GENERAL STRUCTURAL NOTES

CODE AND DESIGN LOADS STRUCTURAL STEEL FOUNDATIONS PE STAMP


1. ALL CONSTRUCTION SHALL CONFORM TO THE 2015 EDITION OF THE 1. STRUCTURAL STEEL CONSTRUCTION SHALL CONFORM TO THE LATEST AISC 1. ALL SLABS AND FOOTINGS SHALL BEAR ON FIRM, UNDISTURBED NATIVE SOIL. ALL
GENERAL INFORMATION
INTERNATIONAL BUILDING CODE. SPECIFICATION FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL SOIL BELOW FOOTINGS AND SLABS SHALL BE COMPACTED TO 95% MINIMUM IN
AND SYSTEM DETAILS
2. GRAVITY: STEEL FOR BUILDINGS. ACCORDANCE TO ASTM D698. DESIGN SOIL BEARING PRESSURE = 1500 PSF AT
GENERAL INFORMATION:
ROOF LIVE LOAD = 20 PSF (REDUCIBLE) 2. STRUCTURAL PROPERTIES: 1'-6" BELOW LOWEST ADJACENT FINISHED GRADE PER MINIMUM VALUES IN I.B.C. SITE ADDRESS:
ROOF SNOW LOAD = 30 PSF (30 PSF GROUND) WIDE FLANGE SHAPES - ASTM A992 (Fy = 50 KSI) TABLE 1804.2.
AZIMUTH:
ROOF DEAD LOAD (SOLAR MODULES) = 3 PSF CHANNELS, PLATES, AND ANGLES - ASTM A36 (Fy = 36 KSI) 2. ALL CONSTRUCTION SHALL COMPLY WITH THE MINIMUM IBC REQUIREMENTS. SYSTEM TYPE:
3. WIND: STRUCTURAL TUBE SHAPES - ASTM A500, GRADE B (Fy = 46 KSI) THE ENGINEER OF RECORD IS NOT RESPONSIBLE FOR ANY GEOTECHNICAL
BASIC WIND SPEED - 115 MPH (3 SEC GUST.) 3. BOLTS STEEL/STEEL - ASTM A325N. ALL HIGH-STRENGTH BOLTS SHALL BE ASPECTS OF THIS PROJECT AND THE CONTRACTOR SHALL HIRE A
TOTAL SYSTEM SIZE:
EXPOSURE - "C" TIGHTENED TO THE SNUG-TIGHT CONDITION AS DEFINED BY AISC UNLESS NOTED GEOTECHNICAL ENGINEER IF UNUSUAL/UNSUITABLE MATERIAL/SOIL IS TOTAL # OF MODULES:
DESIGN WING PRESSURES PER ASCE 7-10, (MWFRS) SECTION 27.4.3 (OPEN OTHERWISE DISCOVERED DURING EXCAVATIONS/CONSTRUCTION. MODULE TILT:
N-S SPACING:
BUILDINGS WITH MONOSLOPE, PITCHED, OR TROUGHED FREE ROOFS), (C&C) 4. ANCHOR RODS (ANCHOR BOLTS) - ASTM F1554 GR 36 (EMBEDMENT PER 3. ABANDONED FOOTINGS, NEW OR EXISTING UTILITIES, ETC., THAT INTERFERE E-W GAP BETWEEN MOD.:
SECTION 30.7.1 (OPEN BUILDING WITH MONOSLOPE FREE ROOFS) FOUNDATION DETAILS) WITH NEW CONSTRUCTION SHALL BE REROUTED OR REMOVED AS E-W GAP BETWEEN ARRAYS:
4. SEISMIC: SEISMIC IS NOT CONSIDERED PER IBC SECTION 1613.1. 5. BOLTS, ANCHOR BOLTS, ETC., SHALL BE INSTALLED WITH STEEL TIGHTENED COORDINATED WITH THE OWNER BUILDING CODES:
NUTS. STRUCTURAL:
GENERAL 6. WELDING ELECTRODES SHALL CONFORM TO AWS D1.1, GRADE E70XX. ALL SOLAR DESIGN EMBEDMENT:
SOIL CLASS:
WELDING SHALL BE DONE BY WELDERS HOLDING VALID CERTIFICATES ISSUED
1. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE 1. THE ENGINEER OF RECORD FOR THE STRUCTURE SHOWN ON THESE DRAWINGS LOADS:
BY AN ACCEPTED TESTING AGENCY AND HAVING CURRENT EXPERIENCE IN TYPE
FINISHED STRUCTURE. THEY DO NOT INDICATE THE MEANS OR METHOD OR IS NOT THE SOLAR DESIGN ENGINEER OF RECORD AND ASSUMES NO DESIGN WIND SPEED:
