Professional Documents
Culture Documents
Univ of Michigan Flint Design Report 442
Univ of Michigan Flint Design Report 442
5/13/16
1.0 SUMMARY/OVERVIEW
1.1 Building Description
1.2 Proposed Structural Systems & Framing Plan
1.3 Site Conditions, Soil Properties, and Geotechnical Considerations
1.4 Design Changes
2.0 LOADS
2.1 Dead Loads
2.2 Live Loads
2.3 Snow Loads
2.4 Wind Loads
2.5 Earthquake Loads
3.0 MATERIALS
List of Figures
List of Tables
For this project, Altan Co. has been contracted to design and construct a replacement for the
UW's civil engineering building, More Hall.
The new infrastructure will be called the Blume Building and is located inside the UW
Seattle's campus in place of the current More Hall.
The building includes a roof that is composed of a lower level and higher level roof, where the
higher portion includes a penthouse to provide space for added storage.
The building will have one-way reinforced concrete slab running north-south, spanning an
average width of 12 ft. (east-west). There will be reinforced concrete beams running east-west,
supported by reinforced-concrete girders running north-south. Each beam will span multiple
bays. Reinforced columns will support the girders and connect into a series of square spread
footings below grade.
Figure [] below shows the direction of beams and slab layout on level 2. Letters (running
east west) and numbers (running north south) denoted indicate column lines.
Beams will be denoted by floor and by number and spans will be donated by letter (for
example Beam 6 Span C-D is labeled on Figure [] below).
Columns will be donated in a similar manner (for example Column 3C is labeled on
Figure [] below).
Figure []: Member Orientation, level 2
To resist the lateral forces, specially reinforced shear walls will be utilized in the elevator core,
connecting to a mat footing beneath grade. Details of both systems will be explained in further
detail in the calculation package.
Please refer to the attached Structural Drawings, ranging from S2.1 to S2.12, for AutoCAD
drawings of the floor plans, and S9 for E/W elevation. For elevation views refer to drawings S3.1
and S3.2.
2. Loads
All loads were calculated using ASCE 7-10 manual
2.1 Dead Loads
Totals (psf)
Level 6 95 psf
Level 5 95 psf
Level 4 95 psf
Level 3 95 psf
Level 2 95 psf
Level 1 95 psf
ASCE 7-10 chapter 7 gives a method of calculating roof and snow loads using this equation:
𝑃𝑓 = 0.7𝐶𝑒 𝐶𝑡 𝐼𝑠 𝑃𝑔
Figure 2-1 (ASCE Fig 7-1 Ground Snow Loads, 𝑃𝑔 , for the United States (Lb/𝐹𝑡 2 )
Using ASCE Table 7-2 given below, the Exposure Factor is 1.0
Table 2-D (7-2 ASCE): Exposure Factor
Figure 2-2 (ASCE Fig 7-7 Drifts Formed at Windward and Leeward Steps)
Sloped Roofs (0.7 * 1.0 * 1.0 * 1.1 * 15) * 0.8 = 9.24 psf
(The Blume Building has a flat roof, so we are using the highlighted values)
Enclosed/Open Enclosed
Wind load varies differently for each level due to different effective area of each floor. Medal
Penthouse is calculated independently with a medal structure resistant, all others calculated
similarly. Using equation (1), velocity pressure qz is determined with parameters.
After velocity pressure qz is determine, average pressure is calculated with equation (2) from
ASCE 7-10, 27.4.1.
𝑝 = 𝑞𝐺𝐶𝑝 − 𝑞𝑖(𝐺𝐶𝑝𝑖) (𝑙𝑏/𝑓𝑡 2 ) (4-13)
(For enclosed building, qi = 0)
Effective Area is calculated by using sum half area of level down and half of level up expect
foundation level and medal penthouse level. For instance, effective area for 3rd floor is half area
of 2nd level and half of 3rd level.
Figure 4-7: Effective Area North Elevation
Lastly, Average Pressure times the effective area give wind load for each elevation for lateral
load design.
Table 4-L Wind Load MWFRS
Wind Load (kip)
Metal Penthouse
Metal Penthouse on top of structure has a similar but different approach according to ASCE 7-
10. From Ch29 for building appurtenance –MWFRS, qz velocity is calculated using equation
from 29.3.2 which it is identical to the qz equation above.
𝑙𝑏
𝑞𝑧 = 0.00256 𝐾𝑧 𝐾𝑧𝑡 𝐾𝑑 𝑉 2 ( )
𝑓𝑡 2
Wind load is calculated using equation 4 from 29.5. Cf is determine to be 1.3 from 29.5-1.
