Loop Cabling for Loudspeakers

Loudspeaker groups in the field, fed by centralized amplifiers from the system cabinet, are
powered from two sides as loop. This way, a simple line break cannot cause a failure of several
loudspeakers. Together with the line monitoring modules a line break will be detected easily and
reported to the system for failure indication. The loops are wired to the Loop Module Terminal
which is equipped with the needed terminals. This module is controlled by the dedicated line
monitoring module.
Amplifier

100V 0V

ZONE SELECTION
RELAY WITH LINE
MONITORING
MODULE
Control signal

LOOP
MONITORING
TERMINAL

Central Exchange
external

3.2.3.2 Intercoms
All external INDUSTRONIC digital subscribers like outdoor and indoor stations are monitored by
the INTRON-D plus. The line and the station itself will be monitored continuously and any failure
will trigger a system monitoring information.

System Description NExBTL Plant 19 / 61


Doc. no. FDE-501-949-100 • V00A • EN • 13.03.2020