OF WELDS SHOWN ON FABRICATION DRAWINGS. ALL WELDING PER AMERICAN
SEQUENCE OF CONSTRUCTION. RESPONSIBILITY FOR ANY ASPECT OF THE SOLAR DESIGN OF.
WELDING SOCIETY STANDARDS. ALL WELDS ON FABRICATION DRAWINGS ARE 3 SEC GUST EFFECT:
2. THE CONTRACTOR IS RESPONSIBLE FOR SAFETY PRECAUTIONS AND PROGRAMS RISK CATEGORY:
IN CONNECTION WITH THE WORK THAT CONFORMS WITH THE REGULATIONS OF
SHOWN AS SHOP WELDS AND SHALL BE SHOWN ON SHOP DRAWINGS. FULL
PENETRATION WELDS SHALL BE TESTED AND CERTIFIED BY AN INDEPENDENT
ELECTRICAL DESIGN EXPOSURE:
MWFRS WIND LOAD (SOUTH WIND):
THE OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) SAFETY AND PSF
TESTING LABORATORY. 1. THE ENGINEER OF RECORD FOR THE STRUCTURE SHOWN ON THESE DRAWINGS MWFRS WIND LOAD (NORTH WIND):
HEALTH STANDARDS FOR THE CONSTRUCTION INDUSTRY.
7. DRYPACK FOR COLUMN BASE PLATES AND BEARING PLATES SHALL BE FIVE STAR IS NOT THE ELECTRICAL ENGINEER OF RECORD AND ASSUMES NO PSF
3. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON THE DESIGN SNOW LOAD: PSF
GROUT OR AN EQUAL NONMETALLIC SHRINKAGE-RESISTANT GROUT WITH RESPONSIBILITY FOR ANY ASPECT OF THE ELECTRICAL DESIGN.
STRUCTURE SO AS NOT TO EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT. MODULE DEAD LOAD: PSF
MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 5000 PSI.
4. WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR MATERIALS,
SUCH STANDARDS SHALL BE THE LATEST EDITION AND/OR ADDENDUM.
8. ALL HOT ROLLED STRUCTURAL STEEL TO BE HOT DIP GALVANIZED PER CIVIL DESIGN MANUFACTURER'S TOLERANCES:
LATERAL POST PLACEMENT
ASTMA-123. (X-Z PLANE):
5. ESTABLISH AND VERIFY ELECTRICAL/SOLAR EQUIPMENT WITH APPROPRIATE 1. THE ENGINEER OF RECORD FOR THE STRUCTURE SHOWN ON THESE DRAWINGS ±2.0" FOR TILT ANGLES < 20°
TRADE. IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO COORDINATE
WITH THE SUBCONTRACTORS AND EQUIPMENT SUPPLIERS. EQUIPMENT BEING
CAST-IN-PLACE CONCRETE IS NOT THE CIVIL ENGINEER OF RECORD AND ASSUMES NO RESPONSIBILITY FOR
ANY ASPECT OF THE CIVIL DESIGN OF THE INSTALLATION SITE.
±1.5" FOR TILT ANGLES ≥ 20°
LATERAL POST PLACEMENT
(Y-Z PLANE): ±4.0" WITHIN ARRAY
SUPPORTED BY OR SUSPENDED FROM THE STRUCTURE SHALL BE COORDINATED 1. CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF ACI 301, POST HEIGHT VARIATION
WITH THE MANUFACTURER. DO NOT PENETRATE ANY STRUCTURAL ELEMENTS "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS" AND ACI 318, SPECIAL INSPECTIONS: (X-Y PLANE): ±0.5"
POST VERTICALITY TOLERANCE:
(BEAMS, COLUMNS, RAILS, ETC.) WITHOUT PRIOR WRITTEN APPROVAL OF THE "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE". < 2.0° ALL DIRECTIONS