𝐹 = 𝑞ℎ 𝐺 𝐶𝑓 𝐴𝑠 (𝑙𝑏)(𝑁)
Figure 4-9: Lateral story loads for Wind - North and South
Figure 4-10: Lateral story loads for Wind - East and West
Horizontal
Height W Fx
Story WxHx Cvx
(ft) (kips) (kips)
Roof 83.67 2679 224151.9 0.2137 823
Level 6 71.00 3733.5 265078.5 0.2527 974
Level 5 56.83 3733.5 212174.8 0.2023 779
Level 4 44.17 3733.5 164908.7 0.1572 606
Level 3 31.50 3771.5 118802.3 0.1132 436
Level 2 16.50 3876 63954.0 0.0610 235
Total 21527 1049070.2 3853
FIGURE []: EARTHQUAKE LOADS (APPLIED IN ALL DIRECTIONS)
Upon inspection and comparison between different load case combinations, it was
determined that effect from earthquake loading is much larger than wind loading,
making earthquake loads the controlling factor when analyzing lateral load.
3. MATERIALS
The Concrete has a normal weight,150 pcf, with a design compressive strength of 5 ksi.
All reinforcement will be ASTM A706 Grade 60.
Concrete:
Unit weight: 150 pcf
Specified/Design Compressive Strength: f’c = 5 ksi
Reinforcement
ASTM A615 Grade 60 steel
Yield Strength: fy = 60 ksi
*For further detail reference General Notes S0.1
4. ONE-WAY SLAB DESIGN
To span in between beams, a one-way flat slab was selected. This was chosen because
primary reinforcement is only necessary in the direction of the span.
Where 𝑞𝑢 is the factored demand load per unit area (ksf) and:
𝑞𝑢 = 1.2𝑞𝑑𝑒𝑎𝑑 + 1.6𝑞𝐿𝐿 = 𝟐𝟒𝟐 𝒑𝒔𝒇
The demand dead load per unit area (ksf) consists of 2 components, from both the self-weight
of concrete in combination with the superimposed dead load:
𝑞𝑑𝑒𝑎𝑑 = 𝑞𝑠𝑤 + 𝑞𝑆𝐼𝐷𝐿 = 𝟗𝟓 𝒑𝒔𝒇
Example analysis
The slab at second floor between 2 and 3 is the example slab that will analysis in the
following process. This slab has the highest live load of 80 psf and width of 16.5ft.
For construction convenience the analysis consider entire slab is consistent with 80 psf live
load.
Example Design
----INSERT slab calculation.pdf
Design Result
S2 – No5 bars with 12 inch spacing : Slab from 2 to 3 and two slabs from 5 to 6 on every floor.
S1 – No4 bars with 12 inch spacing: All slabs except for the ones using S2 design.
The process of designing the flexure reinforcement for girders and beams is mainly consist of two parts:
analysis and design. The first step is to calculate all the loads that will be carried by the beam or girder.
With all the loads calculated, the moment demand for the beam or girder is obtained through analysis
by using SAP2000. After knowing the demand, Excel spreadsheet is used to design the size and
reinforcement of the member so that it has greater capacity than the demand. The spreadsheet utilized
these calculations in finding the optimum amount and size of steel reinforcement.
𝑀𝑛
𝜇= (5-1)
𝑏𝑑 2 𝑓𝑑′
The shear reinforcement design process is almost the similar to flexure reinforcement only
simpler. The beam or girder was first analyzed by using SAP2000 to see the shear demand of
the members. With the shear demands recorded for each beams and girders, the shear
reinforcement is design by using these equations:
𝑉𝑠 = 𝑉𝑛 /Φ - 𝑉𝑐 (5-7)
𝑉𝑠 = 𝐴𝑣 /𝑠 (5-8)
𝐴𝑣 /𝑠 = 𝑉𝑠 /𝑓𝑦 d (5-9)
𝐴
( 𝑣 )min = max (50, 0.75 √𝑓𝑐′ )𝑏𝑤 /𝑓𝑦 (5-10)
𝑠
𝐴𝑣 𝐴
( )final = max (𝐴𝑣 /𝑠 , ( 𝑣 )min) (5-11)
𝑠 𝑠
𝐴
s = min (𝐴𝑣𝑠 /( 𝑣 )final , min(d/4, 24”)) (5-12)
𝑠
Architectural design present us the design of gridline base on leader of 1, 2, 3, 4, 5 etc. horizontally and
A, B, C vertically. As in our convenience, showed in the example each beam segment is name as B
(beam) – A (vertical order) – 4.1 (horizontal order). For the beams without horizontal leader, it is called
as series of beam on the left that has a number leader. The first beam without a number is called .1 and
the second beam with a number is called .2. For example, B. C-14.2 is the second beam on the right side
of B.C-14. This naming convention will be used in numbers of tables in this section of report and girder
has a similar naming convention as beams but slightly more complicated.
