Circuit protection
and control devices
0.5 to 6300 A
LV product characteristics
2005
cover.fm Page 2 Mercredi, 16. mars 2005 2:59 14
A consistent design of offers from All Merlin Gerin offers are designed according to
Medium Voltage to Ultra terminal electrical, mechanical and communication
consistency rules.
The products express this consistency by their
overall design and shared ergonomics.
Electrical consistency:
Mechanical consistency:
Communication consistency:
Thanks to the use of standard Web technologies, you can offer Each product complies with global choices in terms of
your customers intelligent Merlin Gerin switchboards allowing communication protocols (Modbus, Ethernet, etc.) for simplified
easy access to information: follow-up of currents, voltages,
powers, consumption history, etc.
integration in the management, supervision and monitoring
systems.
Guiding Tools
for more efficient design
and implementation
of your installations.
1
p01-04.fm Page 2 Lundi, 14. mars 2005 5:17 17
Trihal
MV/LV dry cast resin
transformer
from 160 to 5000 kVA
Evolis
MV vacuum
switchgear and
components
from 1 to 24 kV.
These technical guides help you comply with The CAD software and tools enhance
installation standards and rules i.e.: productivity and safety.
The electrical installation guide, the They help you create your installations
protection guide, the switchboard by simplifying product choice through
implementation guide, the technical booklets easy browsing in the Guiding System
and the co-ordination tables all form genuine offers.
reference tools for the design of high- Last but not least, they optimise
performance electrical installations. use of our products while also complying
For example, the LV protection co-ordination with standards and proper procedures.
guide - discrimination and cascading -
optimises choice of protection and
connection devices while also increasing
markedly continuity of supply in the
installations.
2
p01-04.fm Page 3 Lundi, 14. mars 2005 5:17 17
Pragma Canalis
Enclosures for Prefabricated Busbar
distribution Trunking
switchboards from 25 to 4000 A
up to 160 A
PowerLogic
Power
management
Training
3
p01-04.fm Page 4 Lundi, 14. mars 2005 5:17 17
4
p05.fm Page 5 Lundi, 14. mars 2005 5:17 17
Circuit protection
and control devices
Contents
Multi 9
Multi 9 circuit breakers from 0.5 to 125 A 6
EasyPact
EasyPact circuit breakers from 15 to 250 A 8
Compact NS
Compact NS AC circuit breakers up to 630 A 10
Compact NS AC circuit breakers from 630 to 3200 A 12
Compact NS DC circuit breakers from 100 to 630 A 14
Masterpact NT and NW
Masterpact NT06 to NT16
AC circuit breakers and switch-disconnectors from 630 to 1600 A 16
Masterpact NW08 to NW63
AC circuit breakers and switch-disconnectors from 800 to 6300 A 18
Masterpact NW10 to NW40 DC circuit breakers from 800 to 6300 A 20
Interpact INS
Interpact INS40 to 160 switch-disconnectors 24
Interpact INS250-100 to 630 switch-disconnectors 28
Interpact INS630b to 2500 switch-disconnectors 32
Interpact INV
Interpact INV100 to 630 switch-disconnectors 36
Interpact INV630b to 2500 switch-disconnectors 40
Fupact
Fupact INFp32 to INFp800 switch-disconnector fuses 44
Fupact ISFT100 to ISFT630 fuse-switch disconnectors 48
Fupact ISFL160 to ISFL630 fuse-switch disconnectors 52
Vigirex
Protection and monitoring relays 56
5
Multi 9 Multi 9 circuit breakers
from 0.5 to 125 A
056984NR_21
D (lm = 10 to 14 ln) - - - - -
K (lm = 10 to 14 In) - - - - -
Z (lm = 2.4 to 3.2) - - - - -
MA (lm = 12 ln) - - - - -
Personal protection
Add-on rcd's (Vigi module) - - integrated integrated b
30-300 mA 10-100 mA
Electrical auxiliaries
NG125. Auxiliary and alarm switches (OF-SD) - b b - b
Shunt trip (MX); undervoltage release (MN) - b b - b
Installation
Plug in base - - - - b
Terminal shieds - - - - b
Padlocking device - b b b b
Rotary handle - - - - b
Dimensions (mm) W 18 18 36 18 18/P
H 81 81 81 111 81
D 70 70 70 73 73
- - - - - - - - - 10 (1P) 15 (1P) - - - -
15 - - 10 (1P) 15 (1P) 20 (1P) 25 (1P) 25 (1P) 25 (1P) - - 25 (1P) 36 (1P) 50 (1P) -
- - - 10 (2P) 20 (2P) 25 (2P) 30 (2P) 30 (2P) 30 (2P) 10 (1P) 15 (1P) 25 (1P) 36 (1P) 50 (1P) -
- - - 20 (3P) 30 (3P) 40 (3P) 50 (3P) 50 (3P) 50 (3P) - - - - - -
- - - 25 (4P) 40 (4P) 50 (4P) 60 (4P) 60 (4P) 60 (4P) 10 (2P) 15 (2P) 25 (2P) 36 (2P) 50 (2P) -
- - - - - - - - - - - 25 (4P) 36 (4P) 50 (4P) -
100 % - - 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % -
b b - b b b b b b b b b - b -
b b b b b b b b b b b b b b -
- - - - b b b b b b b b - b -
- - - - - - b b b - - - - - -
- - - - - - b b b - - - - - -
- - - - - - b y 40 A - - - - - b
- integrated integrated b b b b b b b b b b
30-300 mA 10-100 mA
b b - b b b b b b b b b b
b b - b b b b b b b b b b
- - - b b y 63 A -
- - - b b b
b b b b b b
- - - b b b
18 36 18 18/P 27/P 27/P
81 81 111 81 81 103
70 70 73 73 73 81
Number of poles
Rated current (A) In at 40 °C
250 V
(2P in series)
Rated service breaking capacity Ics % Icu 110-400 V
415-550 V
Suitability for isolation
Utilisation category
Pollution degree
Endurance (C-O cycles) Mechanical
Electrical In/415 V
Electrical characteristics as per JIS C8370
EZC250. Breaking capacity (kA) Icn AC 50/60 Hz 130 V
220 V
460 V
Electrical characteristics as per NEMA-AB1
Breaking capacity (kA) HIC AC 50/60 Hz 240 V
277/480Y V
Protection
Overload protection Bimetal
Instantaneous protection Magnetic
Auxiliaries
Indication contacts Auxiliary switch AX
Alarm switch AL
Combined AX + AL AXAL
Voltage releases Shunt trip release SHT
Undervoltage release UVR
Installation
Connection Crimp lugs/bars
Accessories Box lugs for bare cables
Rotary handles direct
extended
Terminal extensions
Spreaders
Phase barriers
Terminal shields
Padlocking system
DIN rail plate
Dimension and weight
Dimensions (mm) W
H
D
Weight (kg)
(1) Only 3 poles.