1. SPECIAL INSPECTIONS SHALL BE PERFORMED BY A QUALIFIED INSPECTOR AS
ENGINEER OF RECORD THROUGH THE MANUFACTURER. 2. ADDITION OF WATER TO THE BATCH FOR MATERIAL WITH INSUFFICIENT SLUMP POST ROTATIONAL TOLERANCE:
APPROVED BY THE BUILDING OFFICIAL. ±5.0°
6. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND COORDINATE SITE WILL NOT BE PERMITTED, UNLESS THE SUPPLIER HAS SPECIFICALLY WITHHELD ARRAY TILT ANGULAR TOLERANCE:
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A MINIMUM OF 24
CONDITIONS WITH THE DRAWINGS PRIOR TO CONSTRUCTION. ANY WATER FROM THE BATCH AT THE PLANT. IN SUCH CASE THE MIX DESIGN AND ±2.0°
HOURS NOTICE TO THE SPECIAL INSPECTOR AND THE TESTING LABORATORY
DISCREPANCIES AND OMISSIONS SHALL BE RESOLVED WITH THE TRUCK TICKET MUST CLEARLY STATE THE MAXIMUM AMOUNT OF WATER THAT
PRIOR TO BEGINNING ANY WORK FOR WHICH SPECIAL INSPECTION OR TESTING
MANUFACTURER PRIOR TO CONSTRUCTION AND PRIOR TO PROCEEDING. DO NOT CAN BE ADDED TO THE BATCH ON SITE. IN NO CASE SHALL THE DESIGN WATER
IS REQUIRED.
USE SCALED DIMENSIONS. TO CEMENTITOUS MATERIAL RATIO BE EXCEEDED.
3. SPECIAL INSPECTION IS REQUIRED DURING THE FOLLOWING OPERATIONS PER
7. WHERE ANY DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, STRUCTURAL 3. CONCRETE SHALL BE READY MIXED CONCRETE IN ACCORDANCE WITH ASTM C94. MODULE INFORMATION
IBC CHAPTER 17:
NOTES AND SPECIFICATIONS, THE GREATER REQUIREMENTS SHALL GOVERN. CONCRETE USE MINIMUM 28 DAY COMP. STRENGTH
A. BY GEOTECHNICAL ENGINEER - GRADING, EXCAVATION AND FILLING: MODULE: GENERIC
8. TYPICAL DETAILS MAY OR MAY NOT BE CUT ON THE DRAWINGS, AND DETAILS FOUNDATIONS - 3,000 PSI (DESIGNED FOR 2500 PSI) MODULE MODEL: 72 CELL
DURING EARTHWORK EXCAVATIONS, GRADING AND FILLING AS REQUIRED
MAY OR MAY NOT BE CUT AT ALL SPECIFIC LOCATIONS, BUT SHALL APPLY 4. CEMENT SHALL CONFORM TO ASTM C150, TYPE II. AGGREGATE PER ASTM C33. MODULE SIZE: 78.15"x39"x1.81"
TO SATISFY REQUIREMENTS OF IBC CHAPTER 18, INCLUDING PLACEMENT OF MODULE WEIGHT: 57.3 LBS
UNLESS NOTED OTHERWISE. LIGHTWEIGHT AGGREGATE PER ASTM C330. MAXIMUM 5" SLUMP FOR ALL MODULE OUTPUT: VARIES
ENGINEERED FILL. NOTE: THE GEOTECHNICAL ENGINEER WHO PERFORMED
9. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW CONCRETE. CONCRETE CONTAINING SUPERPLASTICIZING ADMIXTURE SHALL
THE GEOTECHNICAL REPORT SHALL PROVIDE THESE INSPECTIONS.
SHALL BEAR THE SEAL OF A PROFESSIONAL ENGINEER REGISTERED IN THE HAVE 8" MAXIMUM SLUMP AT PLACEMENT. MIX DESIGNS SHALL BE DESIGNED BY T H I S D R A W I N G I S T H E P R O P E R T Y O F D P W ,
B. WELDING: DURING ALL STRUCTURAL FIELD WELDING AND SHOP WELDING, DIRECT POWER & WATER CORPORATION AND CANNOT BE USED, COPIED, OR DISCLOSED WITHOUT

