HV Generation and Testing 1.0 Slides PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 43

BEK 4113/BEX 44503

High Voltage Engineering


‘‘HV
HV Generation & Testing 1.0
1.0’’

DR. RIE

BEE 3243 Electric Power Systems – Module 1

Lecture Plan

Objectives

To provide student with the knowledge of the


High Voltage generation

Also to introduce required testing techniques on


insulation that used the generation equipments

1
BEE 3243 Electric Power Systems – Module 1

Lecture Plan
Learning Outcomes

At the end of this subject, the student should have the


ability to adopt the knowledge as follows:

(1) Understand the HV generation types

(2) Plan high voltage measurement and testing works of


high voltage electrical equipment

(3) Perform high voltage experiment setup or project to


complete a specific measurement

(4) Show concern to safety regulations in high voltage


measurement and testing works 3

BEE 3243 Electric Power Systems – Module 1

Lecture Plan

Syllabus

• Subject 2 – Generation of High Voltages


• Subject 3 – High Voltage Measurements
and Diagnostic Testing of Insulation

2
BEE 3243 Electric Power Systems – Module 1

HV Generations & Testing: Introduction

• High voltage is a field of engineering linking the


scientific principles and industrial practice.
• The major use of high voltage is in the area of power
systems.
• Increasing demand in power requires modern-system
operates at higher voltage.
• DC is used in long transmission lines and equipments
such as electron microscope, x-ray units, particles
accelerator, electrostatic precipitators and etc.

• Power system equipments (e.g. transformer, circuit


breaker, insulators, bushings etc.), cables and
overhead line with higher ac voltage ratings.
5

BEE 3243 Electric Power Systems – Module 1

HV Generations & Testing: Problem

• Erecting the higher voltage levels exposing


equipment with high voltage / current stresses
• Major concern in insulating / separating these
equipment from the potential and earthed
structure / object
• The insulation provided must not only be able to
withstand the normal system voltage (with factor
of safety) but also from abnormal overvoltages
(i.e. impulse stresses)
• In this case, the system exposes with high
stresses magnitude from power frequency,
lightning and switching overvoltages
6

3
BEE 3243 Electric Power Systems – Module 1

HV Generations & Testing: What to do?

• Hence, these equipments need to be


tested at higher voltages (normal and
overvoltages levels) before they can
actually put into use.

• It is therefore imperative that there must


be high voltage generators available to
test an insulation system.

BEE 3243 Electric Power Systems – Module 1

HV Generations: Types

The common types of High Voltage


generators:

1) AC Generators

2) DC Generators

3) Impulse Generators

j|ÄÄ ux w|ávâááxw ÄtàxÜ


8

4
BEE 3243 Electric Power Systems – Module 1

Part 1

**High Voltage Testing**

BEE 3243 Electric Power Systems – Module 1

High Voltage Testing: Introduction

• Power system equipment must withstand not only the


rated voltage (Ur), which corresponds to the highest
voltage of particular system, but also overvoltages.

• Accordingly, it is necessary to test HV equipment


during its development stage and commissioning.

• The magnitude and type of test voltage varies with


the rated voltage of particular apparatus.

• The standard methods of measurement of high-


voltage and the basic technique for application for
alternating voltages (AC), direct voltages (DC)
switching impulse voltages (SI) and lightning impulse
voltages (LI) are laid down in the national and
international standards. 10

5
BEE 3243 Electric Power Systems – Module 1

High Voltage Testing

• In general, the amplitude of test voltages are


followed / stated as per national or international
standards (i.e. IEC & IEEE)

• The ‘type’ of high voltage testing will depend on:

- Type of equipment (e.g. transformer, insulator,


circuit breakers etc.)
- Voltage rating (Um, TOV, BSL, BIL etc.)
- Location in which is to be placed (indoor or
outdoor, altitude, coastal, industrial etc.)

11

BEE 3243 Electric Power Systems – Module 1

High Voltage Testing: International Standard

Typically in testing the equipments (e.g.


transformer, insulator), most countries in
Europe (also adopted in Malaysia) used
IEC 60071 ‘Insulation Coordination’
standard as part of the design and
production process.

12

6
BEE 3243 Electric Power Systems – Module 1

Test Required on Insulation According to System


Voltage Level

13

BEE 3243 Electric Power Systems – Module 1

HV Generations & Testing: What to do?

