UCUV-S Series

Air Cooled Condensing Units


Range 7 TR to 136 TR (25 kW to 480 kW)
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Contents Introduction
Introduction ....................................... 2 Selection Procedure ....................... 15
Legend.............................................. 2 Typical Wiring Diagram................... 12 UNTES UCUV-S series Air cooled
Nomenclature ................................... 2 Electrical Data ........................... 18-20 condensing unit are designed for the use on
General Features.............................. 3 Dimensional Data ...................... 20-23 systems with indoor units connected to remote
Component Features ........................ 3 Loading Points ........................... 23-24
condensing units located outside either on
Control Panel .................................... 4 Location & Space Requirements .... 25
Unit Controller................................... 5 Unit Installation ............................... 26 ground or on roof level.
Optional Features ............................. 5 Typical Refrigerant Piping............... 27
Engineering Specificatio ............ 7-10 Recommended Line Sizes......... 28-29 UNTES UCUV-S units are manufactured to
Capacity Ratings ....................... 11-14 Guide Specificatio ......................... 30
meet the requirements of the gulf severe
Capacity Control Steps ................... 15
climatic conditions.

Legend The UCUV-S Air Cooled Condensing unit


are ideal for warehouses, large halls, schools,
The following abbreviations are used throughout this manual:
mosques, or wherever the requirement calls
BPF..... By-pass Factor MBh.... BTUH x 1000 for a heavy duty unit with a scroll hermetic
cfm ..... Cubic feet per minute Ph ....... Phase compressor.
EER .... Energy Efficiency Ratio Pa ....... Pascals
Hz ....... Hertz PD ....... Pressure Drop
inwg .... Inches of water gauge PI ......... Power Input UCUV-S series Air cooled condensing unit
kW ...... kilowatts RPM.......Revolutions per Minute ( Hermetic Scroll ) are available in 50 models
kg ......... kilogram TR ....... Tons of Refrigeration = 12 MBh covering nominal capacity ranges from 7 TR –
lbs ........ Pounds weight ( British units ) V .......... Volt 136 TR (25 kW to 480 kW) in 50Hz and 60Hz.
L/S ...... Liters per second

UCUV-S series provide efficient operation, wide


Nomenclature range of design flexibility coupled with packaged
concept requiring least on-site work.
UCU V - 5 1 008 S Y
UCUV-S series Air Cooled Condensing units
Air cooled are used for commercial and industrial
Power Supply Code
condensing unit Y: 380V-415V/3Ph/50Hz applications where high effic ent condensing
V-Shape Condenser P: 440V/3Ph/50Hz units are needed to match an indoor central
Construction R: 380V/3Ph/60Hz
station AHUs or coils to get maximum
E: 460V/3Ph/60Hz
Power Supply 5 : 50Hz T: 220V/3Ph/60Hz performance advantages of split sytem with
Frequency 6 : 60Hz reasonable initial cost.
No. of Refrigerant Circuits
Scroll Compressor
Nominal Capacity (TR) (R-134a)

UNTES reserves the right to change, in part or in whole the


specifications of its Air Conditioning Equipment at any time
in order to add the latest technology. Therefore, the
enclosed information may change without any prior notice.
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

General Features Parallel Operation


A parallel compressors installation, with common suction line
The UCUV-S series is a modern, diversified and
and common discharge line, give reduced operating cost through
environment friendly series of air cooled condensing unit
greater control of capacity and power consumption. This is
which use R - 134a as a refrigerant.
achieved by staggering compressor switch-on sequences that
allow the parallel system to match its power with the capacity
The complete UCUV-S condensing unit provides an extremely
needed. By switching-off individual compressor from parallel
rugged, heavy duty, long-life and energy efficient that will provide
installation, while other compressor is operating 100%, the
higher efficiency over a long and extended life. What
improved part load efficiency can be achieved. The specially
makes UCUV-S series the pride of UNTES products is the
developed and adopted oil equalization system ensures correct
use of :
compressors operation, oil balancing between compressors and
• • High efficiency totally sealed hermetic scroll compressor. reliability.
• • Totally enclosed, Class F insulated, IP55 protected
condenser
• fan motor.
Condensers
• • Heavy duty condenser optimised in design for long-life
Condenser coils are manufactured of seamless copper
• maintenance free operation.
tubes mechanically bonded to aluminum fins to ensure
• • Cabinet construction specifically designed for Gulf
optimum heat transfer.
• climates.
• • IP 54 Electrical panel.
• • Factory installed, advanced and user friendly All coils are tested against leakage by air pressure of 450 psig
microprocessor (3100 kPa) under water. All standard coils are 2, 3 or
• based control system. 4 rows/14 FPI, 3/8” (9.5 mm) O.D. tubes. An integral
• • Interface capability with major BMS protocols (option). subcooling circuit is provided to increase the cooling
capacity, without additional operating cost.
The UNTES UCUV-S series air cooled condensing units are
For different application requirements, other optional
durable, dependable, strong, reliable, versatile, quiet and energy
condenser fin materials are available
efficient. Wherever a heavy duty condensing unit is required,
the UCUV-S series should be an automatic choice. • • Copper fins.
• • Electrotinned Copper Fins.
• • Copper finned coils with electro-tinned after
manufacturing.
• • Precoated Aluminum fins
Component Features • The pre-coated is hydrophobic polyurethane resin. This
option provides substantial corrosion protection beyond
standard coil construction.
Compressor • • Aeris Guard Coil Coating
• The Aeris Guard Coil is a self etching high performance
Compressors used in UCUV-S condensing unit series are modified epoxy finish that is specifically designed to coat
hermetically sealed, compact scroll with the following features: and protect Aluminum and Copper surfaces. In addition,
the coating is ideal for the protection of ferrous and non
ferrous materials.
• •High Efficiency.

• •Quite operation, Low Sound levels.
• •Compact and light .
• •Limited wear.
• •70% fewer moving parts than comparably sized
reciprocating compressors
• •Unique ability to hadle liquid refrigerant.
• •Suction gas motor cooling.
• •Suction screen.
• •Centrifugal oil pumps with filter and magnet.
• •Brazed fittings or Rotalock options.
• •Two refrigerant circuits on larger units provides efficient
part load.
• •No internal valves.

3
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

UNTES UCUV-S series, all models, are restricted to a 14FPI Refrigerant Charge
(1.8mm) fin spacing condenser coil.
Gulf dust storms and the general level of available maintenance UCUV-S Air Cooled Condensing units are shipped
in Gulf countries ensures this condenser coil design shall provide with nitrogen holding charge only. Actual charging
long life and maintenance-free operation with the least with refrigerant R-134a should be done at site.
possibility of operational blockage on the condenser. Ample
condenser surface and sensible air flow across the condenser
ensures a low temperature differential between
condensing temperature and the high Gulf ambients making Piping connections
the UCUV-S condensing unit perform efficiently and durably.
UCUV-S Air Cooled Condensing units piping connections
Condenser Fans come, as standard, terminated with sealed and soldered
copper pipe ends.
Condenser fans are propeller type, aluminium alloy
blades, directly driven by electric motors. Normal installation would require the cutting off (using roller-type
tube cutters) of the ends prior to connections being resoldered
M o t o r s a r e To t a l l y E n c l o s e d A i r O v e r (TEAO) and connected to the field supplied refrigerant pipework
six pole with class ‘F’ insulation and minimum IP55
protection. Refrigerant Pipe work
The TEAO and class ‘F’ insulation features ensure long UNTES UCUV-S series Condensing units are provided
life and are unique for UNTES. with all internal piping, using ACR grade copper
tubing, between compressor and condenser.

The motors are factory wired, using wires specially selected for Loose supplied liquid line refrigerant controls are available as
high ambients operation, to unit control panel where the motor an option for field installation (Please specify CRSP). When
contactors are located to control the operation of these motors. ordered this option, the unit should be supplied with a correctly
sized thermostatic expansion valve, liquid line solenoid valve,
The condenser fans are individually statically and dynamically liquid line sight glass/moisture indicator and filter drier having
balanced at the factory. Complete fan assembly is provided with flared or soldered ends isolatable with one shut-o f valve.
suitable acrylic coated fan guard.
Shut-off valve for the other side of the filter drier can be supplied,
if option CXFV is specified

Casing/Structure
Designed for ease of handling and low cost to install. The
UCUV-S Air cooled condensing Units are factory assembled Control Panel
and mounted on a rigid base. The unit casing used in
UCUV-S condensing units is made of zinc coated The unit mounted control panel enclosure is fabricated out of heavy
galvanized steel sheets conforming to JIS-G3302 and gauge sheet steel in phosphatized powder coated baked finish.
ASTM A653 which is phosphatized then baked after an The enclosure conforms to IP54 as per guidelines in IEC 529.
electrostatic powder coat of approximately 60 microns.
A hinged access door and key-fastener is provided for easy access
This nisha ndc oating passa 1 000h oursi n5 % s alts prayt esting and security. The panel is factory wired in accordance with NEC
at 95°F (35°C) and 95% relative humidity as per ASTM B117. 430 & 440, labelled, tagged and features 220V / 240V controls.

The entire assembly comes complete with lifting holes on • All compressors are with DOL starting.
the base frame for rigging and installation. Acess panels are
• Individual compressor & condenser fan motor contactors.
provided for easy service and maintainance
• Motor protector circuit breaker for condenser fan motors.
Options available include hot dipped galvanized base frame
and structural members aluminium/stainless steel panels are • Voltage monitoring module for protection against under
available, on request, as option. voltage, over voltage, phase loss, phase reversal and
phase unbalance of the incoming voltage.
• •Control circuit breaker.
• •Control circuit on/off switch.
• •Microprocessor control boards.
• •Control Relays.
• •Power and control terminal blocks.

ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Microprocessor Controller System Control Philosophy


Unit is enabled from the on/off switch in the control
panel. Control is based on room temperature sensed by
room unit. Compressors will be staged based on the set point
and actual room temperature. On an increase in room
temperature, cooling stages will be added and on a decrease
in room temperature, cooling stages will be removed from the
system.
Microprocessor Controller System Protection
All UCUV-S series condensing units are equipped with a full The intelligent microprocessor based controller monitors
function microprocessor based controller as a standard all the safeties related to the unit and makes the necessary
feature. The controller is factory programmed for the control of protections, by shutting down the entire unit or the
AHU fan motor, compressors and condenser fans. The effected circuit. The protection includes:
controller comes with a built in keypad and display for simple
• Low suction pressure.
but meaningful man machine interface. This controller provides
complete operational control for the unit and has built-in auto • High discharge pressure.
diagnostic capability that can signal normal operation or alarm • High compressor motor temperature. (For compressors
conditions as well as shutting down the unit or system if with electronic module).
necessary.
• Compressor short cycling.

BMS Connectivity (Optional)


Volt free contacts for run status, common fault status,
auto mode status and provision for remote on/off shall be
Room Unit provided as option if required.
The controller comes with a loose supplied sleek and elegant In addition, the UCUV-S microprocessor can
design room unit for installing in the conditioned space. support the major BMS protocols such as BACnet, Modbus
Communication between unit controller and room unit is through & LON. Extra hardware may be required depending on the
two wire interface. The communication cable should be 2 protocol.
core, twisted pair, unscreened with stranded conductors
(as per KNX specification). Maximum distance between room Optional Features
unit and controller can be 700 meters. The room unit has a built
Alternative Condenser Material
in sensor for measuring the room temperature. It transmits room
temperature, set point, unit operating mode, operating schedule Made of copper tubes and alternative fin material and/or protective
etc. to the unit controller. Control of the compressors is based on coating.
room temperature and the set point, as standard. If unit control
needs to be based on duct temperature, please specify during • For Pre Coated aluminum fins, specify (FAP).
time of order. • For Aluminum Fins with Aeris Post Coat Protection, specify
(FAA).
• For Copper Fins, specify (FC).
The Main Features of the controller are as follows: • For Copper Fins with Aeris Post Coat Protection,specify
• Built in LCD display with back light. (FCA).
• Roll & push knob and 3 function buttons. • For electrotinned Copper Fins only, specify (CFT).
• Battery backed up built in real time clock. • For Copper Finned Coils electrotinned post manufacturing,
• Multiple authorization level to provide tight security for the specify (FCT).
control system.
• Capacity control based on room temperature or return air
Condenser Coil Guard (CGP)
temperature.
Galvanized wire mesh frame with painted finish for condensers.
• Alarm history.
Recommended on ground level installations where coil needs
• A sleek & elegant design room unit.
to be protected against vandalism.

Display Information Galvanized Frame And Base (GFB)


UNTES UCUV-S series condensing units offer LCD Steel frame and base which are hot dip galvanized
display which allows the operator to access different after manufacturing process. This is recommended for highly
parameters of the unit. Operator can view and change the corrosive environments.
unit parameters. The display information includes:
• Status Pressure Gauges (SDG1)
• Outputs Suction and discharge pressure indication of each refrigerant
• Inputs circuit. Gauges are mounted outside the Control Panel.
• Alarms
Pressure Relief Valve (PRV)
• Set points To protect the unit from being over-pressurized.
• Password

5
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Rotalock Valves on compressors (RVC) Ammeter & Phase Selector switch (AMPI)
For additional facilitation of maintenance of unit. To indicate running AMPS on main incomer of the unit.

Condenser Fan with polyglycoat coating (PGF) Voltmeter & Selector Switch (VSS)
For incoming line voltage.
To provide protection against corrosion for condenser fans.

Marine Paint (MP) Soft Starter (SFS)


To provide increased corrosion resistance coastal environments To reduce the starting current of compressors using reduced
and offshore locations. voltage starting method. Compressors will be started using
electronic solid state soft starters that will ramp up the speed of
Condenser Fan motors with anti-condensation the compressors to rated speed within few seconds thus reducing
heaters built-in (CFMA) the mechanical & electrical stresses .
Where application so requires.
Suction Pressure read out Capability (SPC)
Isolated Condenser Fan Motors (CMS) Additional transducer in suction line to display suction pressure
For elimination of extraneous noise and vibration from condenser in microprocessor.
fan motor, the motors are individually isolated from the frame.
BMS Interface Volt free Contacts (BMVF)
Volt free contacts for run status, common fault status, auto mode
Hot Gas Bypass System (GBP)
With solenoid valve to enable operation of a large sized unit at low
loads, like during low ambients due to application
requirements. status and provision for remote on/off shall be provided as option
if required. For additional requirements, please contact
UNTES.
Pump Down Facility (PD)
The compressor will switch off each time with a Pump Down Cycle
in order to prevent Liquid refrigerant migration to the compressor BMS Interface thru protocol (BMSP)
during off Cycle periods. For interfacing the units with major BMS protocols such
as BACNet, Modbus or LON. Extra hardware may be
With this option, each circuit will be provided with an additional
requireddepending on the protocol
discharge check valve to prevent Refrigerant Migration from High
side to Low side when the compressor is off.
Options for Field Installations
IP-55 Control Panel (ICP)
IP55 enclosure for extra protection against elements.
Anti-vibration mounts (CAVM)
Recommended for roof mounted units or other locations in
the vicinity of occupied spaces, where noise/vibration may be
Low Ambient Operation Kit (LAO) objectionable.
For operation down to lower than normal Gulf ambients. It is also
required for special applications. Hi-Lo Gauges (CSDG1)
Without piping or isolating pet cocks.
Main Isolator (Without door interlock) (ISO)
For main power isolation. (consult UNTES) Liquid Line Controls (CRSP)
Comprises of correctly sized thermostatic expansion valve,
Control Transformer (CXT) suitable solenoid valve,filter drie ,sight glass and one number
This option is necessary and available for UCUV-S models rated shut-off per circuit.
for 440V/3PH/50Hz or 460V/3PH/60Hz only. When ordering for
these voltages this option must be ordered. Extra Shut Off Valve (CXFV)
To fully isolate filter drier, an additional shut-off valve can be
Circuit Breaker for Compressor (CBC) incorporated in the liquid line. Must be ordered, if required, with
For those electrical specification calls for additional over lo d CRSP option.
and short circuit protection.
Duct Temperature Sensor (DTS)
In order to control the unit based on return / supply air duct
External Overload Protection (EOP) temperature.
For those electrical specification requires additional overload
protection for the compressors. Special custom built units incorporating specially required features
like units with anti-condensation resistance heaters embedded
Ammeter & Phase Selector switch (AMPC) in condenser motors and for off-shore application, special units
To indicate running AMPS of each compressor. with stainless steel panels can be manufactured as per customer
requirement.

Contact UNTES for all such applications or requirements.

6
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

ENGINEERING SPECIFICATIONS - 50 HZ
Model UCUV 51008-S 51010-S 51013-S 52015-S 51016-S 52017-S 52019-S
BTUH 86000 110000 146000 168000 176000 190000 220000
Cooling Capacity (1)
W 25205 32239 42790 49238 51583 55686 64478
BTUH 74150 97100 129550 145550 156100 164200 190350
Cooling Capacity (2)
W 21732 28458 37969 42658 45750 48124 55788
Type - Hermetic Scroll Compressor
Quantity - 1 1 1 2 1 2 2
Compressor
Oil Charge per Circuit US Gal 0.86 0.86 1.23 0.86/0.86 1.80 0.86/0.86 0.86/0.86
(A/B/C/D) Liter 3.3 3.3 4.7 3.3/3.3 6.8 3.3/3.3 3.3/3.3
Type - Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 19.4 19.4 24.4 24.4 24.4 24.4 29.3
Face Area
m² 1.8 1.8 2.3 2.3 2.3 2.3 2.7
Type - Propeller direct drive 960 RPM
Code / Qty. - 628/2 628/2 723/2 723/2 723/2 723/2 823/2
Condenser Fan
cfm 9240 8920 13240 13240 13240 13240 17880
Air Flow Rate
l/s 4361 4210 6249 6249 6249 6249 8438
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 0.37/2 0.37/2 0.75/2 0.75/2 0.75/2 0.75/2 1.5/2
Refrigerant (R - 134a) Operating lbs 9.7 14.8 18.3 9.3/9.3 18.3 11.6/8.9 11.5/11.5
Charge per Circuit (A/B/C/D) (3) kg 4.4 6.7 8.3 4.2/4.2 8.3 5.3/4.1 5.2/5.2
Number of Refrigerant Circuits - 1 1 1 2 1 2 2
lbs 809 889 1142 1169 1142 1213 1319
Unit Operating Weight
kg 367 403 518 530 518 550 598

Model UCUV 52022-S 52025-S 52028-S 52030-S 52036-S 52043-S 52048-S


BTUH 250000 290000 320000 348000 430000 500000 560000
Cooling Capacity (1)
W 73271 84994 93787 101993 126026 146542 164127
BTUH 218100 255600 281750 307000 374000 436900 494250
Cooling Capacity (2)
W 63921 74912 82576 89977 109613 128048 144856
Type - Hermetic Scroll Compressor
Quantity - 2 2 2 2 4 4 4
Compressor
Oil Charge per Circuit US Gal 1.2/0.86 1.2/1.2 1.8/1.2 1.8/1.8 1.7/1.7 2.1/2.1 2.5/2.5
(A/B/C/D) Liter 4.7/3.3 4.7/4.7 6.8/4.7 6.8/6.8 6.5/6.5 7.9/7.9 9.3/9.3
Type - Air cooled 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 31.5 40.0 40.0 40.0 53.3 64.0 72.0
Face Area
m² 2.9 3.7 3.7 3.7 5.0 5.9 6.7
Type - Propeller direct drive 960 RPM
Code / Qty. - 823/2 823/3 823/3 823/3 829/3 823/4 823/4
Condenser Fan
cfm 18180 26160 26160 26160 32040 36480 37280
Air Flow Rate
l/s 8580 12346 12346 12346 15121 17217 17594
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Qty. kW 1.5/2 1.5/3 1.5/3 1.5/3 1.5/3 1.5/4 1.5/4
Refrigerant (R - 134a) Operating lbs 15.6/10.8 15.2/15.2 18.0/14.3 15.6/15.6 21.7/21.7 29.9/29.9 34.1/34.1
Charge per Circuit (A/B/C/D) (3) kg 7.1/4.9 6.9/6.9 8.2/6.5 7.1/7.1 9.8/9.8 13.6/13.6 14.5/14.5
Number of Refrigerant Circuits - 2 2 2 2 2 2 2
lbs 1464 1764 1764 1764 2062 3277 3585
Unit Operating Weight
kg 664 800 800 800 935 1486 1626
Table 1
1). Cooling capacity at 95°F (35°C) ambient temperature according to AHRI-365.
2). Cooling capacity at Gulf conditions : 115°F (46.1°C) condenser entering air temperature & 45°F (7.2°C) SST.
3). Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil.
4). Condensing units are shipped with nitrogen holding charge only.