STATE WHICH THE PROJECT IS LOCATED. THE CONCRETE PRODUCTION FACILITY IN ACCORDANCE WITH ACI 301 AND P E R M I S S I O N .

EXCEPT WELDING PERFORMED IN THE SHOP OF A BUILDING OFFICIAL/ DISCLAIMER OF LIABILITY


APPROVED BY THE ENGINEER OF RECORD PRIOR TO CONSTRUCTION. SINCE THE CONDITIONS OF USE AND MAINTENANCE OF THE UNIT ARE BEYOND THE CONTROL OF

COLD FORMED STEEL FRAMING 5. CONCRETE SHALL BE FREE OF CHLORIDE. WHEN USED, FLY ASH SHALL
APPROVED FABRICATOR - PERIODIC.
C. ANCHOR BOLTS INSTALLED IN CONCRETE: INSPECT TIED IN PLACE PRIOR TO
DIRECT POWER & WATER CORPORATION, THE COMPANY DOES NOT ASSUME RESPONSIBILITY AND
E X P R E S S L Y
LIABILITY FOR LOSS, DAMAGE, OR EXPENSE ARISING
D I S C L A I M S

O U T O F O R I N A N Y W A Y C O N N E C T E D W I T H T H E

CONFORM TO ASTM C618, CLASS F. FLY ASH SHALL NOT REPLACE MORE THAN U S E , O R M A I N T E N A N C E O F T H I S S Y S T E M .

1. ALL COLD-FORMED STEEL FRAMING SHALL BE FABRICATED AND ERECTED IN PLACEMENT OF CONCRETE OR INSPECT DURING "WET SET" PLACEMENT IN PLEASE NOTE
20% OF CEMENT BY WEIGHT. IF PLAN VIEW WAS DERIVED BY HAND SCALING A PRINT IMAGE.