• The levels of voltages used in high


voltage testing can be significantly
higher than those actually seen by test
equipment in practice.

• This is particularly true for AC and DC


voltages tests where a piece of
equipment is stressed with an
overvoltages for a set period of time.
14

7
BEE 3243 Electric Power Systems – Module 1

HV Testing: Types

The common types of High Voltage tests:

1) HVAC tests

2) HVDC tests

3) Lightning impulse tests

4) Switching impulse tests

15

BEE 3243 Electric Power Systems – Module 1

IEC 60071: Classification of Overvoltages by


Magnitude and Duration

16

8
BEE 3243 Electric Power Systems – Module 1

IEC 60071: Classification of Overvoltages Shapes

17

BEE 3243 Electric Power Systems – Module 1

HVAC Tests: General


• Also known as the low frequency tests.
• In these tests, the insulation system required
to have the capability to withstand higher than
usual alternating voltages (AC) that present
on the power system during abnormal
conditions.

• The abnormal conditions could be in the form


of continuous power frequency or temporary
overvoltages or TOV.

• Frequency range at 50 or 60 Hz (countries


depended) for continuous and 10 < f < 500 Hz
for TOV tests. 18

9
BEE 3243 Electric Power Systems – Module 1

HVAC Tests: General

• They are used to indentify manufacturing


defects in the insulation and also used for
partial discharge testing that can identify
incipient insulation fault.

• The voltage magnitude could be at the system


voltage and could reach up to 1.5 p.u for TOV.

• The duration of the test varies from 1 minute


to 1000hrs or more.

19

BEE 3243 Electric Power Systems – Module 1

HVAC Tests: Example HV Application

The testing method using HVAC can be


categorised as:

1) Whole scale insulator test

2) Small scale insulation test

3) Long duration insulation test (small scale)

20

10
BEE 3243 Electric Power Systems – Module 1

HVAC Tests: Example HV Application

1) Whole scale insulation tests:

Typically conducted on ready-made product (e.g.


transformer, insulator etc.).

Can be categorised as dry and wet tests. Indoor


equipment is maybe tested in a dry condition but the
external insulation of outdoor equipment is usually
wet-tested by applying standardised rain to a test
object.

Use the working (normal) and abnormal voltage


stress level. Duration lasted about a minute or more.

Example: breakdown test, corona test.


21

BEE 3243 Electric Power Systems – Module 1

Insulator breakdown during HVAC test

22

11
BEE 3243 Electric Power Systems – Module 1

Insulation Sample Breakdown During


Dry HVAC Test

Flashover

23

BEE 3243 Electric Power Systems – Module 1

Intense Corona Seen During Wet


HVAC Test

Intense Corona

24

12
BEE 3243 Electric Power Systems – Module 1

HVAC Wet Test on Composite Sample

Water sprayed from nozzle

HVAC Wet Test

25

BEE 3243 Electric Power Systems – Module 1

HVAC Wet Test on Composite Sample

Superhero handling the crane

26

13
BEE 3243 Electric Power Systems – Module 1

Visual Data Captured using Night-


Vision Camera

Night-
Night-vision Camera

27

BEE 3243 Electric Power Systems – Module 1

HVAC Test: System Setup

28

14
BEE 3243 Electric Power Systems – Module 1

HVAC Test: Equipment Setup

29

BEE 3243 Electric Power Systems – Module 1

Intense Corona Seen During Wet


HVAC Test

30

15
BEE 3243 Electric Power Systems – Module 1

HVAC Tests: Example HV Application

2) Small scale insulation tests:

Use small scale HV voltage on small scale sample.


Conducted to testing new product, verify
characteristic, scientific analysis etc.

Very popular as they are more economic (small scale


test, reliable, many options).

Duration varies from few second, minutes to long


hours or days.

