ÍTEM DESCRIPCIÓN REQUERIDO OFFERED

Network Coomunication
1.00 Switch Required / 2 Lawer
1.01 Model By vendor
1.02 Manufacturer By vendor
1.03 Protocol IEC 61850
Multimode Mode - Fiber
1.04 Network Ports
Optic

According to IED´s Meters,


1.05 Network Ports
relay and controlers

Battery Charger
1.06 Manufacturer VTS
1.07 Quantity 1
1.08 Model / Catalog N° VTS
1.09 Type SCR
1.10 Enclosure Nema 12
1.11 Mounting Floor
1.12 Float Voltage (adjustable) VTS
1.13 Equalize Voltage (adjustable) VTS
1.14 Recharge time (maximum) 8 hours
1.15 Nominal DC Output Current Rating By Vendor
1.16 Maximum ripple 100 mV rms
1.17 Audible noise (maximum) 65 dB at 1.5 m
Measurement, Protection relays, Control, Alarms and
1.18 Required
Lights
1.19 Output Voltmeter Required
1.20 Output Ammeter Required
1.21 Low DC Voltage Relay Required
1.22 DC Output Circuit Breaker Required
1.23 Electronic short circuit and Overload protection Required

1.24 Manufacturer's multifunction standard control/display Unit VTS

Alarms (minimum):
1.25 AC Failure Required
1.26 DC Failure Required
1.27 High VDC Required
1.28 Low VDC Required
1.29 Ground Detection Required
1.30 Overload Required
1.31 High or Equalize ON Pilot Light Required

Battery Bank

1.32 Type Sealed Maintenance Free

1.33 Quantity 1

1.34 Application Switchgear Control Power

1.35 Manufacturer VTS


1.36 Model / Catalog N° VTS
1.37 Cell Container VTS
1.38 Nominal Voltage VDC 125
1.39 Maximum Voltage VDC 140
1.40 Minimum Voltage VDC 105
1.41 Equalize Voltage (Volt Per Cell) 2.37
1.42 Flotation Voltage (Volt Per Cell) 2.25
1.43 End-of Discharge Cell Voltage (Volt Per Cell) 1.75
1.44 Minimum Amper-hour Rating Calculated VTS
Amper hour Capacity at 8 hr rate o discharge to 1.75 Volts
1.45 VTS
per Cell

1.46 Battery constant-current discharge Table, in A (@25°C) VTS

Dry Type Transformer (Auxiliary Services)


1.47 Manufacturer VTS
1.48 Place of Manufacture VTS
1.49 Type High Efficiency Dry type
1.50 Installation Type Indoor Floor Mounted
1.51 Enclosure NEMA 12
1.52 Rated Ambient Temperature (Maximum) VTS
1.53 Rated Ambient Temperature (Minimum) VTS
1.54 Rated Ambient Temperature (24 hrs mean Max) VTS
1.55 Height above sea level 4500 masl
1.56 Cooling VTS
1.57 Connection Dyn 11
1.58 Rated Power KVA See SLD
1.59 Primary - no load voltage KV 0.48
Secondary - no load voltage
1.60 KV 0.4 - 0.23

1.61 Number of Phases 3


1.62 Frequency Hz 60
1.63 Windings VTS
1.64 Tapchanging - Off Circuit/On Line VTS
1.65 Number of positions VTS
1.66 Voltage Rating kV VTS
1.67 No Load Primary Current A VTS
1.68 Magnetizing Inrush Current A VTS
1.69 Excitation Current at 100% Rated Volt % VTS
1.70 Excitation Current at 110% Rated Volt % VTS
1.71 Temperature Rises ⁰C VTS
1.72 Rating: kVA VTS
Class
1.73 Secondary Lightning Arrester VTS
(kV)
Efficiencies at:
1.74 100% % VTS
1.75 75% % VTS
1.76 50% % VTS
1.77 25% % VTS
1.78 Load Losses at Full Load kW VTS
1.79 No Load Losses kW VTS