ACCORDANCE WITH THE LATEST EDITION OF THE "SPECIFICATION FOR THE CONCRETE - CONTINUOUS. THE RESULTING ACCURACY CANNOT BE GUARANTEED.
CUSTOMER ASSUMES ALL RESPONSIBILITY IN VERIFYING
6. CONCRETE SHALL NOT BE DROPPED MORE THAN FIVE FEET VERTICALLY D E S I G N T O A C T U A L C O N S T R U C T I O N C O N D I T I O N S .
DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS" BY THE AMERICAN 4. DUTIES AND RESPONSIBILITIES OF THE SPECIAL INSPECTOR:
WITHOUT USE OF TREMIES.
IRON AND STEEL INSTITUTE. A. THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED FOR REVISION TABLE
7. CONCRETE FOOTINGS MAY BE POURED AGAINST NEAT EXCAVATIONS PROVIDED
2. CEE PURLIN MATERIAL SPECIFICATIONS: CONFORMANCE WITH THE APPROVED DESIGN DRAWINGS AND REV: - BY: - APP BY: - DATE: -
THAT FOOTING DIMENSION ARE ADHERED TO, AND THE REQUIRED CONCRETE -
- DESIGNATION SS GRADE 50 CLASS 1 (MIN FY = 50 KSI) SPECIFICATIONS.
COVERAGE FOR REINFORCING IS MAINTAINED.
- THICKNESS: 0.1292 IN B. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE
8. MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED
- COATING DESIGNATION: G90 GALVINIZATION (ASTM A653) BUILDING OFFICIAL AND TO THE ENGINEER OF RECORD. ALL DISCREPANCIES
9. CONCRETE WHICH HAS CONTAINED WATER FOR MORE THAN 90 MINUTES (60
- ALTERNATE COATING DESIGNATION: G235 GALVINIZATION (ASTM A653) SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR
MINUTES IF AIR TEMPERATURE EXCEEDS 85DEGREES) SHALL NOT BE USED.
(MATERIAL CERTIFICATION REQUIRED) FOR CORRECTION, THEN, IF UNCORRECTED, TO THE ENGINEER OF RECORD
RETEMPERING OF CONCRETE AFTER INITIAL SET HAS OCCURRED IS NOT
3. HIGH LOAD PURLIN SPLICE MATERIAL SPECIFICATIONS: AND THE BUILDING OFFICIAL.
PERMITTED.
- A-36 HRS P&O PLATE C. UPON COMPLETION OF THE ASSIGNED WORK, THE SPECIAL INSPECTOR
10. CURE EXPOSED CONCRETE FOR A MINIMUM OF 7 DAYS IN ACCORDANCE WITH
- THICKNESS: 0.179IN SHALL COMPLETE AND SIGN A FINAL REPORT CERTIFYING THAT TO THE
ACI 301 PROCEDURES IN ORDER TO PREVENT CRACKING. CURE WITH CURING
- COATING DESIGNATION: POWDER COAT SILVER T37-GR105 BEST OF THE INSPECTOR'S KNOWLEDGE, THE WORK IS IN CONFORMANCE
AND SEALING COMPOUND, MOIST CURING, MOISTURE-RETAINING COVER
(MATERIAL CERTIFICATION REQUIRED) WITH THE APPROVED PLANS AND SPECIFICATIONS, AND THE APPLICABLE
CURING, OR COMBINATIONS THEREOF. IF CURING COMPOUND IS USED, APPLY
4. PURLIN SPLICE MATERIAL SPECIFICATIONS: WORKMANSHIP PROVISIONS OF THE CODE.
AT A RATE SPECIFIED BY THE MANUFACTURER.
- A-36 HRS P&O PLATE
11. CONCRETE COMPRESSIVE STRENGTH AND SLUMP SHALL BE TESTED PER ASTM
- THICKNESS: 0.380IN
C31, C39 AND C143. PROVIDE 3 CYLINDERS PER TEST FOR EACH DAY'S
- COATING DESIGNATION: POWDER COAT SILVER T37-GR105
CONCRETE PLACEMENT OR AS DIRECTED BY THE ENGINEER. TEST ONE CLEVELAND, OH
(MATERIAL CERTIFICATION REQUIRED)
CYLINDER AT 7 DAYS AND TWO AT 28 DAYS. TESTING SHALL BE DONE BY A 1-(216)-473-5200
5. CARPORT CANTILEVER MATERIAL SPECIFICATIONS:
QUALIFIED TESTING LABORATORY.
- DESIGNATION SS GRADE 50 CLASS 1 (MIN FY = 50 KSI)
12. ALL HOT WEATHER CONCRETING SHALL MEET THE REQUIREMENTS OF ACI 305; CUSTOMER:

- THICKNESS: 0.1090IN
AND ACI 306 FOR COLD WEATHER CONCRETING.
- COATING DESIGNATION: G90 GALVINIZATION (ASTM A653) PROJECT:

(MATERIAL CERTIFICATION REQUIRED)


6. TEK SCREW CLAMP MATERIAL SPECIFICATIONS:
- DESIGNATION SS GRADE 50 CLASS 1 (MIN FY = 50 KSI) TITLE:

GENERAL STRUCTURAL NOTES


- THICKNESS: 0.1090IN REVISION: DATE: DRAWN BY:

- COATING DESIGNATION: G90 GALVINIZATION (ASTM A653)


