Professional Documents
Culture Documents
Foam Calculation Tank Farm
Foam Calculation Tank Farm
DATA
Diamater of Roof Tank 21,0 m
Fuel CPO
Flash Point > 162⁰C Combustible Liquid (NFPA 30)
Class (NFPA 30) IIIB
Discharge Outlet Type II Monitor
Foam Concentrate 3%
Minimum Application Rate (NFPA 11) 4,1 Liter/minute.m2
Minimum Discharge Duration 50 minute
CALCULATION
Surface Area 346 m2
Application Rate 1.419 Liter/minute
Minimum Discharge Volume 70.968 Liter
Minimum Foam @ 3% Concentrate 2.129 Liter