(2) 50 in 2 poles.
8
p08-09.fm Page 9 Lundi, 14. mars 2005 5:20 17
EasyPact 0
10 25 25 25 50 100 25 50 85
10 25 18 25 25 100 (1) 25 50 85
7.5 10 2.5 18 5 30 18 25 36
7.5 10 2.5 15 5 30 18 25 36
5 7.5 - 10 - 20 15 20 25
2.5 5 - 5 - 10 5 8 10
- 5 5 5 10 10 5 20 30
- 5 - 5 - 10 5 20 30
25 % 50 % 50 % 50 % 50 % 50 % 50 % 50 % 50 %
25 % 50 % 50 % 50 % 50 % 25 % 50 % 50 % 50 %
b b b b b b b b b
A A A A A A A A A
3 3 3 3 3 3 3 3 3
8500 8500 8500 8500 8500 8500 10000 10000 10000
4000 4000 4000 4000 4000 4000 5000 5000 5000
10 25 15 25 30 100 30 50 85
10 25 - 25 - 100 30 50 85
5 7.5 - 10 - 25 15 25 35
- - 10 25 18 100 25 50 85
- - 10 10 18 18 (2) 15 18 25 (1)
b b b b b b b b b
b b b b b b b b b
b b b b b b b b b
b b b b b b b b b
b b b b b b b b b
b b b b b b b b b
b b b b b b b b b
b b b b b b b b b
b b b b b b b b b
- - - - - - b b b
b b b b b b b b b
b b b b b b b b b
b b b b b b b b b
b b b b b b b b b
b b b b b b - - -
9
Compact NS Compact NS AC circuit breakers
up to 630 A
PB101050_33
10
b b b
b b b
- b b
- b b
- b b
- b b b b
- b b b b
- - - - b
- - - - b
- - - - b
nd spreaders b b b
nterphase barriers b b b
b b b
ns 2-3P / 4P 105 x 161 x 86 105 x 161 x 86 / 140 x 161 x 86 140 x 255 x 110 / 185 x 255 x 110
ns 3P / 4P 1.8 / 2.3 2.0 to 2.2 / 2.6 to 2.8 6.2 to 8.1
- b b
11
500/525 V 40 50 100
660/690 V 30 42 25
DC 250 V - - -
500 V - - -
Service breaking capacity (kA rms) lcs Value or % Icu manual operation 100 % 75 % 100 %
electrical operation 75 % 50 % 100 %
Short-time withstand current (kA rms) lcw 0.5 s 25 25 10
V AC 50/60 Hz 1s 17 17 7
V AC 50/60 Hz 3s - - -
Integrated instantaneous protection kA peak ±10 % 55
Suitability for isolation b
Utilisation category B B A
Durability (C-O cycles) mechanical 10000
electrical 440 V In/2 6000 6000 4000
In 5000 5000 3000
Compact NS2000H. 690 V In/2 4000 4000 3000
In 2000 2000 2000
Pollution degree III
Electrical characteristics as per Nema AB1 N H L
Breaking capacity at 60 Hz (kA) 240 V 50 65 125
480 V 35 50 100
600 V 25 50 -
Protection and measurements
Interchangeable control units Micrologic 2.0
Overload protection long time Ir (In x …) b
Short-circuit protection short time Isd (Ir x …) -
instantaneous Ii (In x …) b
Earth-fault protection lg (In x …) -
Residual earth-leakage protection ∆n
I∆ -
Zone selective interlocking ZSI -
Protection of the fourth pole b
Current measurements -
Remote communication by bus
Device-status indication b
Device remote operation b
Transmission of settings -
Indication and identification of protection devices and alarms -
Transmission of measured current values -
Additional indication and control auxiliaries
Indication contacts b
Voltage releases MX shunt release b
MN undervoltage release b
Installation
Accessories terminal extensions and spreaders b
terminal shields and interphase barriers b
escutcheons b
Dimensions fixed devices, front connections (mm) 3P 327 x 210 x 147
HxWxD 4P 327 x 280 x 147
Weight fixed devices, front connections (kg) 3P 14
(1) 65 °C with vertical connections. See the temperature 4P 18
derating tables for other types of connections.
