Design Criteria

First Floor

Live Load Uniform Load, kPa Reference


Reading Rooms 2.9 NSCP 2015, Vol. 1,
7th Edition, Chapter
Libraries
Stack Rooms 7.2 2-17
Table 2015-1

Second Floor

Live Load Uniform Load, kPa Reference


Reading Rooms 2.9 NSCP 2015, Vol. 1,
Stack Rooms 7.2 7th Edition, Chapter
Libraries
Corridors above 2-17
3.8
ground floor Table 205-1

Dead Load Value Reference


23.6 kN/m3 NSCP 2015, Vol. 1,
(Minimum Density 7th Edition, Chapter
Concrete Plain Concrete
for Design Loads 2-13
from Materials) Table 204-1
NSCP 2015, Vol. 1,
Ceramic or Quarry Tile
1.1 kPa (Minimum 7th Edition, Chapter
Floor and Floor Finish (20 mm) on 25 mm
Design Load) 2-14
mortar bed
Table 204-2
NSCP 2015, Vol. 1,
Plaster on Tile of 0.24 kPa (Minimum 7th Edition, Chapter
Ceilings
Concrete Design Load) 2-14
Table 204-2

Roof Deck

Live Load Uniform Load, kPa Reference


NSCP 2015, Vol. 1,
Tributary area method:
7th Edition, Chapter
Roof For roofing area more 0.6
2-20
than 60 m2
Table 205-3

Dead Load Value Reference


Coverings, Roof and Waterproofing 0.07 kPa (Minimum NSCP 2015, Vol. 1,
membranes: 7th Edition, Chapter
Design Load)
Wall Bituminous, smooth 2-13
surface Table 204-2