Professional Documents
Culture Documents
Chillers Specs
Chillers Specs
SECTION 23 60 00
PART 1 – GENERAL
1.1 SUMMARY
A. Statement of Method: Contractor to submit the statement of method for the execution
of each item stating the installation activities, repairing, protection, and the finishing
process.
B. Unit shall be manufactured to withstand and meet the project specified seismic
requirement.
C. Unit shall be installed to withstand and meet the project specified seismic requirement.
1.3 SUBMITTALS
A. Submit shop drawings for all refrigeration equipment specified in Part 2 of this Section.
PART 2 – PRODUCT
A. Air-Cooled screw chillers with performance as indicated on the drawings. Supply and
install where shown in the B.O.Q packaged type air cooled screw water chillers with at
least two refrigerant circuits note each compressor must have its own circuit. Chillers
shall be AHRI or Euro-vent certified and shall comply with EC requirements for
machinery, electromagnetic and pressure equipment directives.Chillers shall be
especially designed for operation on HFC-134a. Refrigerants containing CFC’s or
refrigerant blends shall not be acceptable.
The air-cooled screw chiller will be designed and manufactured in accordance with
following European directives:
Rating of chillers EN 12055
Construction of pressure vessel 97/23/EC (PED)
Machinery Directive 98/37/EC as modified
Low Voltage 2006/95/EC
Electromagnetic Compatibility 2004/108/EC
Electrical & Safety codes EN 60204–1 / EN 60335-2-40
Manufacturing Quality Stds. UNI – EN ISO 9001:2000
Unit footprint shall not exceed than those mentioned in the schedule of equipment.
Chiller shall include as standard not less than: two independent refrigerant circuits,
semi-hermetic type rotary single or twin screw compressors, electronic expansion device
(EEXV), refrigerant direct expansion shell & tube heat exchanger, air-cooled condenser
section, R134a refrigerant, lubrication system, motor starting components, discharge line
shut-off valve, control system and all components necessary for safe and stable unit
operation.
Contractor to ensure chiller dimensions should not exceed than those specified on the
schedule.
B. Units are leak and pressure tested at 390 psig (2689 kPa) high side, 250 psig (1724
kPa) low side, then evacuated and charged. All Air-cooled chillers are factory tested to
confirm operation prior to shipment. Packaged units Chiller will be delivered to the job
site completely assembled and charged with right refrigerant and oil quantity. Comply
with the manufacturer instructions for rigging and handling equipment.
C. Unit panels, structural elements and control boxes are constructed of galvanized steel
and mounted on a welded structural steel base. Unit panels and control boxes are
finished with a baked-on powder paint, and the structural base with an air dry paint. All
paint meets the requirement for outdoor saline environment equipment of the U.S.
Navy and other Federal Government Agencies and meets ASTM B117 1000 Hours salt
spray.
D. Anytime water only is present in the evaporator, the chiller must have flow control of the
chilled water system. Flow control can be done either directly or through an input to a
building automation system to conduct an action resulting in minimum flow through the
chiller evaporator barrel to avoid potentially catastrophic damage to the evaporator due
to freezing. If the system has sufficient glycol to protect down to the lowest expected
ambient, flow control is optional.
E. Evaporator
2. A separate field supplied low voltage power source is required to power the
freeze protection.
3. The evaporator shall have 2 circuits, one for each compressor and shall be single
refrigerant pass. The water connections shall be VICTAULIC type connections as
standard to ensure quick mechanical disconnection between the unit and the
hydronic network.
F. Operating Temperature
1. The condenser coils shall be constructed with internally finned seamless copper
tubes and arranged in a staggered row pattern and mechanically expanded into
lanced and rippled aluminium fins with full fin collars for higher efficiencies. Fins
per inch should be optimized to 14. The condenser coil has an integral sub
cooling circuit. Condensers are factory proof and leak tested at 506 psig (3489
kPa). The space between the fins shall be given by a collar that will increase the
surface area in connection with the tubes, protecting them from ambient corrosion.
Coils shall be protected against corrosion by here-site factory coating and a
warranty of 10 years shall be provided on the coating.
2. Direct drive vertical discharge condenser fans are dynamically balanced. Three
phase condenser fan motors with permanently lubricated ball bearing and internal
L. Refrigerant Circuits
1. Each unit has two refrigerant circuits, with one or two rotary screw compressor
per circuit. Each refrigerant circuit includes compressor suction and discharge
service valves, liquid line shutoff valve (except remote evap), removable core
filter, liquid line sight glass, charging port and one electronic expansion valve per
circuit. Fully modulating compressors and electronic expansion valves provide
variable capacity modulation over the entire operating range.
M. Unit Controls
1. All unit controls are housed in an outdoor rated enclosure per UL 1995 with
removable plates to allow for customer connection of power wiring and remote
interlocks. All controls, including sensors, are factory mounted and tested prior to
shipment.
3. The unit control module with Rapid Restart (TM), utilizing Adaptive Control (TM)
microprocessor automatically takes action to avoid unit shut down due to
abnormal operating conditions associated with low refrigerant pressure, high
condensing pressure and motor current overload. Should the abnormal operating
condition continue until a protective limit is violated, the unit will be shut down.
1. Unit protective functions include loss of chilled water flow, evaporator freezing,
loss of refrigerant, low refrigerant pressure, high refrigerant pressure, compressor
starting and running over current, phase loss, phase imbalance, phase reversal,
under/over voltage protection and loss of oil flow.
2. A menu driven digital display indicates over 20 operating data points including
chilled water set point, current limit set point, entering and leaving chilled water
temperature, evaporator and condenser refrigerant pressures and temperatures.