Source changeover system
(2) Ics: 100 % Icu for breaking capacity 440V/500V/660V
Ics: 75 % Icu for breaking capacity 220V/380V. Manual, remote-operated and automatic source changeover systems b
12
Micrologic 2.0 Micrologic 5.0 Micrologic 2.0 A Micrologic 5.0 A Micrologic 6.0 A Micrologic 7.0 A
b b b b b b
…) - b - b b b
b b b b b b
) - - - - b -
- - - - - b
- - b b b b
b b b b b b
- - b b b b
b b b b b b
b b b b - -
- - b b b b
- - b b b b
- - b b b b
b b
b b
e b b
spreaders b -
rphase barriers b b
b b
327 x 210 x 147 350 x 420 x 160
327 x 280 x 147 350 x 535 x 160
14 24
18 36
b -
13
Number of poles
Electrical characteristics as per IEC 60947-1/ 60947-2 and EN 60947-1 / 60947-2
Rated current at 40 °C In (A)
Rated insulation voltage Ui (V)
Rated impulse withstand voltage Uimp (kV peak)
Rated operational voltage Ue (V DC)
Type of circuit breaker
Ultimate breaking capacity Icu (kA rms) V DC 48-125 V (1P) (1)
(L/R = 5 ms and L/R = 15 ms) 250 V (1P) (1)
500 V (2P) (1)
750 V (3P) (1)
Service breaking capacity Ics % Icu
Rated making capacity Icm % Icu
PB101048a-20
Utilisation category
Breaking time (ms)
Suitability for isolation
Pollution degree (as per IEC 60664-1)
Protection against overcurrents (see "LV circuit breakers and switch-disconnectors direct current 16 to 4000 A" - ABTED205160EN)
Trip units Built-in
Interchangeable
Protection Overloads
Short-circuits
Durability
(O/F cycles) Mechanical
Electrical 250 V In
PB101055a-27
250 V In/2
500 V In
500 V In/2
750 V In
750 V In/2
Indication and control auxiliaries
Auxiliary contacts
Voltage release MX shunt release
MN undervoltage release
Installation and connections
Fixed Front connection
Rear connection
Plug-in (base) Front connection
PB100905a-36
Rear connection
Withdrawable (chassis) Front connection
Rear connection
Dimensions and weight
Dimensions Fixed 1P
H x W x D (mm) connected in series 2P
3P
4P
Weight (kg) Fixed 1P
connected in series 2P
3P
4P
(1) Number of poles taking part in current interruption.
Example. The NS100N circuit breaker exists in the following versions:
- 1 pole with an Icu of 50 kA, for systems y 250 V
- 2 poles with an Icu of 85 kA, for systems y 500 V; 1 pole can be used in a 250 V system.
14
p14-15.fm Page 15 Lundi, 14. mars 2005 5:22 17
Compact NS
b b b b - b b b b - - - -
- - - - b - - - - b b b b
b b b b b b b b b b - - -
b b b b b b b b b b b b b
10000 5000
5000 1000
10000 2000
5000 1000
10000 2000
5000 1000
10000 2000
b
b
b
b
b
- - - - b - - - - b b b b
- - - - b - - - - b b b b
- - - - b - - - - b b b b
- - - - b - - - - b b b b
161 x 35 x 86 - - 161 x 35 x 86 - - -
- 161 x 70 x 86 - - 161 x 70 x 86 - -
- - 161 x 105 x 86 - - 161 x 105 x 86 255 x 140 x 110
- - 161 x 140 x 86 - - 161 x 140 x 86 225 x 185 x 110
0.7 - - 0.7 - - -
- 1.2 - - 1.2 - -
- - 1.6 to 1.9 - - 1.6 to 1.9 6.0
- - 2.1 to 2.3 - - 2.1 to 2.3 7.8
15
p16-19.fm Page 16 Lundi, 14. mars 2005 5:24 17
Common characteristics
PB100767a-48
16
p16-19.fm Page 17 Lundi, 14. mars 2005 5:24 17
Masterpact NT and NW
Sensor selection
Sensor rating (A) 250 (1) 400 630 800 1000 1250 1600
Ir threshold setting(A) 100 to 250 160 to 400 250 to 630 320 to 800 400 to 1000 500 to 1250 640 to 1600
(1) For NT02 rating, please consult us.
42 50 150 - 42 50 -
42 50 100 - 42 50 -
42 42 25 - 42 42 -
HA HA10 HA HA10
75 - 75 -
75 - 75 -
75 - 75 -
- 42 - 42
36 20 36 20
36 20 36 20
20 20 20 20
36 36
25
12.5
H1 H2 L1 H10 H1 H2 L1 H10 H1 H2 L1 H10 H1 H2 H10 H10 H1 H2
630 800 1000 1250 1600
6 6 3 - 6 6 3 - 6 6 3 - 6 6 - - 6 6
3 3 2 - 3 3 2 - 3 3 2 - 3 3 - - 3 3
- - - 0.5 - - - 0.5 - - - 0.5 - - 0.5 0.5 - -
H1/H2/HA
630 800 1000 1250 1600
6 6 6 6 6
3 3 3 3 3
H1/H2/HA
500 630 800 1000 1000
y 250 250 to 335 335 to 450 450 to 560 450 to 560
y 300 300 to 400 400 to 500 500 to 630 500 to 630
6
-
17
p16-19.fm Page 18 Lundi, 14. mars 2005 5:24 17
Common characteristics
PB100768a-38
V AC 50/60 Hz 525 V
690 V
1150 V
Rated service breaking capacity (kA rms) Ics % Icu
Utilisation category
Rated short-time withstand current (kA rms) Icw 1s
V AC 50/60 Hz 3s
Integrated instantaneous protection (kA peak ±10 %)
Rated making capacity (kA peak) Icm 220/415/440 V
V AC 50/60 Hz 525 V
690 V
1150 V
Break time (ms) between tripping order and arc extinction
Closing time (ms)
Circuit-breaker characteristics as per NEMA AB1
Breaking capacity (kA) 240/480 V
V AC 50/60 Hz 600 V
Unprotected circuit-breaker characteristics: tripping by shunt trip as per IEC 60947-2
Type of circuit breaker
Ultimate breaking capacity (kA rms) V AC 50/60 Hz Icu 220...690 V
Rated service breaking capacity (kA rms) Ics % Icu
Rated short-time withstand current (kA rms) Icw 1s
3s
Overload and short-circuit protection with external protection relay:
short-circuit protection, maximum delay: 350 ms (4)
Rated making capacity (kA peak) V AC 50/60 Hz Icm 220...690 V
18
p16-19.fm Page 19 Lundi, 14. mars 2005 5:24 17
Masterpact NT and NW
Sensor selection
Sensor rating (A) 250 (1) 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Ir threshold setting(A) 100 160 250 320 400 500 630 800 1000 1250 1600 2000 2500
to 250 to 400 to 630 to 800 to 1000 to 1250 to 1600 to 2000 to 2500 to 3200 to 4000 to 5000 to 6300
(1) For NW02 rating, please consult us.
NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63
800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
400 400 630 800 to 1600 1000 to 2000 1250 1600 2000 to 4000 2000 2500 3200
to 800 to 1000 to 1250 to 2500 to 3200 to 4000 to 5000 to 6300
N1 H1 H2 L1 (2) H10 H1 H2 H3 L1 (2) H10 H1 H2 H3 H10 H1 H2
42 65 100 150 - 65 100 150 150 - 65 100 150 - 100 150
42 65 85 130 - 65 85 130 130 - 65 85 130 - 100 130
42 65 85 100 - 65 85 100 100 - 65 85 100 - 100 100
- - - - 50 - - - - 50 - - - 50 - -
100 % 100 % 100 % 100 %
B B B B
42 65 85 30 50 65 85 65 30 50 65 85 65 50 100 100
22 36 50 30 50 36 75 65 30 50 65 75 65 50 100 100
Without Without 190 80 Without Without 190 150 80 Without Without 190 150 Without Without 270
88 143 220 330 - 143 220 330 330 - 143 220 330 - 220 330
88 143 187 286 - 143 187 286 286 - 143 187 286 - 220 286
88 143 187 220 - 143 187 220 220 - 143 187 220 - 220 220
- - - - 105 - - - - 105 - - - 105 - -
25 25 25 10 25 25 25 25 10 25 25 25 25 25 25 25
< 70 < 70 < 70 < 80
NW08 / NW10 / NW12 NW16 NW20 NW25 / NW32 / NW40 NW40b / NW50 / NW63
NA HA HF HA10 HA HF HA10 HA HF HA10 HA HF HA10 HA
88 105 187 - 105 187 - 105 187 - 121 187 - 187
- - - 105 - - 105 - - 105 - - 105 -
- - - - - - - - - - - - - -
42 50 85 50 50 85 50 50 85 50 55 85 50 85
- 36 50 50 50 50 50 50 50 50 55 75 50 85
25 20 10
12.5 10 5
N1/H1/H2 L1 H10 H1/H2 L1 H10 H1/H2 H3 H10 H1 H2
800/1000/1250/1600 2000 2500/3200/4000 4000b/5000/6300
10 3 - 8 3 - 5 1.25 - 1.5 1.5
10 3 - 6 3 - 2.5 1.25 - 1.5 1.5
- - 0.5 - - 0.5 - - 0.5 - -
H1/H2/NA/HA/HF H1/H2/H3/HA/HF H1/H2/HA
800/1000/1250/1600 2000 2500/3200/4000 4000b/5000/6300
10 8 5 1.5
10 6 2.5 1.5
H1/H2/HA/HF H1/H2/H3/HA/HF
800 1000 1250 1600 2000
335 to 450 450 to 560 560 to 670 670 to 900 900 to 1150
400 to 500 500 to 630 500 to 800 800 to 1000 1000 to 1300
y 800 800 to 1000 1000 to 1250 1250 to 1600 1600 to 2000
6
19
p20-21.fm Page 20 Lundi, 14. mars 2005 5:25 17
750
900
L/R = 30 ms Icu 500
750
900
Service breaking capacity Ics % Icu
Rated making capacity Icm % Icu
NW10DC 4P. Short-time withstand current Icw 1s
Utilisation category
Breaking time (ms)
Making time (ms)
Suitability for isolation
Pollution degree (as per IEC 60664-1)
Protection against overcurrents (see "LV circuit breakers and switch-disconnectors direct current 16 to 4000 A" - ABTED205160EN)
Trip units Built-in
Protection Overloads
Short-circuits
Durability
(O/F cycles) Mechanical With maintenance
Without maintenance
Electrical Without maintenance 500 V CC
900 V CC
Indication and control auxiliaries
Auxiliary contacts
Voltage release MX shunt release
MN undervoltage release
Characteristics of switch-disconnectors as per IEC 60947-3 and EN 60947-3
Type of switch-disconnector
Rated making capacity Icm % Icu
Rated short-time withstand current Icw 1s
Installation and connections
Connection Drawout 3P RC Horizontal
4P Vertical
Fixed 3P RC Horizontal
4P Vertical
Dimensions and weight
Dimensions Drawout 3P
H x W x D (mm) connected in series 4P
Fixed 3P
4P
Weight (kg) Drawout 3P
connected in series (approximate values) 4P
Fixed 3P
4P
(1) 50 °C - see the derating table for the NW40.
20
p20-21.fm Page 21 Lundi, 14. mars 2005 5:25 17
Masterpact NT and NW
b b b b b b
- - - - - -
b b b b b b
20000
10000
8500 5000 2000
- 2000 - 2000 - 1000
b b b b b b
b b b b b b
b b b b b b
HA HA HA
- 85 - 85 - 85
- 85 - 85 - 85
b b b b - -
b b b b b b
b b b b - -
b b b b b b
21
p22-23.fm Page 22 Lundi, 14. mars 2005 5:26 17
+ instantaneous
X: type of protection
b 2 for basic protection
b 5 for selective protection
b 6 for selective + earth-fault protection
b 7 for selective + earth-leakage protection.
Y: control-unit generation
Identification of the control-unit generation.