Example: tracking test, electrical treeing test, partial


discharge test, corona test, electromagnetic test etc.
31

BEE 3243 Electric Power Systems – Module 1

HVAC Test: Tracking Test Experimentation

32

16
BEE 3243 Electric Power Systems – Module 1

Equipments Arrangement for Tracking Test

33

BEE 3243 Electric Power Systems – Module 1

HVAC Test: Tracking Test Experimentation

Proud Superhero

34

17
BEE 3243 Electric Power Systems – Module 1

Tracking: Samples Before Test

35

BEE 3243 Electric Power Systems – Module 1

Tracking: Samples After Test

36

18
BEE 3243 Electric Power Systems – Module 1

Tracking: Thermal Captured

(a)

37
(b)

BEE 3243 Electric Power Systems – Module 1

Tracking: Data for Composite

700
Temperature >620°C 0.14
600
0.12
Leakage current (Amp)
Temperature (Celcius)

500 System cut off >=60mA


Composite 0.1

400
0.08

300
0.06

200 0.04

100 0.02

0 0
0 5 10 15 20 25 30 35 40 45 50 55
Test time (minute)
(a)
Maximum surface temperature Leakage current
38

19
BEE 3243 Electric Power Systems – Module 1

HVAC Tests: Example HV Application


3) Long duration insulation test:
Typically in small scale but could also be in full scale size
sample. Due to time limitation, the samples always being
tested in large number (bulk).

Testing the durability of the product / sample. Sometime


represent acceleration of aging concept of the particular
product over years of service.

Require sustainable supply of power and other resources


for a long duration. May also require large space and long
occupation of the test cage / chamber.

Test could be costly. Typically have group participant (join


venture companies / utilities). Testing could lasted around
1000hrs duration or more.
Example: the salt fog and atmospheric chambers tests. 39

BEE 3243 Electric Power Systems – Module 1

HVAC Salt Fog Test

40

20
BEE 3243 Electric Power Systems – Module 1

HVAC Salt Fog Test: Experiment Setup

41

BEE 3243 Electric Power Systems – Module 1

Clean Fog Test: Experiment Result

Before

After

42

21
BEE 3243 Electric Power Systems – Module 1

HVAC Salt Fog Test: Tested Samples

Surface damaged

No surface damaged
43

BEE 3243 Electric Power Systems – Module 1

HVDC Tests

• The method of the tests are typically similar to the


AC tests, except the voltage supply is in DC
(magnitude equivalent to AC peak voltage).

• The observation result on the sample (e.g.


damage on the surface) usually worst than the
one shown in AC.

• Can be costly as power rectifier system is


required together with normal power supply.
Isolation of the circuit may be hard and
dangerous (non sinusoidal / zero crossing
waveform).
44

22
BEE 3243 Electric Power Systems – Module 1

HVDC Tests: Continue

• Test may be limited to small scale project


(e.g. <100 kV HVDC).

• Less popular for higher / whole scale test


due to cost, safety, less application etc. If
so, interest may come from the high
equipped laboratory with high budget /
funding.

• Usually considered as focus project that


testing the high durable insulation material /
product.
45

BEE 3243 Electric Power Systems – Module 1

HVDC Tests: Continue

• They also used to test alternating equipment


where it not possible to test with an
alternating voltages.

• Normally occurs when on-site tests of highly


capacitive loads such as power cables are
required.

• By using direct voltages, these loads may


be tested using test equipment a fraction of
the size of the alternating voltage required.

46

23
BEE 3243 Electric Power Systems – Module 1

Impulse Tests

The testing method using negative or positive


polarity impulse waveform (either voltage or
current magnitude).

Can be categorised into two:

1) Lightning impulse test

2) Switching impulse test

j|ÄÄ ux w|ávâááxw ÄtàxÜ ÉÇ àÉwtçËá ÄxvàâÜx


47

BEE 3243 Electric Power Systems – Module 1

Impulse Voltages

• Apart from HVAC continuous and TOV,


electrical transmission and distribution system
are subjected to transient overvoltages,
amplitude of which may exceed the peak value
of the normal system voltage by a large
amount.

• The transient overvoltages are due to two


reasons;
- lightning stroke (direct strikes on lines
conductor causing shielding failure,
induced to equipment etc.)
- switching (improper opening / closing
circuit breaker, isolator, switching etc). 48

24
BEE 3243 Electric Power Systems – Module 1

Impulse Voltages

• Overvoltages due to lightning are considered as an


external overvoltages and are dependent on the
system voltages. Also known as the fast-front
overvoltages or FFO.

• Low system voltages less than 132 kV or distribution


lines are more prone to lightning overvoltages impact
(failure by flashover).

