Short Circuit Calculator
Short Circuit Calculator
Short Circuit Calculator
PRIMARY
132 kV I FLA= 0.196824
I sc= 1457.955
I sc= 1.457955
Z% 13.5
Mbase
(MVA) 45
SECONDARY
I FLA= 0.787296
33 kV I sc= 5831.821
I sc= 5.831821
kA
A
kA
kA
A
kA
How to calculate Isc for transformer
PRIMARY
22 kV I FLA= 0.0656079851
I FLA= 65.607985135
I sc= 1093.4664189
I sc= 1.0934664189
Z% 6
Mbase
(MVA) 2.5
SECONDARY
I FLA= 3.4780136698
I FLA= 3478.0136698
0.415 kV I sc= 57966.894497
I sc= 57.966894497
kA
A
A
kA
kA
A
A
kA
How to calculate Isc for transformer
PRIMARY
132 kV I FLA= 0.1968239554
I FLA= 196.82395541
I sc= 1457.9552252
I sc= 1.4579552252
Z% 13.5
Mbase
(MVA) 45
SECONDARY
I FLA= 0.7872958216
I FLA= 787.29582162
33 kV I sc= 5831.8209009
I sc= 5.8318209009
kA
A
A
kA
kA
A
A
kA
6MVA,
Dy11Y11,
±2X2.5%
33kV 0.655kV
I primary = 6𝑀𝑉𝐴/
(√3∗33𝑘𝑉)
= 104.97 A
I secondary 6𝑀𝑉𝐴/(√3∗0.655𝑘𝑉)
=
= 5288 A