"0" signifies the first generation. Micrologic 5: basic protection
Z: type of measurement
Protection:
b A for "ammeter"
long time
b P for "power meter"
DB101117
+ short time
b H for "harmonic meter". + instantaneous
PB100772a-32
Protection:
long time
DB101117
DB101118
+ short time
+ instantaneous
+ earth fault
Protection:
long time
DB101117
DB101119
+ short time
+ instantaneous
+ earth leakage
22
p22-23.fm Page 23 Lundi, 14. mars 2005 5:26 17
2.0 A
DB101120
DB101122
DB101122
DB101124
DB101124
DB101124
DB101124
23
p24-27.fm Page 24 Lundi, 14. mars 2005 5:26 17
Number of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C
Conventional thermal current in enclosure Ithe at 60 °C
Rated insulation level (V) Ui AC 50/60 Hz
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Interpact INS80 switch-disconnector. Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical AC 50/60 Hz
220-240 V
380-415 V
440-480 V (1)
052168a-50
500 V
660-690 V
Electrical DC
125 V (2P in series)
250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz
220-240 V
230 V (NEMA)
380-415 V
440 V
Interpact INS160 switch-disconnector. 480 V (NEMA)
500-525 V
660-690 V
Rated duties Uninterrupted duty
Intermittent duty
059202a-50
24
p24-27.fm Page 25 Lundi, 14. mars 2005 5:26 17
Interpact INS 0
11 15 22 22 37 45
7,5 15 15 22 37 45
20 30 37 45 55 75
22 30 37 55 55 90
22 30 30 55 75 90
18,5 22 22 55 75 110
- - - 55 75 90
b b b b b b
class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 % class 120 - 60 %
15 15 15 20 20 20
75 75 75 154 154 154
- - - - - -
25
p24-27.fm Page 26 Lundi, 14. mars 2005 5:26 17
26
p24-27.fm Page 27 Lundi, 14. mars 2005 5:26 17
Interpact INS 0
b b b b b b
- - - b b b
b b b - - -
b b b b b b
b b b b b b
- - - b b b
- - - - - -
- - - - - -
- - - b b b
- - - - - -
- - - - - -
b b b b b b
- - - - - -
- - - - - -
- - - - - -
b b b b b b
b b b b b b
b b b b b b
b b b b b b
- - - - - -
b b b b b b
- - - - - -
b b b b b b
- - - b b b
0.7 < Nm < 1.3 0.7 < Nm < 1.3 0.7 < Nm < 1.3 1.4 < Nm < 2 1.4 < Nm < 2 1.4 < Nm < 2
b b b b b b
- - - - - -
- - - - - -
- - - - - -
- - - - - -
b b b b b b
b b b b b b
b b b b b b
- - - - - -
- - - - - -
8 8 8 8 8 8
85 x 90 x 62.5 85 x 90 x 62.5 85 x 90 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5
85 x 90 x 62.5 85 x 90 x 62.5 85 x 90 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5
0.5 0.5 0.5 0.8 0.8 0.8
0.6 0.6 0.6 0.9 0.9 0.9
190 x 115 x 55 190 x 115 x 55 190 x 115 x 55 260 x 160 x 55 260 x 160 x 55 260 x 160 x 55
27
p28-31.fm Page 28 Lundi, 14. mars 2005 5:26 17
Number of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C
Conventional thermal current in enclosure Ithe at 60 °C
Rated insulation level (V) Ui AC 50/60 Hz
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical AC 50/60 Hz
220-240 V
Interpact INS250 switch-disconnector. 380-415 V
440-480 V (1)
500-525 V
660-690 V
Electrical DC
056652a-41
circuit breaker)
Short-time withstand current (A rms) Icw 1s
3s
20 s
30 s
Suitability for isolation
Durability (category A) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz
440 V
500 V
690 V
Electrical DC
250 V
Positive contact indication
Visible break
Interpact INS400 switch-disconnector.
Emergency-off switch disconnector
Degree of pollution
Upstream protection
See the “LV switch-disconnectors - Interpact INS/INV 40 to 2500 A" catalogue
059488a-49
28
p28-31.fm Page 29 Lundi, 14. mars 2005 5:26 17
Interpact INS 0
- - - - - - - -
29
p28-31.fm Page 30 Lundi, 14. mars 2005 5:26 17
30
p28-31.fm Page 31 Lundi, 14. mars 2005 5:26 17
Interpact INS 0
b b b b b b b b
b b b b b b b b
- - - - - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
- - - - - - - -
b b b b b b b b
b b b b b b b b
- - - - b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b - - - -
b b b b - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 13.5 < Nm < 16.5 13.5 < Nm < 16.5 13.5 < Nm < 16.5 13.5 < Nm < 16.5
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b - - - -
- - - - - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
15 15 15 15 50 50 50 50
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130
2 2 2 2 4.6 4.6 4.6 4.6
2.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9
400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200
31
p32-35.fm Page 32 Lundi, 14. mars 2005 5:29 17
Number of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C
Conventional thermal current in enclosure Ithe at 60 °C
Rated insulation level (V) Ui AC 50/60 Hz
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical AC 50/60 Hz
220-240 V
440-480 V (1)
PB100018a-55
500-525 V
660-690 V
Electrical DC
125 V (2P in series)
250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz
220-240 V
380-400 V
415 V
500-525 V
660-690 V
Interpact INS1600 emergency-off switch-disconnector.