Figure 5-3: Example of naming convention for beams
Every Beam is assigned flexure design, bar cutoff design and shear design. For example, B2-BS2 is stands
for beam flexure design 2, beam shear design 2 and all beams has an identical bar cutoff design. The
following report will explain all designs in details.
5.4.2 Beam Flexure Design
Figure 6-4 is an example beam which indicates B2-BS2. B2 is one of beam callout.
There are total of 4 beam callout (B1, B2, B3, and B4). Each callout represent a segment
of beam that includes end -mid-end section. Each end section attaches to a column or a
girder. Each beam callout has 3 section of design which includes total of 3 cross section
rebar designs.
The beam callout detail is in the next table (Concrete Beam Schedule).
Beam Steel Arrangement Steel Arrangement Steel
Callout (Left) (Mid) Arrangement
(Right)
B1 1-R 1 2-R
B2 2-R 3 2-R
B3 2-R 1 3-R
B4 3-R 2 2-R
Figure 5-5: Concrete beam schedule
The table above explained each Beam callout which is an assembly of three cross section. The
following table and AutoCAD drawing show detail of rebar in each layout callout.
2 No 10 bars on the top and 2 No 10 bars on the bottoms are continues all the way through the
span (3 continues beams). All other bars are extra added on. The added on bars will distribute
evenly showed in drawing “Layout Configurations Graphically” below.
Example Beam that showed in flexure design was called out as B2-BS2. BS2 is stands
for beam shear design2. Shear design is for spacing between stirrups with in the beam. Each
one is specified for both side that has a specific spacing and distance form ones side. For
example, S3 is using No4 stirrups. Make L the length of the beam. From the left side, it extends
to 0.15*L with 8 inch stirrups spacing and then it extends from 0.15*L to 0.42*L with 10.5
spacing. And the right side of the beam has the exact same process. The left and right side
are design to be identical for continent construction purpose.
For the beam cutoffs, all designs are identical for ALL beams in this building. Analysis shows
calculation of all 0 moment location. The locations are all inverted in to reference of the length of
the beam. Make symbol L as the length of the beam. Using the largest negative moment, the
design is L/8 on the left top side of the beam and L/11 on the right top side of the beam. The
rest is the added bar located on the bottom middle of the beam with length of L/1.27.
The naming convention that is used for girders are heavily relied on the architectural gridline that was
given in the plan. The vertical gridline is numbered from 1 until 15 while the horizontal gridline is listed
with alphabets starting with A until E. These gridlines are utilized as the guideline for naming the girders.
As an example, girder located at the horizontal gridline A and spanning from vertical gridline 3 to 5
would be named GA3-5. As some girders span to the shear wall, the name would be slightly different.
Instead of having the gridline number indicating the span, it will be replaced with the letter W. For
example, girder located at horizontal gridline B and spanning from vertical gridline 4 to the shear wall
would be named GA4-W (girder GA3-5 and GA4-W is shown in figure below). For girders that are not
aligned with any of the gridlines, the naming convention will be governed by the gridlines before that.
For an example, the girders that are located between horizontal gridline C and D spanning from vertical
gridline 8 to 10 would be named G(C.1)8-10.
Figure 5-10: Example of girder naming convention
Every girder is assigned with flexure reinforcement design and shear reinforcement design. As
shown in the figure, G1-GS2 would indicate that the girder has flexure design 1 and shear
design 2. The following report will explain all the designs.
GX1 1
Figure 5-12: Concrete girder schedule
There are total of 10 different rebar layout that will be used for the flexure design (1, 1-R, 2, 2-R,
3, 3-R, 4, 4-R, 5, and 5-R). Each rebar layout will have 2 no. 10 bars on the top and 2 no. 10
bars at the bottom that will be continuous all the way through the girder and have separate
arrangement for the added bars. The layout callout is shown in the table below (Concrete
Layout Schedule) and the arrangement is shown in the drawing “Layout Configurations
Graphically”.
Layout Size (inch) Top Bars Bottom Bars Moment Capacity (k-ft)
Callout (continuous)
1 18”x28” (2) #10 (4) #10 566
2 18”x28” (4) #10 (6) #10 826
The shear reinforcement of girder is designed with almost similar step as flexure. Analysis was made to
the girders to find the shear demand and the design is made based on the ACI 318-14 code. There are
three designs of shear reinforcement for girders. As an example for the girder with callout G1-GS2 that is
highlighted in the figure above, the GS2 indicates that the girder has shear design 2. Each one of the
design has a specified spacing and distance from both ends of the girder. For example, GS2 indicates
that the no.4 stirrups will be installed from the end of the girder until 0.3*L (with L being the length of
the girder) at both ends of the girder with spacing of 12.5 inches. The middle part will have no stirrups.
