ANNEXURE For FOAM SYSTEM

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 1

EFFICIENT FIRE SERVICES

Survey no 144, Ganesh Nagar Ind. Area. Phursungi, Pune 412 308. Maharashtra
Ph. 20-60502050/60 Cell : 9822008747 Email : anandgadekar@hotmail.com; efficientfire.office@gmail.com

ANNEXURE - FOAM SYSTEM

SIZE FOAM SOLUTION PROPOSED FLOW RATE OF FOAM MINIUM K FACTOR MINIUM K FACTOR FOAM COMPOUND REQU
SEAL AREA M2 DESIGN SIZE OF MIN OPERATION (L
REQUIRED LPM SOLUTION THROUGH EACH PRESSURE REQUIRED PRESSURE REQUIRED SIZE OF
SR. ROOF Formula = DENSITY Formula = SEAL NUMBER OF FOAM MAKER (LPM) REQUIRED AT Formula = Foam INLET OF REQUIRED AT Formula = Foam FOAM
NO. TANK NO (3.141/4) x D2 (LPM/M2) FOAM FOAM Foam Solution Rate (lpm)
4.1 AREA x DESIGN MAKERS Formula = SEAL AREA x INLET OF FOAM Rate / Pressure MAKER INLET OF FOAM Rate / Pressure MAKER
DIA PI VALUE DENSITY DESIGN DENSITY MAKER (Root 3.5 = 1.87) INDUCTOR (Root 6.5 = 2.54) x Foam Induction Rate (%)
x Time

1 8.92 3.1415 62.49 4.1 256.21 1 256.21 3.5 kg/cm2 137.01 65 NB 6.5 kg/cm2 100.87 65 NB 230.59

1 10 3.1415 78.54 4.1 322.00 1 322.00 3.5 kg/cm2 172.19 65 NB 6.5 kg/cm2 126.77 65 NB 289.80