Rated duties Uninterrupted duty
Intermittent duty
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)
Max. (with upstream protection
PB100020a-65
circuit breaker)
Short-time withstand current (A rms) Icw 0.5 s
0.8 s
1s
3s
20 s
30 s
Suitability for isolation
Durability (category B) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz
220-240 V
380-415 V
440-480 V (1)
500-525 V
660-690 V
32
p32-35.fm Page 33 Lundi, 14. mars 2005 5:29 17
Interpact INS 0
50 50 50 50 50 50 50
42 42 42 42 42 50 50
35 35 35 35 35 50 50
20 20 20 20 20 30 30
10 10 10 10 10 13 13
8 8 8 8 8 11 11
b b b b b b b
5000 3000 3000 3000 3000 500 500
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A
AC21B AC22B AC23B AC21B AC22B AC23B AC21B AC22B AC23B
AC21A AC22A
1000 1000 1000 500 500 500 500 500 500 500 500 500 100 100 500 100 100 - 100 100 -
500 500
1000 1000 1000 500 500 500 500 500 500 500 500 500 100 100 500 100 100 - 100 100 -
500 500
1000 1000 1000 500 500 500 500 500 500 500 500 500 100 100 500 100 100 - 100 100 -
500 500
1000 1000 1000 500 500 500 500 500 500 500 500 500 100 100 500 100 100 - 100 100 -
500 500
1000 1000 1000 500 500 500 500 500 500 500 500 500 100 100 500 100 100 - 100 100 -
500 500
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B
1000 1000 1000 500 500 500 500 500 500 500 500 500 500 500 500 100 100 - 100 100 -
1000 1000 1000 500 500 500 500 500 500 500 500 500 500 500 500 100 100 - 100 100 -
b b b b b b b
- - - - - - -
b b b b b - -
III III III III III III III
- - - - - - -
33
p32-35.fm Page 34 Lundi, 14. mars 2005 5:29 17
34
p32-35.fm Page 35 Lundi, 14. mars 2005 5:29 17
Interpact INS 0
b b b b b b b
b b b b b b b
- - - - - - -
b b b b b b b
- - - - - - -
- - - - - b b
- - - - - - -
b b b b b - -
b b b b b b b
b b b b b - -
b b b b b - -
b b b b b b b
- - - - - - -
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
30 30 30 30 30 60 60
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
b b b b b b b
- - - - - - -
50 50 50 50 50 50 50
300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 440 x 347.5 x 227.5 440 x 347.5 x 227.5
300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 440 x 462.5 x 227.5 440 x 462.5 x 227.5
14 14 14 14 14 35 35
18 18 18 18 18 45 45
- - - - - - -
35
p36-39.fm Page 36 Lundi, 14. mars 2005 5:29 17
Number of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C
Conventional thermal current in enclosure Ithe at 60 °C
Rated insulation level (V) Ui AC 50/60 Hz
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical AC 50/60 Hz
220-240 V
380-415 V
440-480 V (1)
Interpact INV250 switch-disconnector. 500-525 V
660-690 V
Electrical DC
125 V (2P in series)
250 V (4P in series)
056654a-48
36
p36-39.fm Page 37 Lundi, 14. mars 2005 5:29 17
Interpact INV 0
- - - - - - - -
37
p36-39.fm Page 38 Lundi, 14. mars 2005 5:29 17
38
p36-39.fm Page 39 Lundi, 14. mars 2005 5:29 17
Interpact INV 0
b b b b b b b b
b b b b b b b b
- - - - - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
- - - - - - - -
b b b b b b b b
b b b b b b b b
- - - - b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b - - - -
b b b b - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
- - - - - - - -
5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 13,5 < Nm < 16.5 13,5 < Nm < 16.5 13,5 < Nm < 16.5 13,5 < Nm < 16.5
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
- - - - - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
15 15 15 15 50 50 50 50
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130
2 2 2 2 4.6 4.6 4.6 4.6
2.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9
400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200
39
p40-43.fm Page 40 Lundi, 14. mars 2005 5:30 17
Number of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 °C
Conventional thermal current in enclosure Ithe at 60 °C
Rated insulation level (V) Ui AC 50/60 Hz
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical AC 50/60 Hz
220-240 V
440-480 V (1)
PB100019a-55
500-525 V
660-690 V
Electrical DC
125 V (2P in series)
250 V (4P in series)
Rated operational power AC23 (kW) Electrical AC 50/60 Hz
220-240 V
380-400 V
415 V
500-525 V
660-690 V
Interpact INV1600 emergency-off switch-disconnector.
Rated duties Uninterrupted duty
Intermittent duty
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)
Max. (with upstream protection
PB100021a-65
circuit breaker)
Short-time withstand current (A rms) Icw 0.5 s
0.8 s
1s
3s
20 s
30 s
Suitability for isolation
Durability (category B) (O - C-O cycles) Mechanical
Electrical AC 50/60 Hz
220-240 V
380-415 V
440-480 V (1)
500-525 V
660-690 V
40
p40-43.fm Page 41 Lundi, 14. mars 2005 5:30 17
Interpact INV 0
50 50 50 50 50 50 50
42 42 42 42 42 50 50
35 35 35 35 35 50 50
20 20 20 20 20 30 30
10 10 10 10 10 13 13
8 8 8 8 8 11 11
b b b b b b b
5000 3000 3000 3000 3000 500 500
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A
AC21B AC22B AC23B AC21B AC22B AC23B AC21B AC22B AC23B
AC21A AC22A
1000 1000 1000 500 500 500 500 500 500 500 500 500 100 100 500 100 100 - 100 100 -
500 500
1000 1000 1000 500 500 500 500 500 500 500 500 500 100 100 500 100 100 - 100 100 -
500 500
1000 1000 1000 500 500 500 500 500 500 500 500 500 100 100 500 100 100 - 100 100 -
500 500
1000 1000 1000 500 500 500 500 500 500 500 500 500 100 100 500 100 100 - 100 100 -
500 500
1000 1000 1000 500 500 500 500 500 500 500 500 500 100 100 500 100 100 - 100 100 -
500 500
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B
1000 1000 1000 500 500 500 500 500 500 500 500 500 500 500 500 100 100 - 100 100 -
1000 1000 1000 500 500 500 500 500 500 500 500 500 500 500 500 100 100 - 100 100 -
b b b b b b b
- - - - - - -
b b b b b - -
III III III III III III III
- - - - - - -
41
p40-43.fm Page 42 Lundi, 14. mars 2005 5:30 17
42
p40-43.fm Page 43 Lundi, 14. mars 2005 5:30 17
Interpact INV 0
b b b b b b b
b b b b b b b
- - - - - - -
b b b b b b b
- - - - - - -
- - - - - b b
- - - - - - -
b b b b b - -
b b b b b b b
b b b b b - -
b b b b b - -
b b b b b b b
- - - - - - -
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
30 30 30 30 30 60 60
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
b b b b b b b
- - - - - - -
50 50 50 50 50 50 50
300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 440 x 347.5 x 227.5 440 x 347.5 x 227.5
300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 440 x 462.5 x 227.5 440 x 462.5 x 227.5
14 14 14 14 14 35 35
18 18 18 18 18 45 45
- - - - - - -
43
p44-47.fm Page 44 Vendredi, 25. mars 2005 10:17 10
30 s
Endurance (category A) (CO cycles) Mechanical
Electrical AC AC22A 500 V
AC22A 690 V
AC23A 500 V
AC23A 690 V
Suitability for isolation
Positive contact indication
Pollution degree
Control
Direct front rotary handle
Extended front rotary handle
INFD400. Extended lateral rotary handle
Locking by padlocks
Operating torque (typical for 3 poles switch-disconnector fuses) (Nm)
Indication auxiliaries
Auxiliary contacts
Blown-fuse indicator
Fuse monitor
Auxiliary contact test position
(1) Suitable for 480 V NEMA.