7
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

ENGINEERING SPECIFICATIONS - 50 HZ
Model UCUV 52053-S 52060-S 53064-S 53071-S 53079-S 53084-S
BTUH 625000 695000 750000 835000 920000 980000
Cooling Capacity (1)
W 183177 203693 219812 244725 269637 287222
BTUH 549900 614050 656350 733900 811650 862000
Cooling Capacity (2)
W 161166 179968 192365 215094 237881 252638
Type - Hermetic Scroll Compressor
Quantity - 4 4 6 6 6 6
Compressor
Oil Charge per Circuit US Gal 3.0/3.0 3.6/3.6 2.1/2.1/2.1 2.5/2.5/2.5 3.0/3.0/2.5 3.6/3.0/3.0
(A/B/C/D) Liter 11.5/11.5 13.6/13.6 7.9/7.9/7.9 9.3/9.3/9.3 11.5/11.5/9.3 13.6/11.5/11.5
Type - Air cooled 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 72.0 72.0 97.5 97.5 97.5 97.5
Face Area
m² 6.7 6.7 9.1 9.1 9.1 9.1
Type - Propeller direct drive 960 RPM
Code / Qty. - 829/4 829/4 823/6 823/6 829/6 829/6
Condenser Fan
cfm 42880 40920 54900 54900 59340 59340
Air Flow Rate
l/s 20237 19312 25910 25910 28005 28005
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 1.5/4 1.5/4 1.5/6 1.5/6 1.5/6 1.5/6
Refrigerant (R - 134a) Operating Charge per lbs 31.9/31.9 35.9/35.9 28.8/28.8/28.8 28.8/28.8/28.8 35.7/35.7/35.7 35.7/35.7/35.7
Circuit (A/B/C/D) (3) kg 14.5/14.5 16.3/16.3 13.1/13.1/13.1 13.1/13.1/13.1 16.2/16.2/16.2 16.2/16.2/16.2
Number of Refrigerant Circuits - 2 2 3 3 3 3
lbs 3585 3815 6139 6533 6727 6727
Unit Operating Weight
kg 1626 1730 2784 2963 3051 3051

Model UCUV 53086-S 54095-S 54106-S 54111-S 54118-S


BTUH 1005000 1125000 1240000 1295000 1380000
Cooling Capacity (1)
W 294549 329719 363423 379543 404455
BTUH 886800 989400 1090650 1141000 1215000
Cooling Capacity (2)
W 259906 289977 319651 334408 356096
Type - Hermetic Scroll Compressor
Quantity - 6 8 8 8 8
Compressor
Oil Charge per Circuit US Gal 3.6/3.6/3.0 2.5/2.5/2.5/2.5 3.0/3.0/3.0/2.5 3.6/3.0/3.0/3.0 3.6/3.6/3.6/3.6
(A/B/C/D) Liter 13.6/13.6/11.5 9.3/9.3/9.3/9.3 11.5/11.5/11.5/9.3 13.6/11.5/11.5/11.5 13.6/13.6/13.6/13.6
Type - Air cooled 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 97.5 130.0 130.0 130.0 130.0
Face Area
m² 9.1 12.1 12.1 12.1 12.1
Type - Propeller direct drive 960 RPM
Code / Qty. - 829/6 829/8 829/8 829/8 829/8
Condenser Fan
cfm 59340 83360 79120 79120 79120
Air Flow Rate
l/s 28005 39342 37340 37340 37340
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Qty. kW 1.5/6 1.5/8 1.5/8 1.5/8 1.5/8
Refrigerant (R - 134a) Operating Charge per lbs 35.7/35.7/35.7 31.3/31.3/31.3 38.8/38.8/38.8/38.8 38.8/38.8/38.8/38.8 38.8/38.8/38.8/38.8
Circuit (A/B/C/D) (3) kg 16.2/16.2/16.2 14.2/14.2/4.2/14.2 17.6/17.6/17.6/17.6 17.6/17.6/17.6/17.6 17.6/17.6/17.6/17.6
Number of Refrigerant Circuits - 3 4 4 4 4
lbs 6727 8293 8551 8551 8551
Unit Operating Weight
kg 3051 3761 3878 3878 3878
Table 1 ends
1). Cooling capacity at 95°F (35°C) ambient temperature according to AHRI-365.
2). Cooling capacity at Gulf conditions : 115°F (46.1°C) condenser entering air temperature & 45°F (7.2°C) SST.
3). Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil.
4). Condensing units are shipped with nitrogen holding charge only.

8 8
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

ENGINEERING SPECIFICATIONS - 60 Hz
Model UCUV 61009-S 61011-S 61016-S 62018-S 61018-S 62020-S 62022-S
BTUH 102000 132000 174000 200000 210000 226000 262000
Cooling Capacity (1)
W 29894 38687 50996 58617 61547 66237 76788
BTUH 88500 117250 154950 173400 185550 196550 229150
Cooling Capacity (2)
W 25938 34364 45413 50821 54382 57606 67160
Type - Hermetic Scroll Compressor
Quantity - 1 1 1 2 1 2 2
Compressor
Oil Charge per Circuit US Gal 0.86 0.86 1.23 0.86/0.86 1.80 0.86/0.86 0.86/0.86
(A/B/C/D) 3.3 6.8 3.3/3.3 3.3/3.3
Liter 3.3 4.7 3.3/3.3
Type - Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 19.4 19.4 24.4 24.4 24.4 24.4 29.3
Face Area
m² 1.8 1.8 2.3 2.3 2.3 2.3 2.7
Type - Propeller direct drive 1150 RPM
Code / Qty. - 628/2 628/2 723/2 723/2 723/2 723/2 823/2
Condenser Fan
cfm 11200 10820 15660 15660 15660 15660 21760
Air Flow Rate
l/s 5286 5106 7391 7391 7391 7391 10270
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 0.55/2 0.55/2 1.1/2 1.1/2 1.1/2 1.1/2 2.2/2
Refrigerant (R - 134a) Operating lbs 9.7 14.8 18.3 9.3/9.3 18.3 11.6/8.9 11.5/11.5
Charge per Circuit (A/B/C/D) (3) kg 4.4 6.7 8.3 4.2/4.2 8.3 5.3/4.0 5.2/5.2
Number of Refrigerant Circuits - 1 1 1 2 1 2 2
lbs 816 895 1142 1169 1142 1213 1319
Unit Operating Weight
kg 370 406 518 530 518 550 598

Model UCUV 62026-S 62030-S 62033-S 62036-S 62043-S 62051-S 62058-S


BTUH 296000 344000 380000 410000 515000 595000 665000
Cooling Capacity (1)
W 86753 100821 111372 120164 150938 174385 194900
BTUH 261500 305550 335650 364650 450050 523900 590900
Cooling Capacity (2)
W 76641 89552 98373 106873 131902 153546 173183
Type - Hermetic Scroll Compressor
Quantity - 2 2 2 2 4 4 4
Compressor
Oil Charge per Circuit US Gal 1.2/0.86 1.2/1.2 1.8/1.2 1.8/1.8 1.7/1.7 2.1/2.1 2.5/2.5
(A/B/C/D) Liter 4.7/3.3 4.7/4.7 6.8/4.7 6.8/6.8 6.5/6.5 7.9/7.9 9.3/9.3
Type - Air cooled 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 31.5 40.0 40.0 40.0 53.3 64.0 72.0
Face Area
m² 2.9 3.7 3.7 3.7 5.0 5.9 6.7
Type - Propeller direct drive 1150 RPM
Code / Qty. - 823/2 823/3 823/3 823/3 829/3 823/4 823/4
Condenser Fan
cfm 22120 31860 31860 31860 38700 44400 45400
Air Flow Rate
l/s 10439 15036 15036 15036 18264 20954 21426
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Qty. kW 2.2/2 2.2/3 2.2/3 2.2/3 2.2/3 2.2/4 2.2/4
Refrigerant (R - 134a) Operating lbs 15.6/10.8 15.2/15.2 18.0/14.3 15.6/15.6 21.7/21.7 29.9/29.9 34.1/34.1
Charge per Circuit (A/B/C/D) (3) kg 7.1/4.9 6.9/6.9 8.2/6.5 7.1/7.1 9.8/9.8 13.6/13.6 14.5/14.5
Number of Refrigerant Circuits - 2 2 2 2 2 2 2
lbs 1464 1764 1764 1764 2090 3277 3585
Unit Operating Weight
kg 664 800 800 800 948 1486 1626
Table 2
1). Cooling capacity at 95°F (35°C) ambient temperature according to AHRI-365.
2). Cooling capacity at Gulf conditions : 115°F (46.1°C) condenser entering air temperature & 45°F (7.2°C) SST.
3). Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil.
4). Condensing units are shipped with nitrogen holding charge only.

