Medium Voltage Cable | N2XSEY XLPE PVC - 6/10 (12)kV Cable

N2XSEY XLPE PVC - 6/10 (12)kV Cable

Eland Product Group: A9X

APPLICATION CABLE STANDARDS


Medium voltage cables for distribution networks; also for DIN VDE 0276-620, HD 620 S2, DIN EN 60228,
connection to generation units and plant and process connection. BS EN/IEC 60332-1-2, BS EN/IEC 60502
To be laid directly in ground, outdoors, indoors and in cable ducts
e.g. in industrial and switchboard plants.

The electrical and dimensional properties of this product are measured by the

CONSTRUCTION Technical and Quality Assurance department at the Eland Cables laboratory. Cable
performance in respect of conductor resistance, construction quality (workmanship),
Conductor dimensional consistency, and other parameters are verified to published standards
Stranded copper conductor and approved product drawings. Conformance to RoHS (Restriction of the use of
Hazardous Substances) is determined and confirmed.

Inner Layer
Semi-conductive material
CHARACTERISTICS
Insulation Voltage Rating (Uo/U)(Um)
XLPE (Cross-Linked Polyethylene) 6/10 (12)kV

Outer Layer Test Voltage


Semi-conductive material and tape 21kV

Screen Temperature Rating


Copper wires Fixed: -20°C to +70°C
Flexed: -5°C to +70°C
Sheath
PVC (Polyvinyl Chloride) Short Circuit Temperature
+250°C

Minimum Bending Radius


15 x overall diameter

Sheath
Red
ISSUE NO 01-03 -2014

UK T 020 7241 8787 | F 020 7241 8700 | sales@elandcables.com | www.elandcables.com


technicalspecification | 1 of 2
International T +44 20 7241 8740 | F +44 20 7241 8700 | international@elandcables.com
Find this product online: elandcables.com | Cables & Accessories
Medium Voltage Cable | N2XSEY XLPE PVC - 6/10 (12)kV Cable

DIMENSIONS
ELAND PART NO. NO. OF NOMINAL CROSS NOMINAL OVERALL NOMINAL WEIGHT
CORES SECTIONAL AREA DIAMETER kg/km
mm
Conductor Copper Wire Screen
mm² mm²

A9X10KV3035 3 35 RM/16 49 2600


A9X10KV3050 3 50 RM/16 51 2900
A9X10KV3070 3 70 RM/16 55 3350
A9X10KV3095 3 95 RM/16 58 4200
A9X10KV3120 3 120 RM/16 62 5050
A9X10KV3150 3 150 RM/25 66 6000
A9X10KV3185 3 185 RM/25 69 7200
A9X10KV3240 3 240 RM/25 75 9000

ELECTRICAL CHARACTERISTICS
ELAND PART NO. NO. OF NOMINAL CROSS CURRENT CARRYING CAPACITY
CORES SECTIONAL AREA

Conductor Copper Wire Screen In Ground In Air


mm² mm² Amps Amps

A9X10KV3035 3 35 RM/16 213 213


A9X10KV3050 3 50 RM/16 220 236
A9X10KV3070 3 70 RM/16 261 265
A9X10KV3095 3 95 RM/16 312 322
A9X10KV3120 3 120 RM/16 355 370
A9X10KV3150 3 150 RM/25 399 420
A9X10KV3185 3 185 RM/25 451 481
A9X10KV3240 3 240 RM/25 523 566
ISSUE NO 01-03 -2014

The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of
publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.

UK T 020 7241 8787 | F 020 7241 8700 | sales@elandcables.com | www.elandcables.com


2 of 2 | technicalspecification
International T +44 20 7241 8740 | F +44 20 7241 8700 | international@elandcables.com