The details of the shear reinforcement is shown in table below.
The zero moment location for all the girders are recorded from the analysis through SAP2000. The
shortest rebar with positive moment and longest bar with negative moment is considered as fractions of
length of the beam. These fractions of length will be used as the universal bar cutoff designs for all
girders. With L being the length of the girder, the top left added bar will be extended to the distance of
L/6.5, and top right added bar extended to the distance of L/8.4 and the bottom added bars will have a
distance of L/1.27. The bar cutoff designs is shown in figure below. The only exceptions for this bar
cutoff design would be for the cantilever beams. The cantilever beams would not have any bar cutoff
where the reinforcement will span throughout the girder.
Is A > Live
Width Width 400ft^2 Load
LL Left Right Load and LL> Red Load per
(psf) Length (ft) (ft) Area per ft 100psf? KLL Coeff ft
b.A 50 25.32 4.5 0 113.93 225 yes 2 0.773106 173.95
40 25.32 0 5.25 132.92 210 yes 2 0.773106 162.35
80 16.85 4.5 5.25 164.27 780 yes 2 0.773106 603.02
b.B 80 25.50 4.5 0 114.75 1016.25 no 1 1016.25
125 25.50 0 5.25 133.88 - no 1
b.C 80 8.71 0 5.25 45.74 420 yes 2 0.760182 319.28
50 35.62 4.5 0 160.29 225 yes 2 0.760182 171.04
40 35.62 4.5 5.25 347.30 390 yes 2 0.760182 296.47
From here, a template span is created based on the length of each beam in the span.
The length of each beam in this span is 42’2” – 25’6” – 44’4” accordingly. When in SAP, the live
and dead loads are applied and Moment and Shear envelopes are created through analysis of
different load combinations, loading patterns, and types of supports. Moments of 0 locations are
also noted for bar cutoffs and shear demand is analyzed d-away (3” from each end). The
following tables show our results for this span as well as a figure showing the envelopes.
2. Live Load
The live load are distributed along the length of girders spanning between columns.
Calculation was done using tributary area method, as indicated in Figure ().
Example: for girder A spanning from 1-3
(16.5’+13.5’) 42.167 1
Tributary area: 𝐴 𝑇 = ∗ ∗ = 316.8 𝑖𝑛2 = 2.2 𝑓𝑡 2
2 2 144
Reduced? AT < 400 in2 so NO
Distributed live load: 𝐿𝐿 = 2.2 ∗ 0.05 = 0.11 𝐾/𝑓𝑡
Values for critical axial load and moment were found and indicate in Table().
Exterior Columns Interior Columns
Column Sizing
Initial dimension of the column were found assuming that the axial demand was within 30% of
the column’s capacity. If the initial dimensions couldn’t provide adequate strength, use trial and
error with incremental dimension to determine required concrete area.
Example: for interior columns on level 1-3
Axial demand: 𝑃𝑑 = 1210 𝐾𝑖𝑝.
𝑃𝑑 1210
= 30% → 𝐴𝑔 = = 803.3
𝑓′𝑐 𝐴𝑔 5 ∗ 0.3
As indicated in the figures, then change in demands vary little from floor to floor. Thus, the
designs for columns were categorized into 4 groups:
Type Level
Exterior 1,2,3
Interior 1,2,3
Exterior 4,5,6
Interior 4,5,6
With this configuration, the flexural reinforcement only needs to be changed starting from level 4
and up. Exterior column carries less demands, and will have a smaller dimensions than interior
columns.
These values were then plotted on the P-M interaction diagram for capacity tests. Figure () and
() show that both capacities of the columns on level 1-3 and 4-roof, respectively, lie within
acceptable design region.
3𝑑𝑏 𝑓𝑦 𝜑𝑙 𝜑𝑐 𝜑𝑠
𝑙𝑑ℎ = ( ) [ACI equation 25.4.2.3a]
40 𝜆𝑋
√𝑓 ′ 𝑐
Where:
𝐵𝑎𝑟 𝑑𝑖𝑎𝑚𝑒𝑡𝑒𝑟: 𝑑𝑏 = 0.625 𝑖𝑛.