• Switching overvoltages are internal overvoltages


cause by switching operations and are also always
related to system operating voltages.

• High voltage equipment or system voltages above


132 kV are prone to switching overvoltages impact.
Also known as slow-front overvoltages or SFO.
49

BEE 3243 Electric Power Systems – Module 1

Impulse Voltages: Continue


• Impulse testing is used to assess the ability of
power system plant to withstand such lightning
and switching overvoltages.

• While it is clear that a test in the laboratory will not


fully represent the overvoltages observed on a
real power system, it does provide a criteria of
pass / fail based on accumulated experience.

• Both lightning and switching impulse test


developed for used in the laboratory use a double
exponential style waveform.

(
V = Vc e −αt − e − βt )
50

25
BEE 3243 Electric Power Systems – Module 1

Double Exponential Waveform

(
V = Vc e −αt − e − βt )

51

BEE 3243 Electric Power Systems – Module 1

Standard Lightning Impulse Voltage

• As mentioned that lightning impulse also known as


the fast-front overvoltages (FFO).

• This is due to very fast rise-time occur on the


waveform shape. The standard waveform used for
testing is 1.2 / 50 μs. The first number (1.2 μs)
represent the rise-time T1 and the second (50 μs) is a
decay-time T2.

• In the standard lightning waveform;

- T1 is determined at about ~93% level (~0.93) just


about to reach the peak voltage / current
magnitude
- T2 is measured at 50% off the peak magnitude.
52

26
BEE 3243 Electric Power Systems – Module 1

Standard Lightning Impulse Voltage Shape

53

BEE 3243 Electric Power Systems – Module 1

Chopped Lightning Impulse Waveforms

(a) FFO waveform chopped on the tail (b) FFO waveform chopped on the front

54

27
BEE 3243 Electric Power Systems – Module 1

Standard Switching Impulse Voltage

• As mentioned that switching impulse also known as


the slow-front overvoltages (SFO).

• This is due to slower rise time occur on the waveform


shape in comparing with the FFO. The standard
waveform used for testing is 250 / 2500μs. The first
number (250 μs) represent the rise-time T1 and the
second (2500 μs) is a decay-time T2.

• In the standard switching waveform;

- T1 is determined at 100% level (1.0) or at a peak


voltage / current magnitude
- T2 is measured also measured at 50% off the
peak magnitude (same as FFO).
55

BEE 3243 Electric Power Systems – Module 1

Standard Switching Impulse Voltage Shape

56

28
BEE 3243 Electric Power Systems – Module 1

Switching & Lightning Impulse Waveforms


for 400kV System Voltage

57

BEE 3243 Electric Power Systems – Module 1

Impulse Waveform: Tutorial

Question:

1)Draw and label a standard lightning impulse


waveform of 1.2/50 μs that having a peak
value of 850 kV.

2)Draw and label a standard switching impulse


waveform of 250/2500 μs that having a peak
value of 750 kV

58

29
BEE 3243 Electric Power Systems – Module 1

Standard Impulse Voltage: Tolerance

• Due to many reasons such as equipments


accuracy / aging, weather condition, humidity etc.,
it may be difficult to generate an accurate impulse
waveforms in the laboratory that can follow
exactly the specific standard 1.2/50 μs of FFO
and 250/2500 μs of SFO.

• Therefore, there are tolerances set-up to these


standard waveforms (rarely applied):

– Lightning impulse waveform: ±30 % for front-


time T1 and of ± 20% for tail-time T2.

– Switching impulse waveform: ±20 % for front-


time T1 and of ± 60% for tail-time T2. 59

BEE 3243 Electric Power Systems – Module 1

Standard Impulse Voltage: Tolerance

• However, researcher / tester usually ensure


the tests are conducted with the highest
accuracy as possible of the standard
waveforms.

60

30
BEE 3243 Electric Power Systems – Module 1

Impulse Waveform: Tutorial

Question:

1)Draw and label a standard lightning impulse


waveform originated from 1.2/50 μs having a
maximum tolerances of front-time T1 and tail-
time T2. The peak voltage value is 850 kV.

2)Draw and label a standard switching impulse


waveform originated from 250/2500 μs
having a minimum tolerances of front-time T1
and tail-time T2. The peak voltage value is
650 kV.
61

BEE 3243 Electric Power Systems – Module 1

Impulse Waveform: Quiz

Question:

1)Draw and label a standard lightning impulse


waveform originated from 1.2/50 μs having a
minimum tolerances of front-time T1 and tail-
time T2. The peak voltage value is 1050 kV.