SHEET SIZE: ENGINEER/REVIEW:
(MATERIAL CERTIFICATION REQUIRED) D-SIZE ADAM M.
SCALE: SHEET: OF:

VARIES 1 3
PE STAMP
2 1 6
GENERAL INFORMATION
TYP AND SYSTEM DETAILS

1 7 GENERAL INFORMATION:
SITE ADDRESS:

TYP AZIMUTH:
SYSTEM TYPE:

2 TOTAL SYSTEM SIZE:


TOTAL # OF MODULES:

3 3 MODULE TILT:
N-S SPACING:
E-W GAP BETWEEN MOD.:

TYP E-W GAP BETWEEN ARRAYS:

BUILDING CODES:

19'-0"
4 STRUCTURAL:
EMBEDMENT:
SOIL CLASS:

8 LOADS:
5 203 5
DESIGN WIND SPEED:

TYP 3 SEC GUST EFFECT:


RISK CATEGORY:

6 TYP EXPOSURE:
MWFRS WIND LOAD (SOUTH WIND):
PSF
MWFRS WIND LOAD (NORTH WIND):
PSF

7 DESIGN SNOW LOAD:


MODULE DEAD LOAD:
PSF
PSF

MANUFACTURER'S TOLERANCES:
LATERAL POST PLACEMENT
8 (X-Z PLANE):
±2.0" FOR TILT ANGLES < 20°
±1.5" FOR TILT ANGLES ≥ 20°
LATERAL POST PLACEMENT
* SHORTER W16X40 FOR 60 CELL (WELDMENT) ALSO AVAILABLE 2 4 (Y-Z PLANE): ±4.0" WITHIN ARRAY
POST HEIGHT VARIATION
(X-Y PLANE): ±0.5"
TYP POST VERTICALITY TOLERANCE:
< 2.0° ALL DIRECTIONS
POST ROTATIONAL TOLERANCE:
±5.0°
ARRAY TILT ANGULAR TOLERANCE:
±2.0°
6 204
1
TYP
MODULE INFORMATION
MODULE: GENERIC
MODULE MODEL: 72 CELL
MODULE SIZE: 78.15"x39"x1.81"
MODULE WEIGHT: 57.3 LBS
MODULE OUTPUT: VARIES

2 T H I S D R A W I N G I S T H E P R O P E R T Y O F D P W ,
DIRECT POWER & WATER CORPORATION AND CANNOT BE USED, COPIED, OR DISCLOSED WITHOUT
P E R M I S S I O N .

8 DISCLAIMER OF LIABILITY
SINCE THE CONDITIONS OF USE AND MAINTENANCE OF THE UNIT ARE BEYOND THE CONTROL OF
DIRECT POWER & WATER CORPORATION, THE COMPANY DOES NOT ASSUME RESPONSIBILITY AND

3 5
E X P R E S S L Y
LIABILITY FOR LOSS, DAMAGE, OR EXPENSE ARISING
D I S C L A I M S

TYP
19'-0"
O U T O F O R I N A N Y W A Y C O N N E C T E D W I T H T H E
U S E , O R M A I N T E N A N C E O F T H I S S Y S T E M .

201 TYP TYP


PLEASE NOTE
IF PLAN VIEW WAS DERIVED BY HAND SCALING A PRINT IMAGE.
THE RESULTING ACCURACY CANNOT BE GUARANTEED.
CUSTOMER ASSUMES ALL RESPONSIBILITY IN VERIFYING
D E S I G N T O A C T U A L C O N S T R U C T I O N C O N D I T I O N S .