𝐿𝑜𝑐𝑎𝑡𝑖𝑜𝑛 𝑓𝑎𝑐𝑡𝑜𝑟: 𝜑𝑙 = 1.3 𝑓𝑜𝑟 𝑡𝑜𝑝
𝐶𝑜𝑎𝑡𝑖𝑛𝑔 𝑓𝑎𝑐𝑜𝑡𝑟: 𝜑𝑒 = 1.0 𝑓𝑜𝑟 𝑏𝑙𝑎𝑐𝑘 𝑏𝑎𝑟
𝐵𝑎𝑟 𝑠𝑖𝑧𝑒 𝑓𝑎𝑐𝑡𝑜𝑟: 𝜑𝑠 = 0.8 𝑓𝑜𝑟 𝑏𝑎𝑟 𝑠𝑖𝑧𝑒 ≤ 𝑁𝑜. 6
𝐶𝑜𝑛𝑐𝑟𝑒𝑡𝑒 𝑓𝑎𝑐𝑡𝑜𝑟: 𝜆 = 1.0 𝑓𝑜𝑟 𝑛𝑜𝑟𝑚𝑎𝑙 𝑤𝑒𝑖𝑔ℎ𝑡
𝑑𝑏
𝑐 = 3/4" + = 1.063 𝑖𝑛.,
2
40𝐴𝑡𝑟
𝐾𝑡𝑟 = = 0 (𝑝𝑒𝑟𝑚𝑖𝑡𝑡𝑒𝑑) [ACI equation 25.4.2.3b]
𝑠𝑛
𝑐 + 𝐾𝑡𝑟
𝑋 = min( , 2.5)
𝑑𝑏
𝒍𝒅 = 𝟐. 𝟎𝟑 𝒇𝒕
Required 2.03 ft. for bondage to happen. Smallest column has dimension 2’x2’
Necessary to hook the bars.
Where:
𝐵𝑎𝑟 𝑑𝑖𝑎𝑚𝑒𝑡𝑒𝑟: 𝑑𝑏 = 0.625 𝑖𝑛.
𝐶𝑜𝑎𝑡𝑖𝑛𝑔 𝑓𝑎𝑐𝑜𝑡𝑟: 𝜑𝑒 = 1.0 𝑓𝑜𝑟 𝑏𝑙𝑎𝑐𝑘 𝑏𝑎𝑟
𝐶𝑜𝑣𝑒𝑟 𝑓𝑎𝑐𝑡𝑜𝑟: 𝜑𝑐 = 1.0
𝐸𝑛𝑐𝑙𝑜𝑠𝑒𝑑 𝑡𝑖𝑒𝑑: 𝜑𝑟 = 1.0
𝐶𝑜𝑛𝑐𝑟𝑒𝑡𝑒 𝑓𝑎𝑐𝑡𝑜𝑟: 𝜆 = 1.0 𝑓𝑜𝑟 𝑛𝑜𝑟𝑚𝑎𝑙 𝑤𝑒𝑖𝑔ℎ𝑡
𝒍𝒅 = 𝟏𝟎. 𝟔 𝒊𝒏.
𝑓𝑦 𝑑𝑏
𝑙𝑑ℎ = max (6 𝑖𝑛. , 8𝑑𝑏 , ) [ACI 318-14 equation 18.8.5.1]
65√𝑓 ′ 𝑐
Placement of the walls –The architectural drawing was looked for the right placement of the
wall and tried to make it roughly symmetrical about the centroid. The building perimeter is
mostly glass windows, therefore there were no place for walls. The rational way to put it were
around elevator cores and stairs. The reason we chose the end walls to be L and not C shaped
was due to the right stairs. We couldn’t make the walls all the way to roof by C configuration.
But the left end wall could have been C shaped, and we decided not to go that way since we
wanted the center of mass to be aligned with the center of rigidity.
There are 11 walls total and the naming goes from SW1 to SW8.
Sizing of the walls – In the building of this size and earthquake loads, 18” of thickness was
chosen based on the shear capacity of the wall, and it is a typical dimension for SRCSW. For
the lengths, it was pushed to the maximum possible length that would allow us to build shear
walls without conflicting the architectural drawing. The sizes of each wall can be viewed from
Figure 7-1 below. Note that these walls are not flanged. They are planar walls.
Longitudinal Reinforcements
The area of steel within the walls is going to change at the 4th level of the building, therefore
there are going to be two designs per wall.
30 boundary steels are being used for the analysis with 4 in bar spacing. Practically, it’s usually
around 4 to 6 in since there should be enough space for the bar splicing. The value of 𝑆𝐷𝑆 =
0.859 from Section 2.5.
For the same SW1 wall, Boundary depth is 42 in, which is based on 10 layers of bars spaced 4
in and 3 in to the center of extreme bar. Dead load = 1050.2 kips including self-weight of the
wall, Live load = 1014.6 kips, and Snow load = 31 kips. These results are based on the tributary
area method of the floor plans.
Which is not enough for our demand, but note that this does not include the web reinforcements
and the compression steel, therefore the exact calculation would be much higher than this
result. The plot of P-M interaction diagram will give exact results.