2)Draw and label a standard switching impulse


waveform originated from 250/2500 μs
having a maximum tolerances of front-time
T1 and tail-time T2. The peak voltage value is
850 kV.
62

31
BEE 3243 Electric Power Systems – Module 1

IEC 60071: Classification of Overvoltages Shapes

63

BEE 3243 Electric Power Systems – Module 1

Non-standard Impulse Test

• As mentioned the standard lightning impulse


waveform is 1.2/50 μs and of 250/2500 μs for
switching.

• These basically the standard impulse waveforms


used to testing the commercial power system
insulation equipments.

• However, there are also testing that used non-


standard lightning and switching impulse waveforms
such as 10/70 μs for FFO and 200/3000 μs for SFO
tests. These are rare applications and more to
research purposes or country regulation basis.

• The voltage shapes of FFO are of 0.1 μs < T1 ≤ 20 μs


and of T2 ≤ 300 μs
64

32
BEE 3243 Electric Power Systems – Module 1

Non-standard Impulse Test: Continue

• The voltage shapes of SFO are of 20 μs < T1 ≤ 5000


μs and of T2 ≤ 300 μs

• The used of non-standard waveforms may be not so


much practical in terms of determining and
standardising the reliability of the particular product
with other international-wise based product.

• Furthermore, a different front-time and tail-time of


waveform requires different value of power
resistances and capacitors. Cost !!

• A researcher / tester may have a problem with the


availability of these resistances and capacitors in the
market and the complexity to determine their correct
values.
65

BEE 3243 Electric Power Systems – Module 1

High Voltage Testing: Overvoltages

Further analysis of the nature and type


of alternating (AC), direct (DC),
switching (SI) and lightning (LI)
overvoltages in power system will be
discussed in ‘Insulation Coordination’
subject.

66

33
BEE 3243 Electric Power Systems – Module 1

Lightning Impulse Tests

• Testing with lightning impulse basically used to simulate


the capability of the insulation component / material in
withstanding the lightning surge strike.

• The usual strike source of a lightning overvoltage is a


lightning strike to an overhead line.

• The result is the production of a fast-front voltage and


travelling waves that propagate along the lines and
could arrive at the substation and without a proper
protection in-place possibly damage the equipment
(e.g. transformer, insulator, breaker etc).

• There are also a possibility direct strikes to the insulator


on the tower and causing damage to it (e.g. damage on
ceramic and glass, puncture on polymeric)
67

BEE 3243 Electric Power Systems – Module 1

Direct Lightning Strike to the Shield Wire of


an Overhead Line

68

34
BEE 3243 Electric Power Systems – Module 1

Lightning Impulse Tests: Continue

• Testing with lightning impulse voltage is important


for the equipment carries a system voltage less
than 132 kV.

• The capability of equipment to withstand the


specific standard lightning impulse level (system
voltage depending) is called ‘Basic Lightning
Insulation Level’ or BIL.

• The impulse voltage (either FFO or SFO) usually


having a magnitude at least about 3 times higher
than the normal system voltage. Therefore larger
clearances are required to prevent unnecessary
flashover and for also used for the safety purposes.
69

BEE 3243 Electric Power Systems – Module 1

Lightning Impulse Tests: Continue

• Thus tests usually require an occupation of large space


area.

• Depending on the voltage magnitude scale, some high


voltage impulse (>1000 kV peak) require a huge
laboratory hall to safely conduct the test (the generator
and measurement devices are also in big size).

• Typically, the tests are conducted on the whole scale


ready-made product (e.g. power transformer, insulator,
surge arrester, circuit breaker etc.) to test its durability.

• Some small scale tests (with lower impulse voltage /


current magnitude) may also conducted following the
HVAC / HVDC tests (e.g. oil test, insulation samples
etc). 70

35
BEE 3243 Electric Power Systems – Module 1

Lightning Impulse Tests: Continue


• The test may be conducted via the positive and
negative polarity impulse waveform.

• The tests with positive polarity are more popular as the


observation damage result typically worst than the one
shown via negative polarity. Also the breakdown
voltage level is lower than that observed by negative
polarity.