202 REVISION TABLE

1 3 REV: - BY: - APP BY: - DATE: -

101 TYP

TYP
7
1 6 2
TYP CLEVELAND, OH
1-(216)-473-5200
CUSTOMER:

205 PROJECT:

CARPORT SECTION VIEW


N TITLE:

STRUCTURE SECTION & PLAN VIEWS


REVISION:

SHEET SIZE:
DATE: DRAWN BY:

ENGINEER/REVIEW:

D-SIZE ADAM M.
SCALE: SHEET: OF:

VARIES 2 3
STEEL COLUMN - TYPICAL
24"Ø 1'-8"
CONCRETE 1 1/4" X 12" X 1'-6" STEEL
FTG BASE PLATE WITH (6) 1"Ø
ANCHOR BOLTS - EMBED
#3 TIES
ANCHOR BOLTS 18" MIN. CEE PURLIN FOR
CARPORT - TYPICAL PE STAMP

GENERAL INFORMATION
4 1/2" AND SYSTEM DETAILS

1'-0"
GENERAL INFORMATION:
SITE ADDRESS:

AZIMUTH:
SYSTEM TYPE:
1 1/2"
TYP CONNECT W16 X 40 TOTAL SYSTEM SIZE:
WELDMENT TO HSS CONNECT CEE TOTAL # OF MODULES:
12 X 6 X 1/2 COLUMN W16 X 40 WELDMENT PURLIN TO W16 X 40 MODULE TILT:
WELDNENT WITH WELDMENT WITH N-S SPACING:
E-W GAP BETWEEN MOD.:
TUBE STEEL COLUMN (12) 1" DIAMETER 3/4" BEAM CLAMP W16 X 40 WELDMENT E-W GAP BETWEEN ARRAYS:
BOLTS - TYPICAL HSS 12 X 6 X1/2 - TYPICAL
STEEL BASE PLATE - SEE COLUMN WELDMENT BUILDING CODES:
STRUCTURAL:
PLAN VIEWS FOR SPECIFICS EMBEDMENT:

DOUBLE NUTS 201 202 SOIL CLASS:

LOADS:
DESIGN WIND SPEED:
1 1/2" ± DRYPACK
3 SEC GUST EFFECT:
RISK CATEGORY:
FINISHED GRADE EXPOSURE:
MWFRS WIND LOAD (SOUTH WIND):
PSF
CEE PURLIN FOR MODULES NOT SHOWN MWFRS WIND LOAD (NORTH WIND):
CARPORT - TYPICAL FOR CLARITY - TYPICAL PSF
DESIGN SNOW LOAD: PSF
MODULE DEAD LOAD: PSF
72 CELL MODULE
10'-2" (AT EXT. COL. W/ NO CONC. SLAB RESTRAINT AT GRADE)

12'-9" (AT INT. COL. W/ NO CONC. SLAB RESTRAINT AT GRADE)


MANUFACTURER'S TOLERANCES:

6'-2" (AT EXT. COL. W/ CONC. SLAB RESTRAINT AT GRADE)

7'-9" (AT INT. COL. W/ CONC. SLAB RESTRAINT AT GRADE)


(3) #3 TIES FRAME - TYPICAL LATERAL POST PLACEMENT
(X-Z PLANE):
IN UPPER 5" ±2.0" FOR TILT ANGLES < 20°
±1.5" FOR TILT ANGLES ≥ 20°
OF PIER LATERAL POST PLACEMENT
SELF DRILLING SCREW (Y-Z PLANE): ±4.0" WITHIN ARRAY
CONCRETE PIER CLAMP - TYPICAL POST HEIGHT VARIATION
(X-Y PLANE): ±0.5"
FOUNDATION CONNECT SELF DRILLING POST VERTICALITY TOLERANCE:
CONNECT MODULE SCREW CLAMP TO CEE < 2.0° ALL DIRECTIONS
TO TEK SCREW PURLIN WITH (2) 1/4" POST ROTATIONAL TOLERANCE:
±5.0°
CLAMP WITH 1/4" DIAMETER SELF-DRILLING ARRAY TILT ANGULAR TOLERANCE:
DIAMETER BOLTS SCREWS - TYPICAL ±2.0°
- TYPICAL
VERTICAL BARS
72 CELL MODULE
#3 TIES GLASS - TYPICAL
MODULE INFORMATION
MODULE: GENERIC
MODULE MODEL: 72 CELL
MODULE SIZE: 78.15"x39"x1.81"
MODULE WEIGHT: 57.3 LBS
MODULE OUTPUT: VARIES
3" CLEAR 203 T H I S D R A W I N G I S T H E P R O P E R T Y O F D P W ,

2'-0" Ø DIRECT POWER & WATER CORPORATION AND CANNOT BE USED, COPIED, OR DISCLOSED WITHOUT
P E R M I S S I O N .