Web reinforcements - Use #5 bars with 13.5 in spacing to satisfy the minimum reinforcement
of 0.25%.
In the spreadsheet input, the steels were grouped into 5 chunks. 1 for each of the boundary
elements and 3 for the web elements. The inputted numbers are shown below Figure 7-2.
The two dots indicates the two load combination for the analysis.
For level 4, the analysis is the same. The demands are of the dead, live, snow loads, and
demand moments are respectively follows.
The area of steel will decrease into 30 #6 bars. The P-M interaction at Level 4 is shows below
Figure 7-4.
There is another way of doing this. By discontinuing some of the #11 steels at level 4 and
continue the remaining ones all the way up. But the issue with that was there weren’t enough
confinement in the boundary elements. The shear reinforcements are spaced 6 in and the
spacing of the confinement had to be smaller than that, if the steel was discontinued. Therefore,
the changing of bars was used at level 4.
Horizontal reinforcements – Shear reinforcement
Steel ratio
𝐴𝑣
𝜌= = 0.0037
𝑏∗𝑠
Which is greater than the minimum required steel of 2.5% so that’s good.
Shear capacity
This is less than our maximum shear that has been calculated early.
Which is enough.
Confinement – When designing for seismic, the boundary elements have to be confined.
Figure 7-5: Confinement figure
Choose spacing as 6 in making it the same as the shear spacing. This results that every layer
has to be confined in the short and long direction.
𝐴𝑔 𝑓𝑐′ 𝑓𝑐′
𝐴𝑠ℎ1 = 𝑠 ∗ 𝑏𝑐1 ∗ max (0.3 ( − 1) ; 0.09 ) = 1.772 𝑖𝑛2
𝐴𝑐ℎ 𝑓𝑦𝑡 𝑓𝑦𝑡
𝐴𝑔 𝑓𝑐′ 𝑓𝑐′
𝐴𝑠ℎ2 = 𝑠 ∗ 𝑏𝑐2 ∗ max (0.3 ( − 1) ; 0.09 ) = 0.6 𝑖𝑛2
𝐴𝑐ℎ 𝑓𝑦𝑡 𝑓𝑦𝑡
Using all #4 confinement bars for 10 layers in the long direction and 3 layers on the short
direction would satisfy the required area.
At level 4, the results are the same. Confine each layer of bars in both directions.
𝑀𝑢
max ( ; 𝑙 ) = 16.33 𝑓𝑡
4𝑉𝑢 𝑤
30 ∗ 𝐴𝑠 400𝑝𝑠𝑖
𝜌= = 0.017 >
𝑏 ∗ 𝐵𝑑 𝑓𝑦
Meaning the whole wall elevation has to be confined the same as the critical section.
Cross section of the wall is shown below, based on the design.
8. Foundation Design
8.1 Design consideration
The foundation type that will be used for this building is shallow foundation type. Due to the
column dimension, the foundation was designed with a square dimension for effectiveness. Mat
foundation will be used to support the shear walls and the mat foundation for the two right shear
walls , SW 8 and 11, will also support three columns beside it due to overlapping foundation
size.The design will be based on the ACI 318-14 codes.
Design criteria:
● The size of the foundation is calculated based on the highest load any column will
support with a total of two loads, exterior and interior loads.
● All of the interior isolated column footings to be the same size based on maximum axial
load.
● All of the exterior isolated column footings to be the same size based on maximum axial
load.
● Column footings was assumed to carry no lateral loads and all the lateral loads will be
carried by the shear walls.
The following equation was used in determining the size of the footing for different columns.
Two way shear or the punching shear is a case where the concrete fails in both direction
breaking at a distance of the footing depth away from the surface in all direction. The punching
shear will be the one controlling the thickness of the designed footings. The strength design
equation was used to find the shear strength in punching shear case.
The two way shear used the following equation and was then compared to the shear strength
equation. The thickness of the footing needs to be controlled so that there is no need for shear
ties in the footing.
The ultimate shear need to be smaller than the shear strength for it to work perfectly. The phi
factor was used for safety factor. The development length of the dowel to transfer the load from
the column to the footing would also control if the calculated thickness is smaller than the
development length required.
8.2.1.3 Flexural reinforcement
For the flexural reinforcement of the footings, we analyze it by assuming that the footing is a
slab sitting on a column. Moment was taken by using equation for calculating moment on a
cantilever slab. Once we computed the moment demand of the footings, we compare it to the
moment capacity by using the following equation.
To find the required reinforcement area for the footing, the moment demand was set to be lower
than the capacity and by manipulating the equation, the minimum reinforcement area could be
found.