9
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

ENGINEERING SPECIFICATIONS - 60 HZ
Model UCUV 62063-S 62071-S 63076-S 63085-S 63094-S 63100-S
BTUH 740000 825000 895000 990000 1095000 1165000
Cooling Capacity (1)
W 216882 241794 262309 290152 320926 341442
BTUH 654050 731700 787200 876100 969850 1027950
Cooling Capacity (2)
W 191691 214449 230715 256770 284247 301275
Type - Hermetic Scroll Compressor
Quantity - 4 4 6 6 6 6
Compressor
Oil Charge per Circuit US Gal 3.0/3.0 3.6/3.6 2.1/2.1/2.1 2.5/2.5/2.5 3.0/3.0/2.5 3.6/3.0/3.0
(A/B/C/D) Liter 11.5/11.5 13.6/13.6 7.9/7.9/7.9 9.3/9.3/9.3 11.5/11.5/9.3 13.6/11.5/11.5
Type - Air cooled 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 72.0 72.0 97.5 97.5 97.5 97.5
Face Area
m² 6.7 6.7 9.1 9.1 9.1 9.1
Type - Propeller direct drive 1150 RPM
Code / Qty. - 829/4 829/4 823/6 823/6 829/6 829/6
Condenser Fan
cfm 51760 49560 66840 66840 72000 72000
Air Flow Rate
l/s 24428 23390 31545 31545 33980 33980
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 2.2/4 2.2/4 2.2/6 2.2/6 2.2/6 2.2/6
Refrigerant (R - 134a) Operating Charge per lbs 31.9/31.9 35.9/35.9 28.8/28.8/28.8 28.8/28.8/28.8 35.7/35.7/35.7 35.7/35.7/35.7
Circuit (A/B/C/D) (3) kg 14.5/14.5 16.3/16.3 13.1/13.1/13.1 13.1/13.1/13.1 16.2/16.2/16.2 16.2/16.2/16.2
Number of Refrigerant Circuits - 2 2 3 3 3 3
lbs 3625 3850 6139 6536 6787 6787
Unit Operating Weight
kg 1644 1746 2784 2964 3078 3078

Model UCUV 63102-S 64113-S 64126-S 64132-S 64140-S


BTUH 1195000 1335000 1475000 1540000 1640000
Cooling Capacity 1)
W 350234 391266 432298 451348 480657
BTUH 1056450 1179850 1303000 1361050 1446000
Cooling Capacity 2)
W 309628 345794 381887 398901 423798
Type - Hermetic Scroll Compressor
Quantity - 6 8 8 8 8
Compressor
Oil Charge per Circuit US Gal 3.6/3.6/3.0 2.5/2.5/2.5/2.5 3.0/3.0/3.0/2.5 3.6/3.0/3.0/3.0 3.6/3.6/3.6/3.6
(A/B/C/D) Liter 13.6/13.6/11.5 9.3/9.3/9.3/9.3 11.5/11.5/11.5/9.3 13.6/11.5/11.5/11.5 13.6/13.6/13.6/13.6
Type - Air cooled 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 97.5 130.0 130.0 130.0 130.0
Face Area
m² 9.1 12.1 12.1 12.1 12.1
Type - Propeller direct drive 1150 RPM
Code / Qty. - 829/6 829/8 829/8 829/8 829/8
Condenser Fan
cfm 72000 100880 96000 96000 96000
Air Flow Rate
l/s 33980 47610 45307 45307 45307
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Qty. kW 2.2/6 2.2/8 2.2/8 2.2/8 2.2/8
Refrigerant (R - 134a) Operating Charge per lbs 35.7/35.7/35.7 31.3/31.3/31.3 38.8/38.8/38.8/38.8 38.8/38.8/38.8/38.8 38.8/38.8/38.8/38.8
Circuit (A/B/C/D) (3) kg 16.2/16.2/16.2 14.2/14.2/4.2/14.2 17.6/17.6/17.6/17.6 17.6/17.6/17.6/17.6 17.6/17.6/17.6/17.6
Number of Refrigerant Circuits - 3 4 4 4 4
lbs 6787 8370 8630 8630 8630
Unit Operating Weight
kg 3078 3796 3914 3914 3914
Table 2 ends
1). Cooling capacity at 95°F (35°C) ambient temperature according to AHRI-365.
2). Cooling capacity at Gulf conditions : 115°F (46.1°C) condenser entering air temperature & 45°F (7.2°C) SST.
3). Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil.
4). Condensing units are shipped with nitrogen holding charge only.

10
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

CAPACITY RATINGS - 50 H Z
Condenser Entering Air Temperature
Model SST 95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)
UCUV Total Capacity PI* Total Capacity PI* Total Capacity PI* Total Capacity PI*
°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW
35 1.7 72.4 21.2 5.5 67.4 19.8 6.3 62.0 18.2 7.0 56.5 16.6 7.8
40 4.4 79.0 23.2 5.6 73.7 21.6 6.3 67.9 19.9 7.1 62.1 18.2 7.9
51008-S
45 7.2 85.9 25.2 5.7 80.2 23.5 6.4 74.0 21.7 7.2 68.0 19.9 7.9
50 10 93.1 27.3 5.8 86.9 25.5 6.5 80.4 23.6 7.2 74.1 21.7 7.8
35 1.7 93.1 27.3 7.4 86.7 25.4 8.3 79.5 23.3 9.3 72.3 21.2 10.3
40 4.4 102.1 29.9 7.5 95.4 28.0 8.5 87.9 25.8 9.5 80.6 23.6 10.4
51010-S
45 7.2 111.6 32.7 7.7 104.5 30.6 8.6 96.8 28.4 9.6 89.4 26.2 10.6
50 10 121.6 35.6 7.8 114.1 33.4 8.8 106.3 31.1 9.8 98.7 28.9 10.8
35 1.7 119.6 35.1 9.6 112.4 32.9 10.8 105.0 30.8 12.2 97.5 28.6 13.6
40 4.4 132.6 38.9 9.8 124.7 36.5 11.0 116.6 34.2 12.4 108.6 31.8 13.8
51013-S
45 7.2 146.5 42.9 10.1 137.9 40.4 11.4 129.1 37.8 12.7 120.4 35.3 14.1
50 10 161.4 47.3 10.4 152.0 44.6 11.7 142.5 41.8 13.1 133.1 39.0 14.4
35 1.7 142.8 41.9 11.3 132.7 38.9 12.8 121.8 35.7 14.4 111.0 32.5 15.9
40 4.4 155.8 45.7 11.5 144.9 42.5 13.0 133.3 39.1 14.5 122.1 35.8 16.0
52015-S
45 7.2 169.2 49.6 11.7 157.5 46.2 13.2 145.3 42.6 14.6 133.6 39.1 16.1
50 10 183.2 53.7 11.9 170.7 50.0 13.3 157.8 46.3 14.7 145.6 42.7 16.0
35 1.7 144.6 42.4 12.6 135.8 39.8 14.2 126.9 37.2 15.9 118.0 34.6 17.6
40 4.4 160.1 46.9 12.9 150.5 44.1 14.5 140.7 41.2 16.3 131.1 38.4 18.0
51016-S
45 7.2 176.7 51.8 13.3 166.1 48.7 14.9 155.4 45.6 16.7 144.9 42.5 18.3
50 10 194.2 56.9 13.7 182.9 53.6 15.4 171.5 50.3 17.1 160.3 47.0 18.7
35 1.7 160.3 47.0 13.7 148.4 43.5 15.4 135.7 39.8 17.1 123.7 36.2 18.8
40 4.4 175.2 51.3 14.0 162.6 47.6 15.7 149.5 43.8 17.4 137.2 40.2 19.1
52017-S
45 7.2 190.6 55.9 14.3 177.3 52.0 16.0 163.8 48.0 17.7 151.3 44.3 19.3
50 10 206.8 60.6 14.5 192.8 56.5 16.2 178.9 52.4 17.9 166.1 48.7 19.4
35 1.7 183.4 53.8 15.1 170.2 49.9 17.0 155.8 45.7 19.0 141.7 41.5 21.0
40 4.4 201.1 58.9 15.5 187.3 54.9 17.4 172.4 50.5 19.4 158.1 46.3 21.3
52019-S
45 7.2 219.6 64.4 15.8 205.0 60.1 17.8 189.8 55.6 19.7 175.5 51.4 21.6
50 10 239.0 70.0 16.2 223.8 65.6 18.1 208.3 61.1 20.2 193.7 56.8 22.0
35 1.7 206.5 60.5 17.9 192.5 56.4 20.1 177.9 52.1 22.6 163.7 48.0 24.8
40 4.4 227.4 66.7 18.4 212.5 62.3 20.7 197.1 57.8 23.1 182.3 53.4 25.3
52022-S
45 7.2 249.6 73.1 19.0 233.6 68.5 21.3 217.5 63.7 23.6 202.1 59.2 25.8
50 10 273.0 80.0 19.6 256.1 75.1 21.9 239.1 70.1 24.2 223.0 65.4 26.3
35 1.7 236.7 69.4 19.6 222.2 65.1 22.0 207.4 60.8 24.8 192.5 56.4 27.6
40 4.4 262.1 76.8 20.1 246.3 72.2 22.6 230.3 67.5 25.4 214.3 62.8 28.1
52025-S
45 7.2 289.4 84.8 20.7 272.2 79.8 23.3 254.7 74.7 26.1 237.5 69.6 28.7
50 10 318.6 93.4 21.4 299.8 87.9 24.0 280.9 82.3 26.8 262.3 76.9 29.3
35 1.7 261.3 76.6 22.6 245.3 71.9 25.5 229.0 67.1 28.6 212.7 62.4 31.7
40 4.4 289.3 84.8 23.2 271.7 79.6 26.2 254.0 74.4 29.3 236.4 69.3 32.3
52028-S
45 7.2 319.1 93.5 23.9 300.0 87.9 26.9 280.6 82.2 30.1 261.6 76.7 33.0
50 10 350.9 102.8 24.8 330.2 96.8 27.8 309.5 90.7 30.9 289.1 84.7 33.6
35 1.7 285.3 83.6 25.8 267.7 78.5 29.1 250.0 73.3 32.6 232.4 68.1 35.9
40 4.4 315.7 92.5 26.5 296.4 86.9 29.9 277.0 81.2 33.4 257.9 75.6 36.6
52030-S
45 7.2 348.0 102.0 27.3 326.8 95.8 30.8 305.6 89.6 34.2 284.9 83.5 37.3
50 10 382.1 112.0 28.3 359.6 105.4 31.7 337.0 98.8 35.1 314.9 92.3 38.0
35 1.7 361.8 106.1 31.0 334.9 98.1 34.8 306.1 89.7 38.8 278.6 81.6 42.7
40 4.4 396.5 116.2 31.9 368.2 107.9 35.7 338.7 99.3 39.6 311.0 91.2 43.3
52036-S
45 7.2 432.5 126.8 32.6 403.1 118.1 36.4 373.1 109.3 40.4 345.3 101.2 44.0
50 10 470.4 137.9 33.3 439.9 128.9 37.3 409.3 120.0 41.2 381.2 111.7 44.7
35 1.7 413.6 121.2 35.8 385.5 113.0 40.2 356.3 104.4 45.0 327.9 96.1 49.6
40 4.4 455.5 133.5 36.8 425.5 124.7 41.3 394.8 115.7 46.0 365.2 107.0 50.5
52043-S
45 7.2 499.8 146.5 37.8 467.9 137.1 42.4 435.6 127.7 47.1 404.7 118.6 51.4
50 10 546.8 160.3 39.0 512.9 150.3 43.7 479.0 140.4 48.3 446.7 130.9 52.5
Table 3

Notes :
* Power input mentioned in this page should not be used for cable or fuse selection. MC and MFA values given in the electrical data
pages (18 - 20) should be referred for the same.
Computer Print outs for matched ratings with UNTES Air Handling Units are
available.
11
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

CAPACITY RATINGS - 50 H Z
Condenser Entering Air Temperature
Model SST 95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)
UCUV Total Capacity PI* Total Capacity PI* Total Capacity PI* Total Capacity PI*
°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW
35 1.7 461.1 135.1 41.2 432.0 126.6 46.4 402.5 118.0 52.0 373.4 109.4 57.1
40 4.4 509.5 149.3 42.4 478.0 140.1 47.7 446.2 130.8 53.3 414.9 121.6 58.2
52048-S
45 7.2 561.3 164.5 44.0 527.0 154.5 49.3 492.7 144.4 54.7 459.0 134.5 59.5
50 10 616.5 180.7 45.6 579.3 169.8 51.0 542.3 158.9 56.3 506.2 148.4 60.9
35 1.7 512.8 150.3 46.9 480.6 140.9 52.9 448.1 131.3 59.2 416.1 122.0 65.0
40 4.4 566.7 166.1 48.3 531.7 155.8 54.4 496.5 145.5 60.7 462.0 135.4 66.2
52053-S
45 7.2 624.2 183.0 50.0 586.0 171.7 56.1 547.7 160.5 62.3 510.5 149.6 67.6
50 10 685.2 200.8 51.9 644.1 188.8 58.0 603.3 176.8 63.9 563.4 165.1 69.0
35 1.7 570.7 167.3 51.6 535.5 157.0 58.2 499.9 146.5 65.2 464.8 136.2 71.8
40 4.4 631.3 185.0 53.0 592.8 173.8 59.8 554.0 162.4 66.8 515.8 151.2 73.2
52060-S
45 7.2 695.9 204.0 54.7 653.6 191.6 61.5 611.2 179.2 68.5 569.9 167.0 74.6
50 10 764.2 224.0 56.6 719.1 210.8 63.5 674.1 197.6 70.2 629.8 184.6 76.0
35 1.7 621.1 182.1 53.5 579.1 169.7 60.2 535.2 156.9 67.4 492.5 144.3 74.3
40 4.4 684.1 200.5 55.0 639.2 187.4 61.8 593.1 173.8 68.9 548.6 160.8 75.6
53064-S
45 7.2 750.7 220.0 56.6 702.9 206.0 63.5 654.4 191.8 70.6 608.0 178.2 77.1
50 10 821.4 240.8 58.3 770.6 225.9 65.3 719.6 210.9 72.3 671.1 196.7 78.6
35 1.7 686.1 201.1 62.7 642.4 188.3 70.6 598.3 175.4 79.0 554.9 162.6 86.5
40 4.4 757.7 222.1 64.7 710.4 208.2 72.7 663.0 194.3 80.9 616.4 180.7 88.2
53071-S
45 7.2 834.2 244.5 67.1 782.9 229.5 75.2 731.7 214.4 83.2 681.6 199.8 90.2
50 10 915.6 268.3 69.8 860.0 252.1 77.8 804.8 235.9 85.6 751.4 220.2 92.3
35 1.7 754.0 221.0 65.7 707.3 207.3 74.0 659.9 193.4 83.1 612.9 179.6 91.8
40 4.4 834.2 244.5 67.5 783.4 229.6 76.0 732.0 214.5 85.1 681.2 199.7 93.6
53079-S
45 7.2 920.1 269.7 69.7 864.5 253.4 78.4 808.6 237.0 87.4 753.7 220.9 95.6
50 10 1011.3 296.4 72.1 951.3 278.8 80.9 891.3 261.2 89.7 832.4 244.0 97.6
35 1.7 801.8 235.0 72.0 752.1 220.4 81.2 701.8 205.7 91.1 652.0 191.1 100.3
40 4.4 886.8 259.9 74.1 832.5 244.0 83.5 777.8 228.0 93.3 724.0 212.2 102.2
53084-S
45 7.2 977.5 286.5 76.5 918.0 269.1 86.1 858.4 251.6 95.7 800.2 234.5 104.3
50 10 1073.5 314.6 79.3 1009.8 296.0 88.8 946.2 277.3 98.2 883.8 259.1 106.4
35 1.7 825.4 241.9 75.3 774.1 226.9 84.9 722.4 211.7 95.1 671.3 196.8 104.6
40 4.4 912.7 267.5 77.5 856.7 251.1 87.3 800.4 234.6 97.5 745.0 218.4 106.6
53086-S
45 7.2 1005.7 294.8 80.1 944.3 276.8 90.0 882.9 258.8 100.0 823.0 241.2 108.7
50 10 1104.1 323.6 82.9 1038.5 304.4 92.9 973.2 285.2 102.5 909.1 266.5 110.8
35 1.7 922.9 270.5 82.2 864.6 253.4 92.6 805.6 236.1 103.8 747.4 219.1 114.2
40 4.4 1019.8 298.9 84.7 956.7 280.4 95.3 893.2 261.8 106.4 830.6 243.4 116.4
54095-S
45 7.2 1123.6 329.3 87.8 1055.0 309.2 98.5 986.3 289.1 109.3 918.9 269.3 119.0
50 10 1234.1 361.7 91.1 1159.7 339.9 101.8 1085.6 318.2 112.4 1013.5 297.1 121.7
35 1.7 1013.4 297.0 88.6 950.6 278.6 99.9 886.9 260.0 112.2 823.8 241.5 123.8
40 4.4 1121.2 328.6 91.1 1052.8 308.6 102.6 983.7 288.3 114.9 915.5 268.3 126.2
54106-S
45 7.2 1236.4 362.4 94.0 1161.7 340.5 105.8 1086.6 318.5 117.9 1012.7 296.8 128.9
50 10 1358.8 398.3 97.4 1278.3 374.7 109.1 1197.6 351.0 121.0 1118.5 327.8 131.6
35 1.7 1061.2 311.0 95.0 995.4 291.7 107.1 928.8 272.2 120.1 862.9 252.9 132.3
40 4.4 1173.8 344.0 97.7 1101.9 323.0 110.1 1029.5 301.8 123.0 958.3 280.9 134.9
54111-S
45 7.2 1293.8 379.2 100.9 1215.2 356.2 113.5 1136.4 333.1 126.2 1059.2 310.5 137.6
50 10 1421.1 416.5 104.5 1336.7 391.8 117.1 1252.5 367.1 129.5 1170.0 342.9 140.3
35 1.7 1131.7 331.7 104.8 1061.3 311.1 118.3 990.4 290.3 132.3 920.5 269.8 145.2
40 4.4 1251.2 366.7 108.0 1174.2 344.1 121.6 1096.9 321.5 135.6 1021.2 299.3 148.0
54118-S
45 7.2 1378.1 403.9 111.6 1293.7 379.2 125.3 1209.4 354.5 139.0 1127.6 330.5 150.9
50 10 1512.4 443.3 115.6 1422.5 416.9 129.3 1333.1 390.7 142.5 1245.3 365.0 153.6
Table 3 ends
Notes :
* Power input mentioned in this page should not be used for cable or fuse selection. MC and MFA values given in the electrical data
pages (18 - 20) should be referred for the same.
Computer Print outs for matched ratings with UNTES Air Handling Units are
available.

12
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

CAPACITY RATINGS - 60 H Z
Condenser Entering Air Temperature
Model SST 95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)
UCUV Total Capacity PI* Total Capacity PI* Total Capacity PI* Total Capacity PI*
°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW
35 1.7 86.2 25.3 6.9 79.6 23.3 7.7 72.8 21.3 8.6 66.0 19.3 9.5
40 4.4 94.4 27.7 7.0 87.7 25.7 7.9 80.6 23.6 8.8 73.7 21.6 9.7
61009-S
45 7.2 102.3 30.0 7.2 95.6 28.0 8.1 88.5 25.9 9.0 81.8 24.0 9.9
50 10 109.7 32.2 7.4 103.2 30.3 8.3 96.4 28.3 9.2 90.0 26.4 10.0
35 1.7 111.7 32.7 9.3 104.5 30.6 10.4 96.6 28.3 11.5 88.8 26.0 12.7
40 4.4 122.4 35.9 9.5 114.7 33.6 10.6 106.5 31.2 11.8 98.6 28.9 12.9
61011-S
45 7.2 133.7 39.2 9.8 125.6 36.8 10.9 117.0 34.3 12.0 108.8 31.9 13.1
50 10 145.5 42.6 10.1 136.9 40.1 11.2 128.0 37.5 12.3 119.6 35.1 13.4
35 1.7 142.8 41.9 12.2 134.4 39.4 13.6 125.9 36.9 15.2 117.4 34.4 16.8
40 4.4 158.1 46.3 12.5 148.9 43.6 14.0 139.6 40.9 15.6 130.4 38.2 17.2
61016-S
45 7.2 174.5 51.1 12.9 164.5 48.2 14.4 154.4 45.3 16.0 144.4 42.3 17.5
50 10 192.0 56.3 13.3 181.2 53.1 14.8 170.3 49.9 16.4 159.5 46.8 17.9
35 1.7 169.2 49.6 14.1 156.0 45.7 15.8 142.5 41.8 17.6 129.1 37.8 19.3
40 4.4 185.3 54.3 14.5 171.7 50.3 16.3 157.7 46.2 18.1 144.3 42.3 19.8
62018-S
45 7.2 201.0 58.9 14.9 187.3 54.9 16.7 173.3 50.8 18.5 160.3 47.0 20.2
50 10 215.7 63.2 15.3 202.4 59.3 17.1 189.1 55.4 18.9 176.9 51.8 20.5
35 1.7 171.9 50.4 15.9 161.7 47.4 17.8 151.5 44.4 19.8 141.3 41.4 21.7
40 4.4 190.2 55.7 16.3 178.9 52.4 18.3 167.7 49.1 20.3 156.5 45.9 22.2
61018-S
45 7.2 209.6 61.4 16.9 197.2 57.8 18.9 184.7 54.1 20.9 172.6 50.6 22.6
50 10 230.2 67.5 17.5 216.8 63.5 19.5 203.4 59.6 21.4 190.4 55.8 23.1
35 1.7 190.4 55.8 17.2 176.2 51.6 19.2 161.7 47.4 21.2 147.9 43.3 23.1
40 4.4 208.3 61.0 17.7 193.5 56.7 19.7 178.6 52.4 21.7 164.8 48.3 23.6
62020-S
45 7.2 226.5 66.4 18.2 211.3 61.9 20.3 196.3 57.5 22.3 182.7 53.5 24.0
50 10 244.8 71.8 18.8 229.5 67.3 20.8 214.5 62.9 22.8 201.5 59.0 24.4
35 1.7 219.5 64.3 19.1 204.6 60.0 21.4 188.9 55.4 23.7 173.8 50.9 26.0
40 4.4 240.3 70.4 19.7 224.6 65.8 21.9 208.3 61.1 24.2 193.0 56.6 26.4
62022-S
45 7.2 262.1 76.8 20.3 245.6 72.0 22.5 228.7 67.0 24.8 213.1 62.5 26.8
50 10 284.9 83.5 20.9 267.5 78.4 23.1 250.0 73.3 25.4 234.2 68.6 27.3
35 1.7 246.5 72.3 22.7 230.6 67.6 25.4 214.3 62.8 28.2 198.6 58.2 30.8
40 4.4 271.1 79.5 23.5 254.1 74.5 26.1 236.9 69.4 28.8 220.4 64.6 31.3
62026-S
45 7.2 297.2 87.1 24.2 279.0 81.8 26.9 260.8 76.4 29.6 243.6 71.4 31.9
50 10 324.7 95.2 25.0 305.3 89.5 27.7 286.1 83.9 30.4 268.3 78.6 32.6
35 1.7 282.4 82.8 24.9 265.6 77.8 27.9 248.6 72.9 31.1 231.7 67.9 34.2
40 4.4 312.4 91.6 25.6 294.1 86.2 28.6 275.6 80.8 31.8 257.2 75.4 34.9
62030-S
45 7.2 344.5 101.0 26.4 324.6 95.1 29.5 304.5 89.3 32.7 284.7 83.5 35.6
50 10 378.7 111.0 27.2 357.1 104.7 30.4 335.5 98.3 33.5 314.2 92.1 36.4
35 1.7 311.1 91.2 28.7 292.5 85.7 32.1 273.8 80.3 35.7 255.3 74.8 39.1
40 4.4 344.0 100.8 29.5 323.7 94.9 33.0 303.2 88.9 36.6 283.0 82.9 39.9
62033-S
45 7.2 379.1 111.1 30.5 356.8 104.6 34.0 334.4 98.0 37.6 312.5 91.6 40.8
50 10 416.3 122.0 31.6 392.1 114.9 35.1 368.1 107.9 38.6 344.7 101.0 41.7
35 1.7 339.1 99.4 32.6 318.7 93.4 36.5 298.3 87.4 40.5 278.1 81.5 44.2
40 4.4 374.7 109.8 33.6 352.3 103.2 37.6 329.9 96.7 41.6 307.9 90.2 45.1
62036-S
45 7.2 412.4 120.9 34.8 387.7 113.6 38.8 363.0 106.4 42.7 339.3 99.4 46.1
50 10 452.3 132.6 36.2 425.7 124.8 40.1 399.4 117.1 43.9 374.0 109.6 47.0
35 1.7 432.4 126.7 39.3 402.1 117.9 43.8 370.9 108.7 48.5 341.7 100.1 52.8
40 4.4 472.9 138.6 40.5 441.2 129.3 44.9 409.1 119.9 49.5 379.5 111.2 53.7
62043-S
45 7.2 515.6 151.1 41.7 482.3 141.4 46.2 449.2 131.7 50.6 419.3 122.9 54.6
50 10 559.9 164.1 43.0 525.0 153.9 47.5 491.0 143.9 51.9 461.0 135.1 55.5
35 1.7 493.8 144.7 45.4 461.9 135.4 50.7 429.3 125.8 56.2 397.9 116.6 61.4
40 4.4 543.1 159.2 46.8 509.0 149.2 52.1 474.6 139.1 57.6 441.6 129.4 62.6
62051-S
45 7.2 595.4 174.5 48.3 558.9 163.8 53.7 522.5 153.1 59.0 488.0 143.0 63.8
50 10 650.5 190.7 49.9 611.6 179.3 55.3 573.2 168.0 60.6 537.4 157.5 65.0
Notes : Table 4

* Power input mentioned in this page should not be used for cable or fuse selection. MC and MFA values given in the electrical data
pages ( 18-20 ) should be referred for the same.
Computer Print outs for matched ratings with UNTES Air Handling Units are
available.

13
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

CAPACITY RATINGS - 60 Hz
Condenser Entering Air Temperature
Model SST 95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)
UCUV Total Capacity PI* Total Capacity PI* Total Capacity PI* Total Capacity PI*
°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW
35 1.7 549.9 161.2 52.3 516.3 151.3 58.5 482.7 141.5 64.9 449.4 131.7 70.8
40 4.4 607.1 177.9 54.1 570.6 167.2 60.3 534.1 156.5 66.6 498.1 146.0 72.2
62058-S
45 7.2 668.1 195.8 55.9 628.5 184.2 62.2 589.1 172.7 68.4 550.6 161.4 73.8
50 10 732.8 214.8 58.0 690.1 202.3 64.3 647.7 189.8 70.3 606.7 177.8 75.3
35 1.7 609.5 178.6 59.6 572.4 167.8 66.6 535.3 156.9 73.8 498.6 146.1 80.2
40 4.4 672.8 197.2 61.6 632.3 185.3 68.7 591.8 173.4 75.8 552.1 161.8 81.9
62063-S
45 7.2 740.1 216.9 63.8 695.6 203.9 71.0 651.6 191.0 77.8 609.0 178.5 83.6
50 10 811.2 237.8 66.3 763.4 223.8 73.4 716.3 209.9 80.0 670.9 196.6 85.4
35 1.7 680.0 199.3 64.9 639.3 187.4 72.6 598.4 175.4 80.7 557.9 163.5 88.0
40 4.4 751.5 220.3 66.9 706.7 207.1 74.8 661.8 194.0 82.8 617.7 181.1 89.9
62071-S
45 7.2 827.4 242.5 69.2 777.9 228.0 77.2 728.5 213.5 85.1 680.9 199.6 91.8
50 10 907.7 266.0 71.9 854.4 250.4 79.8 801.6 234.9 87.4 750.6 220.0 93.8
35 1.7 741.7 217.4 67.9 693.9 203.4 75.8 645.1 189.1 84.2 597.8 175.2 92.0
40 4.4 815.9 239.1 70.0 764.7 224.1 78.0 713.0 209.0 86.2 663.4 194.4 93.7
63076-S
45 7.2 894.6 262.2 72.2 839.9 246.2 80.3 785.1 230.1 88.3 733.3 214.9 95.5
50 10 977.5 286.5 74.6 919.1 269.4 82.7 861.4 252.5 90.7 807.5 236.7 97.4
35 1.7 817.1 239.5 79.9 766.8 224.8 89.2 716.5 210.0 98.7 666.9 195.5 107.3
40 4.4 901.4 264.2 82.6 846.9 248.2 92.0 792.4 232.3 101.3 738.9 216.6 109.5
63085-S
45 7.2 991.3 290.6 85.6 932.2 273.2 95.1 873.5 256.0 104.2 816.3 239.3 111.9
50 10 1086.6 318.5 88.8 1022.8 299.8 98.3 959.8 281.3 107.1 899.2 263.6 114.1
35 1.7 899.6 263.7 83.1 845.6 247.9 93.0 791.3 231.9 103.4 737.4 216.1 113.3
40 4.4 994.4 291.5 85.6 935.4 274.2 95.7 876.1 256.8 106.1 817.6 239.6 115.6
63094-S
45 7.2 1095.6 321.1 88.4 1031.0 302.2 98.7 966.4 283.3 109.0 903.2 264.7 118.1
50 10 1202.8 352.6 91.6 1133.1 332.1 101.9 1063.6 311.7 112.0 996.1 291.9 120.6
35 1.7 955.5 280.1 91.0 898.0 263.2 101.8 840.4 246.3 113.0 783.2 229.5 123.3
40 4.4 1055.7 309.4 93.8 992.7 291.0 104.9 929.5 272.4 116.0 867.5 254.3 126.0
63100-S
45 7.2 1162.3 340.7 97.1 1093.0 320.4 108.2 1023.9 300.1 119.2 956.9 280.5 128.6
50 10 1275.1 373.7 100.8 1200.4 351.8 111.8 1126.4 330.1 122.4 1054.8 309.2 131.4
35 1.7 983.1 288.1 95.0 923.8 270.8 106.3 864.5 253.4 117.9 805.6 236.1 128.4
40 4.4 1085.9 318.3 98.1 1020.8 299.2 109.5 955.8 280.1 121.0 892.0 261.4 131.2
63102-S
45 7.2 1195.1 350.3 101.5 1123.3 329.2 113.1 1052.0 308.3 124.3 983.3 288.2 133.9
50 10 1310.5 384.1 105.5 1233.3 361.5 116.9 1157.1 339.1 127.8 1083.6 317.6 136.8
35 1.7 1098.3 321.9 104.9 1031.2 302.3 117.3 963.9 282.5 130.1 897.4 263.0 141.8
40 4.4 1212.4 355.4 108.4 1139.5 334.0 120.9 1066.5 312.6 133.5 994.7 291.5 144.7
64113-S
45 7.2 1334.1 391.0 112.2 1255.1 367.9 124.8 1176.3 344.8 137.2 1099.3 322.2 147.8
50 10 1463.3 428.9 116.3 1377.8 403.8 129.0 1293.2 379.0 141.0 1211.4 355.0 150.8
35 1.7 1208.9 354.3 112.0 1136.3 333.1 125.4 1063.4 311.7 139.5 990.9 290.4 152.7
40 4.4 1336.2 391.6 115.5 1256.9 368.4 129.1 1177.2 345.0 143.1 1098.5 322.0 155.9
64126-S
45 7.2 1472.0 431.4 119.3 1385.2 406.0 133.1 1298.3 380.5 147.0 1213.4 355.6 159.2
50 10 1616.0 473.6 123.6 1522.2 446.1 137.5 1428.8 418.8 151.0 1338.0 392.2 162.6
35 1.7 1264.8 370.7 119.9 1188.7 348.4 134.2 1112.4 326.0 149.1 1036.7 303.8 162.8
40 4.4 1397.5 409.6 123.7 1314.1 385.2 138.3 1230.6 360.7 153.0 1148.4 336.6 166.2
64132-S
45 7.2 1538.8 451.0 128.0 1447.1 424.1 142.7 1355.7 397.4 157.2 1267.0 371.4 169.7
50 10 1688.3 494.8 132.8 1589.5 465.9 147.4 1491.5 437.2 161.5 1396.7 409.4 173.3
35 1.7 1347.1 394.8 132.1 1265.9 371.0 147.8 1184.5 347.2 163.7 1103.8 323.5 178.0
40 4.4 1487.6 436.0 136.5 1398.2 409.8 152.4 1308.9 383.6 168.2 1221.6 358.1 181.9
64140-S
45 7.2 1636.4 479.6 141.4 1537.6 450.7 157.4 1439.7 422.0 172.7 1345.8 394.4 185.6
50 10 1793.8 525.8 147.1 1687.7 494.7 162.8 1583.1 464.0 177.5 1482.7 434.6 189.6
Table 4 ends
Notes :
* Power input mentioned in this page should not be used for cable or fuse selection. MC and MFA values given in the electrical data
pages ( 18-20) should be referred for the same.
Computer Print outs for matched ratings with UNTES Air Handling Units are
available.
1). Cooling capacity at 95°F (35°C) ambient temperature according to AHRI-365.
2). Cooling capacity at Gulf conditions : 115°F (46.1°C) condenser entering air temperature & 45°F (7.2°C) SST.
3). Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil.
4). Condensing units are shipped with nitrogen holding charge only.