Over 60 diagnostic checks are made and displayed when a problem is detected.
The digital display can be read and advanced on the unit without opening any
control panel doors. Touch screen LCD allows for easy access of all important
chiller operating information.
1. A short circuit current rating offers a measure of safety for what the starter panel
enclosure is able to withstand in the event of an explosion caused by a short
circuit.
P. Power Disconnect Switch
Q. Power Connection
S. Flow Switch
1. There is a factory installed flow switch with a velocity set point of 35 cm/sec
T. Seismic Anchoring
W. Warranty:
1. Provide a five (5) year total service (“flange to flange”) service contract for the
refrigeration machines which includes the following:
a. All required emergency service, including all parts and labor required for
emergency service, 24 hours a day, 7 days a week with a response time
of 2 hours;
b. All required parts and labor, including refrigerant for all maintenance
work;
1. Trane
2. YORK
3. Mcquay / Diakin
4. Carrier
2. The expansion module will manage four internal DPDT relays at fully
programmable alarm levels.
4. The expansion module shall indicate the exact concentration of gas and the gas
detected. The LCD display will indicate multiple alarm levels for each sensing
point. The LED will also provide visual feedback in the following manner:
5. The standard three high/low alarm levels will be complemented with a fault relay.
6. The expansion module shall provide an individual 4-20mA output per refrigerant
sensor (up to four) for BAS compatibility.
3. The remote panel shall comply with ASHRAE or B-52 Mechanical Codes. This
includes a key for manual ‘’fan start’’ only operation, a silence key to
acknowledge the internal 65 dB audible alarm and a RED strobe on top of the unit
as a visual alarm.
4. The Remote panel will indicate the exact concentration of gas and the gas
detected. The LCD display will indicate multiple alarm levels for each sensing
point. The LED will also provide visual feedback in the following manner:
5. The unit shall be equipped with a NEMA 4X polycarbonate ABS impact resistant,
weather proof housing.
6. The standard three high/low alarm levels will be complemented with a fault relay.
7. The expansion module must provide an individual 4-20mA output per refrigerant
sensor (up to four) for BAS compatibility.
1. The sensor will be powered by the expansion module. Refrigerant gas will enter
the infrared gas detection chamber according to the diffusion principle. The ABC
logic infrared sensing technology will detect the refrigerant gas by sensing the
absorption rate of a specific bandwidth of light. The gas sensor will have
resolution levels of 1 ppm with a standard range of 0-1000 ppm. Temperature
and relative humidity variations will have no effect on the unit’s accuracy.
2. The sensor will be capable of operating within relative humidity ranges of 5-95%
4. The sensor alarm levels and unit are to be installed in accordance with the
following parameters:
E. Site Services:
1. Conduct site review of installed refrigeration plant and determine (finalize) most
suitable location(s) for refrigerant sampling point locations.
1. Supply three (3) bound operating and maintenance manuals each complete with:
G. Acceptable manufacturers are Vulcain (USA), MSA Inc. (USA), or approved equal.
fittings; strap mounted over shoulder tank status dial type indicator; alpine style
backpack with hinged support plate, "NOMEX"/"KEVLAR" straps, 1-piece stainless
steel cylinder band, lower cylinder support, buckles, loops, etc., and designed such
that equipment weight is
distributed over the hips.
B. The unit shall be equipped with a weatherproof housing clearly labeled with
“SELF-CONTAINED BREATHING APPARATUS”.
C. Site Services:
1. Supply three (3) bound, operating and maintenance manuals each complete with:
PART 3 – EXECUTION
C. Anchor the frame and concrete base in accordance with requirements specified in
Section entitled Seismic Control and Restraint. Provide flexible connections in all
piping connections.
D. Provide two (2) flow switches for each machine and install a flow switch in the chilled
water piping connection to the machine. Connect each flow switch to the machine control
panel to shut down the machine on a no flow condition. Provide all required sensors and
piping wells.
E. Provide a drain valve and vent cock for the water box of the machine. Pipe the pressure
relief rupture disc of the evaporator to atmosphere in accordance ASHRAE 15
requirements.
G. For low pressure refrigeration machines, provide valved chilled water supply piping
with strainer and valved chilled water return piping connections to the purge unit and oil
cooler on the machine. Piping shall be in accordance with the machine
manufacturer’s recommendations. In the chilled water piping to the purge condenser,
leave a piping tee for connection of domestic cold water piping as part of the plumbing
work specified in Division 22 “Plumbing”.
I. Supply a minimum of four (4) copies of complete wiring and piping connection
diagrams and details for proper execution and completion of the control circuits and
cooling water requirements.
J. Provide all required control wiring in conduit in accordance with requirements of
Electrical Division and in accordance with control wiring schematics and the machine
manufacturer's instructions.
K. Arrange for the refrigeration machine supplier to check machine installation prior to
start-up, to start-up the machine and to check out the machine through a performance
and acceptance test in the presence of and to the satisfaction of the Engineer, and to
completely instruct the Employer's designated operating personnel on proper machine
operation and maintenance. Supply and turn over to the Engineer, a minimum of four (4)
typewritten copies of machine start-up reports indicating all operating capacities and
performance, and a letter from the machine supplier stating that he (the supplier), has
checked the machine installation and found it to be in accordance with the
manufacturer's recommendations and instructions.
E. Forward four (4) copies of letter from manufacturer certifying satisfactory installation
and operation of system.
A. Provide two (2) self-contained breathing apparatuses and install as indicated by the
Engineer on site.
END OF SECTION
23 60 00