DISCLAIMER OF LIABILITY
SINCE THE CONDITIONS OF USE AND MAINTENANCE OF THE UNIT ARE BEYOND THE CONTROL OF
DIRECT POWER & WATER CORPORATION, THE COMPANY DOES NOT ASSUME RESPONSIBILITY AND
E X P R E S S L Y D I S C L A I M S

CONCRETE PIER CEE PURLIN FOR LIABILITY FOR LOSS, DAMAGE, OR EXPENSE ARISING
O U T O F O R I N A N Y W A Y C O N N E C T E D W I T H T H E
U S E , O R M A I N T E N A N C E O F T H I S S Y S T E M .

FOUNDATION CARPORT - TYPICAL PLEASE NOTE


IF PLAN VIEW WAS DERIVED BY HAND SCALING A PRINT IMAGE.

CEE PURLIN FOR 3/4" BEAM CLAMP


THE RESULTING ACCURACY CANNOT BE GUARANTEED.
CUSTOMER ASSUMES ALL RESPONSIBILITY IN VERIFYING

CARPORT - TYPICAL PURLIN SPLICE D E S I G N T O A C T U A L C O N S T R U C T I O N C O N D I T I O N S .

TYPICAL - TYPICAL
135° HOOK, TYPICAL REVISION TABLE
3/4"BEAM CLAMP REV: - BY: - APP BY: - DATE: -
- TYPICAL -
W16 X 40 WELDMENT
#3 TIES AT 16" O.C., HIGH LOAD PURLIN
MAXIMUM SPLICE - TYPICAL END OF CEE
CONNECT HIGH PURLIN FOR
(5) #5 VERTICAL BARS CARPORT
LOAD PURLIN
SPLICE TO CEE - TYPICAL
PURLIN FLANGE
AND W16X40
FLANGE WITH CONNECT HIGH LOAD
CONTRACTORS OPTIONS: 3/4" BEAM CLAMP PURLIN SPLICE TO CEE
- TYPICAL PURLIN FLANGE WITH CONNECT PURLIN
1) 7/8"Ø OR 1"Ø THREADED RODS WITH PLATE WASHERS AND DOUBLE NUTS
(18) 1/4" DIAMETER SELF SPLICE TO CEE
CAN BE USED IN LIEU OF STANDARD ANCHOR BOLTS. -DRILLING SCREWS PURLIN FLANGE
2) 36"Ø CONCRETE FOUNDATION CAN BE USED IN LIEU OF 24"Ø. SEE EMBEDMENT - TYPICAL AND W16X40
DEPTHS BELOW; CARPORT CLEVELAND, OH
FLANGE WITH
8'-10" (AT EXT. COL. W/ NO CONC. SLAB RESTRAINT AT GRADE) 3/4" BEAM CLAMP CANTILEVER 1-(216)-473-5200
5'-5" (AT EXT. COL. W/ CONC. SLAB RESTRAINT AT GRADE) - TYPICAL - TYPICAL CUSTOMER:

11'-2" (AT INT. COL. W/ NO CONC. SLAB RESTRAINT AT GRADE)


6'-9" (AT INT. COL. W/ CONC. SLAB RESTRAINT AT GRADE) PROJECT:

REINFORCING STEEL REQUIREMENTS FOR 36"Ø;


(8) #5 VERTICAL BARS (IN LIEU OF 5)
TITLE:
#3 TIES ARE REQUIRED TO BE SPACED AT 12" O.C. MAX. STRUCTURE DETAILS

101 204 202 REVISION:

SHEET SIZE:
DATE: DRAWN BY:

ENGINEER/REVIEW:

D-SIZE ADAM M.
SCALE: SHEET: OF:

VARIES 3 3