8.2.2 Mat foundation (Shear Wall foundation)
The mat foundation was chosen to be the footing type to support the shear wall because the
length and size of the shear wall, which is mostly “L” or coupled wall shaped, do not support the
use of combined or square footings. The main difference between this design and the column
foundation design is that the mat foundation will be designed to resist moment from the lateral
loads that the walls hold.
The lateral loads will cause an overturning moment and the eccentricity bearing, or a non-
uniformed bearing pressure acting against the footing. The axial loads that the walls support will
help to reduce the overturning caused by the lateral loads. The loads was determined by using
the tributary area method and the tributary area is cut in an angle between two side by side
walls.
The design will start by guessing a preliminary size of the footings. The equation that was used
is different from the calculation of the column design as in this case we need to take into
account the moment acting on the footings caused by the lateral loads. The preliminary size
also needs to be larger than the length and width of the covered elements. After approximating
the size, eccentric bearing, overturning moment and shear will be checked and the size will
change regarding to this requirements. Lastly, the flexural reinforcement is calculated for the
mat foundation.
8.2.2.1 Overturning moment
For simple approximation of the size of the foundation, overturning moment was calculated for
the footing. The overturning moment will be the first check on whether the footing size could
accommodate the moment that the lateral loads created. ACI stated that the foundation only
needs to withstand 75% of the lateral loads in the walls. The loads that will control is the seismic
load as the building is located in the area with a very frequent seismic activity. The ASD load
combination that was used in this analysis is D + 0.75(0.7E) + 0.75L+ 0.75S which shows the
least amount of dead load for the highest amount of lateral or earthquake load. The overturning
moment will be resisted by the dead load of the wall. The length of the foundation needs to be
adequate so that the moment caused by the lateral loads could be equalized by the moment
caused by the dead load of the building.
After the eccentricity was calculated, the length of the footing that resist the bearing pressure,
Le, is calculated and was used to find the maximum bearing pressure using the following
equation. Where B is the shorter distance of the foundation.
This bearing pressure shows the maximum bearing pressure that footings with that eccentricity
will have for the bearing pressure. Therefore the maximum bearing pressure, qmax, could not
exceed the allowable bearing pressure, qall .
8.2.2.3 Shear
The shear needs to be checked as the shear will likely be the one controlling the thickness of
the mat foundation. One way shear as well as the two way shear or the punching shear still
need to be checked in order for the foundation to resist shear without the need to use any shear
stirrups. LRFD will be used for the load combination.
For one way shear, the analysis will be similar to the column foundation design. The footing was
assumed to be an upside down slab sitting on a column. The moment will be calculated at the
depth of the footing away from the nearest wall surface to take into account the 45 angled shear
failure.
For punching shear, it is also similar to the column footing design. The moment was taken 0.5d
away from the wall surface as it is considered the critical length of the 45 degree break. The
analysis considered all four side broke off at the same. The punching shear will most of the time
controls the thickness of the footing.
Name Width (ft) Length (ft) Thickness Rebar long Rebar short
(in)
Interior 9.5 9.5 42 (9)#9 (9)#9
columns
Exterior 7 7 26 (7)#7 (7)#7
columns
Mat 27 40 48 (25)#11 25#11
foundation L (top and (top and
bottom) bottom)
Mat 30 50 72 (44)#11 (20)#11
foundation (top and (top and
M bottom) bottom)
Mat 35 45 48 (25)#11 (20)#11
foundation (top and (top and
R bottom) bottom)
The Penthouse resides on the top of the Blume building. It spans 258 feet North to
South and 25.5 feet East to West. It is surrounded by a mechanical screen and has an
overlapping section on the South side that extends to the lower roof level. The height of the wall
is 11 feet in all areas except the south side which extends 3 feet past marker 13 in plan and is
25 feet 2 inches tall.
Since Earthquake loading controls at 134 kips, the penthouse will be designed with
Square HSS metal columns at each in the plan view shown below. Running East to West, there
will also be a beam that spans the 25’6” gap to account for the moments imposed on the
penthouse through loading. The calculations are shown in the Calculation Package show our
design process based on the loading.
Figure 9-2 Plan View
Bolt Design:
Due to our moment resisting frame, the analysis can be conducted with only a Shear
force in the x-direction and a Normal Force in the z-direction. To complete the analysis, the
program Hilti PROFIS Anchor was utilized to size the bolts and check for modes of failure. This
includes concrete breakout strength, shear load, tension load, pullout strength and steel
strength. Based on our designs above, the software was used to:
Since there are 2 different loading conditions, two analyzes were run with both base
plates to ensure the ACI 318-14 design criteria was met. These results will be listed in the
Calculations Package. The loading conditions and configurations are shown in the following
figures.
