakage current and plot a curve of leakage currents versus test
voltage on graph paper as the test progresses. Read the leakage current SAES-P-116
B5
at the same time interval for each voltage step. Sec. 3.2
(NETA ATS, 2009 Sec. 7.4)
Upon reaching maximum test voltage, hold the voltage for 15 minutes.
Read the leakage current at 60 seconds intervals and plot a curve of
leakage current versus time on the same graph paper as the step voltage
SAES-P-116
B7 curve. Stop the test if leakage current starts to rise, or decrease and again
Sec. 3.2
starts to rise. the leakage current should decrease and stabilize for good
cable.
(NETA ATS, 2009 Sec. 7.4)
Schedule Q
C1 The test equipment calibration cycle shall not exceed six (6) months.
Att. IV, Sec. 7.1
D. TEST RESULTS
Step 1 kV
Step 2 kV
Step 3 kV
Step 4 kV
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
15 SEC
30 SEC
45 SEC
1 MIN
2 MIN
3 MIN
4 MIN
5 MIN
6 MIN
7 MIN
8 MIN
9 MIN
10 MIN
11 MIN
12MIN
13 MIN
14 MIN
15 MIN
GENERAL DATA
% REL. HUM.
INSUL THICK
E. CONCLUSIONS
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Test results are acceptable and in accordance with Saudi Aramco Schedule Q
E4
Engineering Standards and contractual requirements. Sec. 1.3
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
REMARKS:
REFERENCE DOCUMENTS:
1. Schedule G -- Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), Contract Specific
2. Schedule Q -- Quality Requirements (Pro Forma Contract), Contract Specific
3. 16-SAMSS-520 -- Cablebus, 4 June 2014
4. NETA ATS -- Acceptance Testing Specifications for Electrical Equipment and Systems, 2009
5. SAES-P-104 -- Wiring Methods and Materials, 01 January 2018
6. SAES-P-116 -- Switchgear and Control Equipment,8 August 2017
7. Saudi Aramco Form 7823 (5/91)
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products or
services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the
manufacturer indicates compliance with appropriate standards or performance in a specified manner.
*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED