208‐230V Heat Recovery

REYQ_PBTJ

Simultaneous heating and cooling from a single 
system.
Key features include:
• Extended operating range with the ability to operate 
at outdoor ambient conditions down to 23°F with an 
option down to ‐4°F  in cooling mode and down to 
‐4°F in heating mode.
• Long refrigerant piping lengths with up to 3,280 ft. of 
total “one‐way” piping in the complete piping 
network
• Advanced continuous heating during defrost cycle
• Automatic charge function

Outdoor Units - REYQ_PBTJ Heat Recovery 6 Ton 8 Ton 10 Ton 12 Ton 14 Ton 16 Ton 18 Ton
Name REYQ72PBTJ REYQ96PBTJ REYQ120PBTJ REYQ144PBTJ REYQ168PBTJ REYQ192PBTJ REYQ216PBTJ
Model 1x REMQ96PBTJ + 1x REMQ120PBTJ +
Combination 2x REMQ96PBTJ
1x REMQ72PBTJ 1x REMQ96PBTJ
Rated Cooling Capacity Btu/h 69,000 92,000 114,000 138,000 160,000 184,000 206,000
Rated Heating Capacity Btu/h 77,000 103,000 129,000 154,000 180,000 206,000 231,000
Operating Range - Cooling °F DB (-4) 23 – 122 (-4) 23 – 122 (-4) 23 – 122 (-4) 23 – 122 (-4) 23 – 122 (-4) 23 – 122 (-4) 23 – 122
Performance
Operating Range - Heating °F DB 0 - 77 0 - 77 0 - 77 0 - 77 0 - 77 0 - 77 0 - 77
Power V/Ph/Hz 208-230/3/60 208-230/3/60 208-230/3/60 208-230/3/60 208-230/3/60 208-230/3/60 208-230/3/60
Sound Pressure Level @3ft dB(A) 58 58 60 62 61 62 62
Fan Airflow cfm 6,700 6,700 7,410 8,300 6,530 + 6,350 6,530 + 6,530 7,060 + 6,530
Vertical Pipe Length Above ft. 164 (295 with option) 164 (295 with option) 164 (295 with option) 164 (295 with option) 164 (295 with option) 164 (295 with option) 164 (295 with option)
Vertical Pipe Length Below ft. 295 295 295 295 295 295 295
Refrigerant
Actual Pipe Length ft. 540 540 540 540 540 540 540
Piping
Equivalent Pipe Length ft. 620 620 620 620 620 620 620
Total Pipe Length ft. 3,280 3,280 3,280 3,280 3,280 3,280 3,280
Weight lbs. 730 730 730 747 560 + 450 560 + 560 560 + 560
Unit
Dimensions (H x W x D) in. 66-1/8 x 51-3/16 x 30-1/8 (66-1/8 x 36-5/8 x 30-1/8) x 2
20 Ton 22 Ton 24 Ton 26 Ton 28 Ton
Name REYQ240PBTJ REYQ264PBTJ REYQ288PBTJ REYQ312PBTJ REYQ336PBTJ
1 x REMQ120PBTJ +
Model 2 x REMQ96PBTJ + 1 x REMQ120PBTJ + 2 x REMQ120PBTJ +
Combination 2 x REMQ120PBTJ 1 x REMQ96PBTJ +
1 x REMQ72PBTJ 2 xREMQ96PBTJ 1 x REMQ96PBTJ
1 x REMQ72PBTJ
Rated Cooling Capacity Btu/h 240,000 251,000 274,000 297,000 320,000
Rated Heating Capacity Btu/h 257,000 283,000 308,000 334,000 360,000
Operating Range - Cooling °F DB (-4) 23 – 122 (-4) 23 – 122 (-4) 23 – 122 (-4) 23 – 122 (-4) 23 – 122
Performance
Operating Range - Heating °F DB 0 - 77 0 - 77 0 - 77 0 - 77 0 - 77
Power V/Ph/Hz 208-230/3/60 208-230/3/60 208-230/3/60 208-230/3/60 208-230/3/60
Sound Pressure Level @3ft dB(A) 63 62 63 64 64
Fan Airflow cfm 7,060 + 7,060 6,530 + 6,530 + 6,350 7,060 + 6,530 + 6,350 7,060 + 6,530 + 6,530 7,060 + 7,060 +6530
Vertical Pipe Length - above ft. 164 (295 with option) 164 (295 with option) 164 (295 with option) 164 (295 with option) 164 (295 with option)
Vertical Pipe Length - below ft. 295 295 295 295 295
Refrigerant
Actual Pipe Length ft. 540 540 540 540 540
Piping
Equivalent Pipe Length ft. 620 620 620 620 620
VRV

Total Pipe Length ft. 3,280 3,280 3,280 3,280 3,280


Weight lbs. 560 + 560 560 + 560 + 450 560 + 560 + 450 560 + 560 + 560 560 + 560 + 560
Unit (66-1/8 x 36-5/8 x
Dimensions (H x W x D) in. (66-1/8 x 36-5/8 x 30-1/8) x 3
30-1/8) x 2
For all equipment installation and application limitations please refer to the specific Engineering Data Books.

Low Ambient Cooling Wind Hood / Hail Guard Accessory Kit - Full Kit consists of 4 complete hood sections for the back, left, right and top portions of the outdoor unit.
Partial Kit for multiple unit installations consists of 2 complete hood sections for the back and top portions of the outdoor unit only.
Full Kit Model Indoor Units
DACA-WH36F REYQ144-336PBTJ Note: The VRVIII wind hood accessories are designed to be used in conjunction with an outdoor unit field setting and applicable 
DACA-WH51F REYQ72-144PBTJ branch selector unit dip switch settings to engage the low ambient cooling feature for heat recovery units only. Please refer to 
Partial Kit Model Indoor Units the DACA WH36_51F/P Installation Manual for additional information.  
DACA-WH36P REYQ144-336PBTJ This accessory is currently available for all 36‐5/8” and 51‐3/16” width heat recovery units.
DACA-WH51P REYQ72-144PBTJ