(2) AC23B.
(3) Some fuse-links limit these values. Motor starting current must be considered separately.
(4) Switch-disconnector combined with fuses.
(5) Only for NFC fuse-links.
(6) Only for DIN fuse-links.
44
p44-47.fm Page 45 Vendredi, 25. mars 2005 10:17 10
Fupact
INFp32 INFD40 INFp63 INFB100 INFC125 INFp160 INFp250 INFp400 INFp630 INFp800
NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS DIN-BS DIN-BS DIN-BS DIN-BS
NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS DIN-BS DIN-BS DIN-BS DIN-BS
NFC - NFC-DIN - NFC DIN DIN DIN DIN DIN
b b b b b b b b b b
b b b b b b b b b b
b b b b b b b - - -
b b b b b b b b b b
3 3 4 8 8 8 22 22 28 28
b b b b b b b b b b
b (5) - b (5) - b - b (6) b (6) b (6) b (6)
b b b b b b b b b b
b (standard) b (standard) b (standard) b (standard) b (standard) b (standard) b (optional) b (optional) b (optional) b (optional)
45
p44-47.fm Page 46 Vendredi, 25. mars 2005 10:17 10
46
p44-47.fm Page 47 Vendredi, 25. mars 2005 10:17 10
Fupact
INFp32 INFD40 INFp63 INFB100 INFC125 INFp160 INFp250 INFp400 INFp630 INFp800
b - - - - - - - - -
b - b - - - - - - -
- - b - b b - - - -
- b b - - b - - - -
- - b - - b - - - -
- - - - - - b - - -
- - - - - - - b - -
- - - - - - - - b b
b - - - - - - - - -
b - - - - - - - - -
b - b b - b - - - -
- - b b - b - - - -
- - - b (1) - b (1) - - - -
- - - - - - b b - -
- - - - - - b b - -
- - - - - - b (2) b - -
- - - - - - - b - -
- - - - - - - - b b
- - - - - - - - b b
- - - - - - - - - b
b b b b b b b b b b
2 2 3.5 15-22 15-22 15-22 30-44 30-44 50-75 50-75
2 2 2 M5: 3.5 M8: 5 - M5: 3.5 M8: 5 15 15 40 40
b (standard) b (standard) b (standard) b (optional) b (optional) b (optional) b (optional) b (optional) b (optional) b (optional)
- - - b b b b b b b
b b b b b b b b b b
- b b b b b b b b b
97 x 106 x 105 97 x 106 x 133 100 x 143 x 128 140 x 180 x 130 140 x 180 x 130 140 x 180 x 130 162 x 278 x 199 180 x 302 x 206 232 x 378 x 234 232 x 408 x 234
97 x 142 x 105 97 x 142 x 133 100 x 188 x 128 140 x 215 x 130 140 x 215 x 130 140 x 215 x 130 162 x 340 x 199 180 x 372 x 206 232 x 458 x 234 232 x 498 x 234
0.7 0.7 1.3 1.5 1.5 1.5 6.9 7.8 15.5 17
0.9 0.9 1.6 1.8 1.8 1.8 7.9 8.8 19 21
300x350x200 600 x 350 x 300 / 500 x 400 x 250 600 x 700 x 300 / 800 x 600 x 270
NFC-BS DIN NFC-DIN-BS BS NFC DIN-BS DIN-BS DIN-BS DIN-BS DIN-BS
32 40 63 100 125 160 250 400 630 800
30.4 38 60 95 119 152 237 380 600 760
28.8 36 56.7 90 113 144 225 360 567 720
27.2 34 53.6 85 106 136 212 340 536 680
25.6 32 50.4 80 100 128 200 320 504 640
25 30 47.2 75 94 120 187 300 474 600
24.4 28 44 70 88 112 175 280 441 560
31 38 61 96 121 156 242 386 610 772
29.5 36 58 92 115 148 230 368 580 736
28 34 55 87 109 140 218 350 550 700
26.5 32 52.2 83 103 133 207 331 522 662
25 30 49.3 78 97 126 195 313 493 625
23.5 28 46.4 74 92 118 184 295 464 588
22 26 43 69 86 111 172 277 434 552
20.5 24 40 65 81 103 161 268 406 514
47
p48-51.fm Page 48 Mercredi, 16. mars 2005 1:58 13
48
p48-51.fm Page 49 Mercredi, 16. mars 2005 1:58 13
Fupact
b b b b b
- - - - -
b b b b b
b b b b b
- b - - -
b b b b b
b b b b b
b b - - -
- b b b b
- b b b b
b b - - -
b b b b
b - - - -
b - - - -
b - - - -
- b b b b
141 x 89 x 71 163 x 107 x 80 246 x 186 x 110 271 x 210 x 127 271 x 250 x 132
0.46 0.64 2.06 2.96 4.00
49
p48-51.fm Page 50 Mercredi, 16. mars 2005 1:58 13
50
p48-51.fm Page 51 Mercredi, 16. mars 2005 1:58 13
Fupact
b b - - -
- b - - -
- - b - -
- - - b -
- - - - b
b - - - -
b b b b b
- b b - -
- b b b b
- - b b b
see "New fusepact range from 32
to 800 A - Fupact" catalogue
100/160 (3) 160 250 400 630
100/160 160 250 400 630
95/152 152 238 380 599
90/144 144 225 360 567
85/136 136 213 340 536
80/128 128 200 320 504
75/120 120 188 300 473
70/112 112 175 280 441
100/160 160 250 400 630
95/152 152 238 380 599
90/144 144 225 360 567
85/136 136 213 340 536
80/128 128 200 320 504
75/120 120 188 300 473
70/112 112 175 280 441
51