14
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Capacity Control Steps


The Standard Capacity Control Steps are shown below.

UCUV Standard Number of Steps


51008-S 61009-S 100-0 1
51010-S 61011-S 100-0 1
51013-S 61016-S 100-0 1
52015-S 62018-S 100-50-0 2
51016-S 61018-S 100-0 1
52017-S 62020-S 100-56-0 2
52019-S 62022-S 100-50-0 2
52022-S 62026-S 100-58-0 2
52025-S 62030-S 100-50-0 2
52028-S 62033-S 100-54-0 2
52030-S 62036-S 100-50-0 2
52036-S 62043-S 100-75-50-25-0 4
52043-S 62051-S 100-81-50-31-0 4
52048-S 62058-S 100-75-50-25-0 4
52053-S 62063-S 100-77-50-27-0 4
52060-S 62071-S 100-75-50-25-0 4
53064-S 63076-S 100-86-67-53-33-19-0 6
53071-S 63085-S 100-83-67-50-33-17-0 6
53079-S 63094-S 100-85-69-53-34-18-0 6
53084-S 63100-S 100-85-68-53-35-18-3 6
53086-S 63102-S 100-85-68-51-34-17-0 6
54095-S 64113-S 100--88-75-63-50-38-25-13-0 8
54106-S 64126-S 100--88-76-65-51-39-25-14-0 8
54111-S 64132-S 100--87-74-62-49-38-25-13-0 8
54118-S 64140-S 100--88-75-63-50-38-25-13-0 8
Table 5

Actual capacity (at level) = Sea level capacity x altitude correction


Selection Procedure factor (from Table 6).

Example
Altitude Correction Factors
The following information should be determined:
1. Required total capacity = 455 MBh (126 kW) The unit ratings are based on sea level. Above sea level
2. Saturated suction temperature = 50°F (10°C) apply the following correction factors:
3. Condenser entering air temperature = 115°F (46°C)
4. Power Supply (V/PH/Hz) = 380/3/50 Altitude Capacity Power
feet meter Multiplier Multiplier
Enter capacity ratings from Table 3 at 115°F (46°C) 0 0 1 1
condenser entering air temperature and select model
2000 610 0.99 1.01
UCUV 52043-S having a cooling capacity of 479MBh (140.4 kW)
at 50°F (10°C) saturated suction temperature, compressor 4000 1219 0.98 1.02
motor power input is 48.3 kW. For further details refer to 6000 1829 0.97 1.03
physical data and specifications sheets.Capacity ratings are 8000 2438 0.96 1.04
based on sea level operation. Above sea level, apply the 10000 3048 0.95 1.05
following corrections method. Table 6

15
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Field Connections

UCUV-S series self-contained heavy duty air cooled condensing units are designed for minimum field interaction.
Power hook-ups for AHU starter and fan interlock and control wiring of room unit as per Electrical hook-up diagram is all that is
required to electrically connect any model of UCUV-S series .

Every UCUV-S series condensing unit requires, at most, field installed fused disconnect switches or circuit breakers, and room unit.

Refer below for a schematic representation of required field electrical hook-ups for a standard UCUV-S series condensing unit.

All field wiring must be done in accordance with applicable local and national codes.

For maximum recommended fuse sizes and minimum circuit amps for cable sizing, see Page 18 - 20 of this bulletin.

The UCUV-S series is then ready to provide cooling, on demand.

Field Wiring Requirement Schematic


L1 L2 L3 N L N L1 L2 L3 N

3 PHASE,
3 WIRE SYSTEM
440V/3PH/50HZ CIRCUIT BREAKER
220V/3PH/60HZ OR FUSED CIRCUIT BREAKER
460V/3PH/60HZ DISCONNECT SWITCH OR FUSED
(NOT BY UNTES) DISCONNECT SWITCH
(NOT BY UNTES)

3 PHASE,
4 WIRE SYSTEM
380-415V/3PH/50HZ
L1
L2
380V/3PH/60HZ
L3
N

GROUND 3 PHASE,
4 WIRE SYSTEM
E
380-415V/3PH/50HZ
L1 380V/3PH/60HZ
L2

CUSTOMER SUPPLIED
EFM STARTER INTERLOCK TO AHU AND INSTALLED
AHU STARTER BOX
(BY OTHERS) FIELD ACCESSORY
(CONTACTOR, OVERLOAD
RELAY & ON/OFF CONTROL etc.)

DOL/STAR DELTA
FAN INTERLOCK FROM AHU

ROOM UNIT
(LOOSESUPPLY) U
V M
W 3~

+ -
E
CE+ CE-

AIR HANDLING UNIT


CE+

CE-
2 CORE UNSCREENED TWISTED PAIR CABLE
AS PER KNX SPECIFICATION (BY OTHERS) LINE VOLTAGE
FIELD WIRING
AU MR
ACUV-S A-SERIES
SERIES
CONTROL PANEL LOW VOLTAGE
FIELD WIRING
REFER ACTUAL WIRING DIAGRAM
FURNISHED WITH THE UNIT FOR
EXACT IDENTIFICATION OF WIRE NUMBERS.

**AAUMR
CUV - S ASERIES
SERIES UNITS RATED FOR 440V/3PH/50HZ, 460V/3PH/60HZ, OR POWER SUPPLIES WITH OUT NEUTRAL
REQUIRE SEPARATE SOURCE OF CONTROL POWER SUPPLY THRU FIELD SUPPLIED & INSTALLED 15A/220V FUSED
CONTROL DISCONNECT SWITCH OR ORDER WITH FACTORY BUILT IN OPTION ' CXT '.

16
17
**L1
POWERSUPPLY
L2
L3
N
F

C1 C2

N L1 MPCB1 MPCB2 MPCB3 MPCB4

MPM1 * MPM2 I> I> I> I> I> I> I> I> I> I> I> I>
L2 L2
L1 L3
* L1 L3

T2 T1 M1 M2 S1 S2 T2 T1 M1 M2 S1 S2 C3 C4 C5 C6 VMM
CM1 CM2
A BC
NC Com NO
MCB1 CFM1 CFM2 CFM3 CFM4 PROVIDE OVERCURRENT, EARTH FAULT PROTECTION, SHORT CIRCUITAND
** DISCONNECT MEANS AS REQUIRED BYLOCAL & NATIONAL ELECTRIC CODE.