Figure 9-5 11’ HSS 7x7x1/2” column w/ 4 Heavy Hex-head ASTM F 1554 Gr. 55 5/8” bolts on
a ¼” A36 Steel Plate
Figure 9-6 25’2” HSS 7x7x1/2” column w/ 4 Heavy Hex-head ASTM F 1554 Gr. 55 1/2” bolts on
a ¼” A36 Steel Plate
Loading follow stiffness and since the 25’2” columns at the South end of the building are
less stiff, the figure below denotes how the load will act. This requires 2 designs for the base
plate, welds, and bolts into the slab below.
𝐴𝐸
𝐾=
𝐿
Beam Design:
Applying the earthquake loading to these beams, we find the following loading conditions
on the beams, which result in a moment demand of 175 k-ft. Consulting the steel construction
manual, the iterative process of selecting the beam finds that HSS 7x7x1/2” is sufficient with a
stress of 45.6 ksi, which is under the yield stress of 5 ksi.
𝑀𝑐 175𝑘−𝑓𝑡(3.5𝑖𝑛)∗12𝑖𝑛
𝜎= = = 45.6ksi <50ksi
𝐼 80.5𝑖𝑛4 ∗2𝑐𝑜𝑙𝑢𝑚𝑛𝑠
The next thing to look at would be to apply the loading to the moment frames in order to
determine designs for the beams that span East to West as well as the ones running North to
South. From the analysis shown below, the E-W spans have a moment demand of 87 k-ft and
the N-S spans are a maximum of 103.66 k-ft.
East to West Span: W18x40 (moment capacity of 90.5) (Table 3-6 AISC Steel)
North to South Spans: W18x55 (moment capacity of 112)
Since determining moment frame connections to HSS columns is outside the scope of
the project and class, they will assumed to be bolted flange plates the will needed to be sized,
welded and checked for flange stiffness, tension, and panel zone shear.
15.88
K
6.94 K
Equation F11-1 procedure for LFRD determines the required thickness of baseplate
𝑃𝑢 26.38𝑘
𝑓𝑝𝑢 = = = 0.218 ksi
𝐴𝑒𝑓𝑓 121𝑖𝑛2
𝑃𝑢 28.32𝑘
𝑓𝑝𝑢 = = = 0.234 ksi
𝐴𝑒𝑓𝑓 121𝑖𝑛2
𝑓𝑝𝑢 𝑙 2
𝑀𝑢 = 𝜑𝑏 = 0.9
2
𝑡𝑝 2
𝑍= 𝑀𝑢 = 𝑀𝑝 = 𝐹𝑦 𝑍
4
Setting 𝑀𝑢 = 𝜑𝑏 𝑀𝑛
2𝑓𝑝𝑢 𝑙 2 2(0.218𝑘𝑠𝑖)(4.35𝑖𝑛)
𝑡𝑝(𝑟𝑒𝑞) = √ =√ = 0.241 in (11’)
𝜑𝑏 𝐹𝑦 0.9(36𝑘𝑠𝑖)
2(0.234𝑘𝑠𝑖)(4.35𝑖𝑛)
=√ = 0.251 in (25’2”)
0.9(36𝑘𝑠𝑖)
Therefore we can use 1/4” A36 steel plate for the 11’ columns in the penthouse and use 1/2”
A36 steel plate for the 25’2” columns.
Weld Design:
From table J2.3 In the steel manual, the effective throat is determined by the thinner
material. Since the base plates are is 1/4” and 1/2” thick and the HSS is ½” thick, the effective
throats are 1/8” and 3/16” accordingly..
Also, since the base metal is A36 and ≤ ¾” thick, the weld will consist of a 60 &70ksi
filler material (matching filler).
Connection Design
Minimum Development Length: Slabs to Columns
Development length, or the minimum length required to ensure enough bondage between
reinforcing steel from slab and column’s cross section, can be calculated using:
[ACI equation 25.4.2.3a]
Where:
lbd = 0.0005*fy*db
will be used to calculate the length into the column for lap splice.
The development length into the footing will be calculated using the equation
0.02fy/(sqrt(f'c))*db=ldb.
The footing is deep enough to support the length so no actual hook length is needed for the
development length requirement. However, to ensure an adequate connection strength, hooks
will be made for safety reason.
11.0 Codes and References
ASCE 7-10 Minimum Design Loads for Buildings and Other Structures
ACI 318-14 Building Code Requirements for Structural Concrete
Foundation Design: Principles and Practices; Donald P. Coduto (3rd edition)
Reinforced Concrete: Mechanics and Design; James K. Wight, James G. MacGregor (7th
edition)
AISC: Steel Construction Manual
AISC Seismic Design Provisions
WABO-SEAW Snow Load
12.8 Summary of Weekly Team Meetings