p52-55.fm Page 52 Mardi, 15. mars 2005 8:56 08
Rated short-circuit breaking capacity (kA rms) / Rated Icn/Icm/In fuse-link 415 V
short-circuit making capacity (kA peak)/ In fuse-link (A) (2) 500 V
690 V
Endurance (category B) (CO cycles) Mechanical
Electrical AC AC22B 415 V
AC21B 690 V
Suitability for isolation
Visible break
Pollution degree
Control
Direct front rotary handle (operator-dependent opening and closing)
Locking Padlocks
Lead seal
Indication auxiliary
Auxiliary contacts
Blown-fuse indicator
Current transformer
Installation and connection accessories
Mounting position Horizontal
Vertical
Connector For bare Cu/Al cables
For flexible bars
Lugs for Cu/Al cables
Terminal shields
Dimensions and weight
Overall dimensions H x W x D (mm) 3P
Approximate weight without fuse-links (kg) 3P
ISFL250. (1) Suitable for 480 V NEMA.
(2) Fuse-switch disconnector with fuse-links.
52
p52-55.fm Page 53 Mardi, 15. mars 2005 8:56 08
Fupact
b b b b
b b b b
- - - -
b b b b
- - - -
b b b b
b - - -
b b b b
b b b b
b - - -
b - - -
b b b b
456 x 50 x 159 755 x 100 x 192 755 x 100 x 192 755 x 100 x 192
1.35 6.35 6.35 6.35
53
p52-55.fm Page 54 Mardi, 15. mars 2005 8:56 08
54
p52-55.fm Page 55 Mardi, 15. mars 2005 8:56 08
Fupact
b - - -
b - - -
- b - -
- - b -
- - - b
b - - -
b - - -
- b b b
b - - -
b - - -
see "New fusepact range from 32 to 800 A - - -
- Fupact" catalogue
55
p56-cover.fm Page 56 Lundi, 14. mars 2005 5:41 17
PB100435a_18
PB100430a_19
PB100433a_18
PB100431a_19
Functions
Protection b b
Local indications b b
Remote indications (hard-wired) - -
Remote indications (via communication) - -
Display of measurements - -
Wiring
Optimum continuity of service b b
Optimum safety (failsafe) b b
Mounting
DIN rail b b
Front-panel mount b b
Rated operational voltage
1 DC voltage range from 12 to 48 V b b
1 DC voltage range from 24 to 130 V and AC 48 V - -
6 AC voltage ranges from 12 to 525 V b b
4 AC voltage ranges from 48 to 415 V - -
Thresholds
Fault (I∆n) 1 fixed instantaneous threshold 2 user-selectable thresholds
choose from 0.03 A to 1 A 0.03 A or 0.3 A
Alarm - -
Pre-alarm - -
Time delays
Fault Instantaneous Instantaneous for I∆n = 0.03 A
1 user-selectable time delay
instantaneous or 0.06 s for I∆n = 0.3 A
Alarm - -
Pre-alarm - -
Sensors
Merlin Gerin A, OA, E toroids (7) up to 630 A b b
Merlin Gerin rectangular sensors up to 3200 A b b
(1) Type A relays up to I∆N = 5 A. (4) Mandatory with an RMH (multiplexing for the 12 toroids).
(2) Relay with output contact requiring local, manual reset after fault clearance. (5) Mandatory with an RM12T (multiplexing for the 12 toroids).
(3) Relay with output contact that automatically resets after fault clearance.
56
p56-cover.fm Page 57 Lundi, 14. mars 2005 5:41 17
Vigirex 0
059484Ra_21
PB100434a_18
PB100432a_19
PB100715a_20
059483a_21
PB100429Ra_18
PB100432Ra_20
059485Ra_27
+ 0
(4)
b b b - -
b b b b b
- b b b b
- - b except RHUs - b
- b (8) b - b 12 measurement channels (5)
b b b - -
b b b - -
b - - b -
b b b b b
b - - b -
- b - - -
b - - b -
- b b - 220 to 240 V AC
b b (9) b b b
b b b - -
- b b b b
- - - - b
- on bargraph b - b
- - b - b
(10)
b b b b b
b b b b -
b b b b -
- - b except RHUs - b
- - b except RHUs - b
see "Low-voltage residual-current see "Low-voltage see "Low-voltage see "Low-voltage residual-current see "Low-voltage residual-current
protection relays - Vigirex" residual-current residual-current protection relays - Vigirex" protection relays - Vigirex" catalogue
catalogue protection relays - protection relays - catalogue
Vigirex" catalogue Vigirex" catalogue
b b b b b
b b b b b
(6) Depending on the type of wiring (optimum continuity of service (8) On a bargraph.
or optimum safety). (9) No voltage presence relay.
(7) see "Low-voltage residual-current protection relays - Vigirex" catalogue. (10) With actuation of contacts only.
cover.fm Page 0 Mercredi, 16. mars 2005 2:59 14
ABTED296014V1EN 03-2005