Prepare : CPK

ENGINEERING CONSULTANCY
POLYACRYLAMIDE SERVICES
Review : CPK Rev A

PLANT MECHANICAL DATASHEET FOR


Approve : KK Sheet 1 of 2
STEAM TRAPS Date :25.06.19

MECHANICAL DATASHEET FOR STEAM TRAPS

PROJECT
POLYACRYLAMIDE PLANT

A 25.06.19 ISSUED FOR APPROVAL CPK CPK KK


REV REV DATE PURPOSE PREPD REVWD APPD
POLYACRYLAMIDE PLANT MECHANICAL DATASHEET FOR STEAM TRAPS

POLYACRYLAMIDE PLANT
REV. DATE DESCRIPTION BY PROJECT NAME:
A 25-Jun-19 Issued For Approval KK LOCATION:
NAME Steam Traps TAG NUMBER

GENERAL
TAG NO. ST-001-008 SIZE (in) 1"
TYPE Thermodynamic Trap SERVICE Steam
SPEC - QTY. 8 Nos
RATING 150#
OPERATING CONDITIONS
DESIGN PRESSURE (barg) 15 CORROSION ALLOWANCE (inch) 0.0625
DESIGN TEMPERATURE (ºC) -2 / 320 DENSITY (kg/m3) 5.638
OPERATING PRESSURE (barg) 10.0
OPERATING TEMPERATURE (ºC) 184
CONSTRUCTION
END CONNECTION Socket MANUFACTURER TBD
UPSTREAM PRESSURE (barg) 10 STRAINER YES
DOWNSTREAM PRESSURE (barg) ATM CONDENSATE LOAD (kg) 72.5

CONSTRUCTION MATERIAL

BODY ASTM A 743 Gr CA - 40 SEAT ASTM A 743 Gr CA - 40

CAP ASTM A 743 Gr CA - 40 STRAINER MESH Stainless Steel ASTM A 240 SS 304

DISC ASTM A 743 Gr CA - 40


OTHERS
"A" (in) VTC WEIGHT(LB) VTC
OVERALL DIMENSION WITH
"B"(in) VTC
G.A.DRAWING
"C" (in) VTC
INSPECTION AND TEST
HYDROSTATIC TEST YES TEST PRESSURE AS PER ASME B31.3
PNEUMATIC TEST NO
NDT AS REQUIRED
NOTE
(1) VTC - Vendor to Confirm
(2) Materails indicted shows minimum matullurgical requirements.
(3) Submission of GA Drawing for approval along with TAG no.
(4) Operation & Maintenance manual (1 No.) to be submitted (If applicable)
(5) Spare list (1 No.) to be submitted
(6) Guarantee / Warrantee Certificate to be submitted
(8) Painting as per Vendor Recommendation

Tag Line No P & ID Size End Condition Qty