Ac Resistance and Reactance 50 HZ

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6

AC Resistance

Typical AC resistances for copper and aluminium insulated cables operating at 50Hz are based on values given in AS/NZS 3008

Contents
1 Multicore Cables
1.1 Copper Conductors
1.2 Aluminium Conductors
2 Single Core Cables

Multicore Cables

Copper Conductors

Note that for tinned copper conductors, a scaling factor of 1.01 should be applied.

AC Resistance (Ώ/km) of Multicore Copper Cables

Size (mm2)
Circular Conductors Shaped Conductors
o o
45 C 60 C 75oC 90oC o
110 C o
45 C 60oC 75oC 90oC
1 23.3 24.5 25.8 27 28.7 - - - -
1.5 14.9 15.7 16.5 17.3 18.4 - - - -
2.5 8.14 8.57 9.01 9.45 10 - - - -
4 5.06 5.33 5.61 5.88 6.24 - - - -
6 3.38 3.56 3.75 3.93 4.17 - - - -
10 2.01 2.12 2.23 2.33 2.48 - - - -
16 1.26 1.33 1.4 1.47 1.56 1.26 1.33 1.4 1.47
25 0.799 0.842 0.884 0.927 0.984 0.799 0.842 0.884 0.927
35 0.576 0.607 0.638 0.669 0.71 0.576 0.607 0.638 0.669
50 0.426 0.449 0.471 0.494 0.524 0.426 0.448 0.471 0.494
70 0.295 0.311 0.327 0.343 0.364 0.295 0.311 0.327 0.342
95 0.214 0.225 0.236 0.248 0.262 0.213 0.224 0.236 0.247
120 0.17 0.179 0.188 0.197 0.209 0.17 0.179 0.187 0.196
150 0.139 0.146 0.153 0.16 0.17 0.138 0.145 0.153 0.16
185 0.112 0.118 0.123 0.129 0.136 0.111 0.117 0.123 0.128
240 0.087 0.0912 0.0955 0.0998 0.105 0.0859 0.0902 0.0945 0.0988
300 0.0712 0.0745 0.0778 0.0812 0.0852 0.0698 0.0732 0.0766 0.08
400 0.058 0.0605 0.063 0.0656 0.0685 0.0563 0.0589 0.0615 0.0641
500 0.0486 0.0506 0.0525 0.0544 0.0565 0.0465 0.0485 0.0508 0.0526

Aluminium Conductors
AC Resistance (Ώ/km) of Multicore Aluminum Cables
2
Size (mm )
Circular Conductors Shaped Conductors
o
45 C 60oC 75oC o
90 C o
45 C 60oC 75oC 90oC
16 2.1 2.22 2.33 2.45 2.1 2.22 2.33 2.45
25 1.32 1.39 1.47 1.54 1.32 1.39 1.47 1.54
35 0.956 1.01 1.06 1.11 0.956 1.01 1.06 1.11
50 0.706 0.745 0.784 0.822 0.706 0.745 0.783 0.822
70 0.488 0.515 0.542 0.569 0.488 0.515 0.542 0.568
95 0.353 0.373 0.392 0.411 0.353 0.372 0.392 0.411
120 0.28 0.295 0.31 0.325 0.279 0.295 0.31 0.325
150 0.228 0.241 0.253 0.265 0.228 0.24 0.253 0.265
185 0.182 0.192 0.202 0.212 0.182 0.192 0.202 0.211
240 0.14 0.148 0.155 0.162 0.139 0.147 0.154 0.162
300 0.113 0.119 0.125 0.131 0.112 0.118 0.124 0.13
400 0.0897 0.0943 0.0988 0.103 0.0886 0.0932 0.0978 0.102
500 0.073 0.0765 0.08 0.0835 0.0716 0.0752 0.0788 0.0824