• The test duration usually lasted less than a few second


per-test and it typically being repeated many times
depending on the test method (e.g. 80 times repetitions
up-and-down test method for determining U50).

• Similar for HVAC / HVDC, the test also usually


conducted in laboratory in dry and simulate-wet
conditions. 71

BEE 3243 Electric Power Systems – Module 1

Switching Impulse Tests


• Testing with switching impulse basically used to
simulate the capability of the insulation component /
material in withstanding the switching overvoltages
(SFO).

• The usual switching overvoltages source is due to fault


clearing or line opening (line isolation for maintenance
work etc.). These causing an opening / closing the
circuit breaker, switch / isolator devices that could
trigger the switching overvoltages.

• Typically occur in the substation.

• The result is the production of a slow-front voltages and


without a proper protection in-place possibly damage
the substation (e.g. transformer, insulator, breaker etc)
and overhead tower equipment (insulator). 72

36
BEE 3243 Electric Power Systems – Module 1

Switching Flashovers:

Its…movie time!!!!

73

BEE 3243 Electric Power Systems – Module 1

Switching Impulse Tests: Continue

• Testing with switching impulse voltage is important


for the equipment carries a system voltage above
132 kV.

• The capability of equipment to withstand the


specific standard switching impulse level (system
voltage depending) is called the ‘Basic Switching
Insulation Level’ or BSL.

• The impulse voltage (either FFO or SFO) typically


having a magnitude about 3 times higher than the
normal system voltage. Therefore larger
clearances are required to prevent unnecessary
flashover and for the safety purposes.
74

37
BEE 3243 Electric Power Systems – Module 1

Switching Impulse Tests: Continue


• Same as the FFO, switching impulse tests also require
an occupation of large space area.
• Especially for EHV level, the tests under switching
impulse require a huge laboratory hall to safely conduct
the test (the generator and measurement devices are
also in big size). The required clearances normally
defined based on the SFO level.

• Similar as FFO, the test usually conducted on the whole


scale ready-made product (e.g. power transformer,
insulator, surge arrester, circuit breaker etc.) to test its
durability.
• Some small scale tests (with lower impulse voltage /
current magnitude) may also conducted that follow the
HVAC / HVDC test (e.g. oil test, insulation samples
etc). 75

BEE 3243 Electric Power Systems – Module 1

Switching Impulse Tests: Continue

• Same as FFO, the test may be conducted via the


positive and negative polarity impulse waveform.

• The tests with positive polarity are more popular as the


observation damage result typically worst than the one
shown via negative polarity. Also the breakdown
voltage level (+ve) is lower than that observed in (-ve)

• The tests duration lasted less than a few second per


test and it typically being repeated many times
depending on the test method (e.g. 80 times repetitions
up-and-down test method for determining U50).

• Same as for HVAC / HVDC, the test also usually


conducted in laboratory using dry and simulate-wet
conditions. 76

38
BEE 3243 Electric Power Systems – Module 1

Switching & Lightning Impulse Test:


System Setup

77

BEE 3243 Electric Power Systems – Module 1

Switching & Lightning Impulse Test:


Impulse Waveforms

78

39
BEE 3243 Electric Power Systems – Module 1

Switching Impulse Test: Experiment Setup

79

BEE 3243 Electric Power Systems – Module 1

Switching Impulse Test: Flashover between


Grading Rings

80

40
BEE 3243 Electric Power Systems – Module 1

Switching Impulse Test: Flashover as


Streamers

81

BEE 3243 Electric Power Systems – Module 1

Switching Impulse Test: Flashover to


the Floor (Ground)

82

41
BEE 3243 Electric Power Systems – Module 1

Electrical Flashovers from Positive


Switching Impulse

83

BEE 3243 Electric Power Systems – Module 1

Switching Impulse Test: Flashover on


Prototype (Insulation Failure)

84

42
BEE 3243 Electric Power Systems – Module 1

Note References

1. Subir Ray, An Introduction to High Voltage


Engineering, Prentice Hall India, 2004

2. E. Kuffel, High Voltage Engineering: Fundamentals,


Newness, 2000

3. I. Cotton, An Introduction to High Voltage Testing,


MSc. Lecture Note, The University of Manchester,
2006

85

43

You might also like