Single Core Cables


AC Resistance (Ώ/km) of Single Core Cables
Size (mm2)
Aluminum Conductors Copper Conductors
45oC 60oC 75oC 90oC 45oC 60oC 75oC 90oC 110oC
1 - - - - 23.3 24.5 25.8 27 28.7
1.5 - - - - 14.9 15.7 16.5 17.3 18.4
2.5 - - - - 8.14 8.57 9.01 9.45 10
4 - - - - 5.06 5.33 5.61 5.88 6.24
6 - - - - 3.38 3.56 3.75 3.93 4.17
10 - - - - 2.01 2.12 2.23 2.33 2.48
16 2.1 2.22 2.33 2.45 1.26 1.33 1.4 1.47 1.56
25 1.32 1.39 1.47 1.54 0.799 0.842 0.884 0.927 0.984
35 0.956 1.01 1.06 1.11 0.576 0.607 0.638 0.668 0.71
50 0.706 0.745 0.783 0.822 0.426 0.448 0.471 0.494 0.524
70 0.488 0.515 0.542 0.568 0.295 0.311 0.327 0.342 0.363
95 0.353 0.372 0.392 0.411 0.213 0.225 0.236 0.247 0.262
120 0.279 0.295 0.31 0.325 0.17 0.179 0.188 0.197 0.208
150 0.228 0.24 0.253 0.265 0.138 0.145 0.153 0.16 0.169
185 0.182 0.192 0.202 0.212 0.111 0.117 0.123 0.129 0.136
240 0.14 0.147 0.155 0.162 0.0862 0.0905 0.0948 0.0991 0.105
300 0.113 0.119 0.125 0.13 0.0703 0.0736 0.077 0.0803 0.0846
400 0.089 0.0936 0.0981 0.103 0.0569 0.0595 0.062 0.0646 0.0677
500 0.0709 0.0744 0.0779 0.0813 0.0467 0.0487 0.0506 0.0525 0.0547
630 0.0571 0.0597 0.0623 0.0649 0.0389 0.0404 0.0418 0.0432 0.0448

Note (1): for tinned copper conductors, a scaling factor of 1.01 should be applied.
Back to Low Voltage Cable Data Reference

AC Reactance
Typical AC reactances for copper and aluminium insulated cables operating at 50Hz are based on values given in AS/NZS 3008.

Multicore Cables

AC Reactance (Ώ/km)

Size (mm2) PVC XLPE


EPR
Circular (1) Shaped (1) Circular (1) Shaped (1)

1 0.119 - 0.139 0.114 -


1.5 0.111 - 0.129 0.107 -
2.5 0.102 - 0.118 0.0988 -
4 0.102 - 0.11 0.093 -
6 0.0967 - 0.104 0.0887 -
10 0.0906 - 0.0967 0.084 -
16 0.0861 0.0794 0.0913 0.0805 0.0742
25 0.0853 0.0786 0.0895 0.0808 0.0744
35 0.0826 0.0761 0.0863 0.0786 0.0725
50 0.0797 0.0734 0.0829 0.0751 0.0692
70 0.077 0.071 0.0798 0.0741 0.0683
95 0.0766 0.0706 0.079 0.0725 0.0668
120 0.0743 0.0685 0.0765 0.0713 0.0657
150 0.0745 0.0687 0.0765 0.0718 0.0662
185 0.0744 0.0686 0.0762 0.072 0.0663
240 0.0735 0.0678 0.0751 0.0709 0.0653
300 0.0732 0.0675 0.0746 0.0704 0.0649
400 0.0728 0.0671 0.074 0.0702 0.0647
500 0.0723 0.0666 0.0734 0.07 0.0645

Note (1): Circular or shaped refers to the conductor's cross-sectional shape

Single Core Cables


AC Reactance (Ώ/km)
2
Size (mm )
PVC EPR XLPE
(1) (1) (1)
Flat Trefoil Flat Trefoil Flat Trefoil
1 0.184 0.168 0.194 0.179 0.181 0.166
1.5 0.172 0.157 0.183 0.167 0.17 0.155
2.5 0.159 0.143 0.168 0.153 0.156 0.141
4 0.152 0.137 0.157 0.142 0.146 0.131
6 0.143 0.128 0.148 0.133 0.138 0.123
10 0.134 0.118 0.138 0.123 0.129 0.114
16 0.126 0.111 0.13 0.114 0.122 0.106
25 0.121 0.106 0.125 0.109 0.118 0.102
35 0.117 0.101 0.12 0.104 0.113 0.0982
50 0.111 0.0962 0.114 0.0988 0.108 0.0924
70 0.107 0.0917 0.109 0.0941 0.104 0.0893
95 0.106 0.0904 0.108 0.0924 0.102 0.0868
120 0.102 0.087 0.104 0.0889 0.0996 0.0844
150 0.102 0.0868 0.104 0.0885 0.0996 0.0844
185 0.101 0.0862 0.103 0.0878 0.0988 0.0835
240 0.0999 0.0847 0.101 0.0861 0.097 0.0818
300 0.0991 0.0839 0.1 0.0852 0.0961 0.0809
400 0.0982 0.0829 0.0993 0.0841 0.0955 0.0802
500 0.0973 0.082 0.0983 0.083 0.0948 0.0796
630 0.0952 0.08 0.0961 0.0809 0.094 0.0787

Note (1): Single core cables are laid flat and touching

Back to Low Voltage Cable Data Reference


alues given in AS/NZS 3008.1.
alues given in AS/NZS 3008.1.

You might also like