CR1 CR2

ROOM UNIT NOTE:-


(LOOSE SUPPLY) * Typical wiring diagramgivenhereis for units with 380~ 415/3/50 or
380/3/60, 4 wirepower supplies.
Typical Wiring Diagram

* Wiring diagrams for 440/3/50, 220/3/60 or 460/3/60


power supplies areavailableonrequest.
G G
CR1 CR2 CS CR6 + -
* For 440/3/50 or 460/3/60 or power supplies without neutral,
I I CXToption is amust.
VMM
2COREUNSCREENED * MPMModule is not available in some small compressors.

LPS-1
LPS-2
TWISTED PAIR CABLE
AS PER KNXSPECIFICATON

RUN/STOP
(BY OTHERS)

FAN INTERLOCK
L E GEN D

DISC. PRESSURE-1
DISC. PRESSURE-2
MCB2
TFR TRANSFORMER VMM VOLTAGEMONITORINGMODULE
CS CONTROL SWITCH MPM MOTOR PROTECTOR MODULE
C CONTACTOR MPCB MOTOR PROTECTORCIRCUT BREAKER
CCH CRANK CASE HEATER OL OVERLOADRELAY
MCB MINIATURECIRCUITBREAKER LSV LIQUID LINESOLENOID VALVE
CFM CONDENSERFANMOTOR EFM EVAPORATOR FANMOTOR
CM COMPRESSORMOTOR CR CONTROL RELAY
24~_ RS485 PB LPS LOW PRESSURESWITCH
FIELD WIRING
HPS HIGH PRESSURESWITCH

B-

M
M
M
M
M
M
M

X1
X2
X3
X4
X5
X6
X7
X8

B1
B2
B3
A+

D1
D2
DG
CE-

REF
CE+

5V=
5V=
DU1
DU2

T1
T2
T3
T4
T5
T6
T7

VOLT FREE CONTACT TO

24V=
24V=
MATCHING AHU FOR

CR5

INFO

EFMSTARTER
MICROPROCESSSOR
OK INTERLOCK
TFR
CONTROLLER

24V

220~ 240V
ESC

C1 C2 CR3 CR4

T8
T9

24~_
G0
Q12
Q11
Q14
Q22
Q21
Q24
Q33
Q34
Q43
Q44
Q53
Q54
Q64
Q73
Q74
Q84
C
D01
D02
DL1
DN
DL2

T10
T11
T12
T13
T-IP
T-HI

LSV-1 LSV-2
CCH1
CCH2
(BY OTHERS)

HPS-1
HPS-2
FAN INTERLOCK

COMP.-1
LSV-1
COMP.-2
LSV-2
CFM1
CFM2
CFM3
CFM4
EFM
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

E C1 CR3 C2 CR4 C3 C4 C5 C6 CR5 CR6


Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

ELECTRICAL DATA Power Supply: 380-415V / 3Ph / 50Hz


Unit Characteristic
Model Compressor Condenser Fan Motor
UCUV
MFA MCA ICF QTY RLA LRA QTY FLA LRA
51008-S 63 30 123 1 22 118 2 1.1 3.9
51010-S 80 40 179 1 30 174 2 1.1 3.9
51013-S 100 52 236 1 38 225 2 2.4 8.9
52015-S 80 54 151 1+1 22 + 22 118 + 118 2 2.4 8.9
51016-S 125 60 283 1 44 272 2 2.4 8.9
52017-S 100 64 207 1+1 30 + 22 174 + 118 2 2.4 8.9
52019-S 125 75 225 1+1 30 + 30 174 + 174 2 3.9 17.2
52022-S 125 85 276 1+1 38 + 30 225 + 174 2 3.9 17.2
52025-S 160 97 288 1+1 38 + 38 225 + 225 3 3.9 17.2
52028-S 160 105 335 1+1 44 + 38 272 + 225 3 3.9 17.2
52030-S 160 111 341 1+1 44 + 44 272 + 272 3 3.9 17.2
52036-S 200 139 289 2+2 30 + 30 174 + 174 3 3.9 17.2
52043-S 200 161 352 2+2 38 + 30 225 + 174 4 3.9 17.2
52048-S 250 177 368 2+2 38 + 38 225 + 225 4 3.9 17.2
52053-S 250 191 421 2+2 44 + 38 272 + 225 4 3.9 17.2
52060-S 250 203 433 2+2 44 + 44 272 + 272 4 3.9 17.2
53064-S 315 237 441 3+3 38 + 30 225 + 174 6 3.9 17.2
53071-S 315 261 465 3+3 38 + 38 225 + 225 6 3.9 17.2
53079-S 400 274 518 2+4 44 + 38 272 + 225 6 3.9 17.2
53084-S 400 286 530 4+2 44 + 38 272 + 225 6 3.9 17.2
53086-S 400 292 536 5+1 44 + 38 272 + 225 6 3.9 17.2
54095-S 400 345 549 4+4 38 + 38 225 + 225 8 3.9 17.2
54106-S 500 364 608 3+5 44 + 38 272 + 225 8 3.9 17.2

Table 7
54111-S 500 376 620 5+3 44 + 38 272 + 225 8 3.9 17.2
54118-S 500 394 638 8 44 272 8 3.9 17.2

Power Supply: 440V / 3Ph / 50Hz


Unit Characteristic
Model Compressor Condenser Fan Motor
UCUV
MFA MCA ICF QTY RLA LRA QTY FLA LRA
51008-S 63 30 123 1 22 118 2 1.1 3.9
51010-S 80 40 179 1 30 174 2 1.1 3.9
51013-S 100 53 237 1 38 225 2 2.8 9.2
52015-S 80 55 152 1+1 22 + 22 118 + 118 2 2.8 9.2
51016-S 125 61 284 1 44 272 2 2.8 9.2
52017-S 100 65 208 1+1 30 + 22 174 + 118 2 2.8 9.2
52019-S 125 76 226 1+1 30 + 30 174 + 174 2 4.3 17.6
52022-S 125 86 277 1+1 38 + 30 225 + 174 2 4.3 17.6
52025-S 160 98 289 1+1 38 + 38 225 + 225 3 4.3 17.6
52028-S 160 106 336 1+1 44 + 38 272 + 225 3 4.3 17.6
52030-S 160 112 342 1+1 44 + 44 272 + 272 3 4.3 17.6
52036-S 200 140 290 2+2 30 + 30 174 + 174 3 4.3 17.6
52043-S 250 163 354 2+2 38 + 30 225 + 174 4 4.3 17.6
52048-S 250 179 370 2+2 38 + 38 225 + 225 4 4.3 17.6
52053-S 250 192 423 2+2 44 + 38 272 + 225 4 4.3 17.6
52060-S 250 204 435 2+2 44 + 44 272 + 272 4 4.3 17.6
53064-S 315 239 443 3+3 38 + 30 225 + 174 6 4.3 17.6
53071-S 315 263 467 3+3 38 + 38 225 + 225 6 4.3 17.6
53079-S 400 277 520 2+4 44 + 38 272 + 225 6 4.3 17.6
53084-S 400 289 532 4+2 44 + 38 272 + 225 6 4.3 17.6
53086-S 400 295 538 5+1 44 + 38 272 + 225 6 4.3 17.6
54095-S 400 348 552 4+4 38 + 38 225 + 225 8 4.3 17.6
54106-S 500 367 611 3+5 44 + 38 272 + 225 8 4.3 17.6
54111-S 500 379 623 5+3 44 + 38 272 + 225 8 4.3 17.6
Table 8

54118-S 500 397 641 8 44 272 8 4.3 17.6

18
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

ELECTRICAL DATA Power Supply: 380 / 3Ph / 60Hz


Unit Characteristic
Model Compressor Condenser Fan Motor
UCUV
MFA MCA ICF QTY RLA LRA QTY FLA LRA
61009-S 63 33 151 1 24 145 2 1.5 4.5
61011-S 100 49 202 1 37 196 2 1.5 4.5
61016-S 125 59 293 1 42 280 2 3.1 9.6
62018-S 100 60 182 1+1 24 + 24 145 + 145 2 3.1 9.6
61018-S 160 76 366 1 56 353 2 3.1 9.6
62020-S 125 76 233 1+1 37 + 24 196 + 145 2 3.1 9.6
62022-S 160 94 256 1+1 37 + 37 196 + 196 2 5.3 17.5
62026-S 160 100 340 1+1 42 + 37 280 + 196 2 5.3 17.5
62030-S 160 110 350 1+1 42 + 42 280 + 280 3 5.3 17.5
62033-S 200 128 423 1+1 56 + 42 353 + 280 3 5.3 17.5
62036-S 200 142 437 1+1 56 + 56 353 + 353 3 5.3 17.5
62043-S 250 173 335 2+2 37 + 37 196 + 196 3 5.3 17.5
62051-S 250 190 429 2+2 42 + 37 280 + 196 4 5.3 17.5
62058-S 250 200 439 2+2 42 + 42 280 + 280 4 5.3 17.5
62063-S 315 231 526 2+2 56 + 42 353 + 280 4 5.3 17.5
62071-S 400 259 554 2+2 56 + 56 353 + 353 4 5.3 17.5
63076-S 400 279 531 3+3 42 + 37 280 + 196 6 5.3 17.5
63085-S 400 294 546 3+3 42 + 42 280 + 280 6 5.3 17.5
63094-S 400 326 633 2+4 56 + 42 353 + 280 6 5.3 17.5
63100-S 500 354 661 4+2 56 + 42 353 + 280 6 5.3 17.5
63102-S 500 368 675 5+1 56 + 42 353 + 280 6 5.3 17.5
64113-S 500 389 641 4+4 42 + 42 280 + 280 8 5.3 17.5
64126-S 500 434 742 3+5 56 + 42 353 + 280 8 5.3 17.5

Table 9
64132-S 630 462 770 5+3 56 + 42 353 + 280 8 5.3 17.5
64140-S 630 504 812 8 56 353 8 5.3 17.5

Power Supply: 460 / 3Ph / 60Hz


Unit Characteristic
Model Compressor Condenser Fan Motor
UCUV
MFA MCA ICF QTY RLA LRA QTY FLA LRA
61009-S 63 29 132 1 21 125 2 1.3 5.2
61011-S 80 38 186 1 28 179 2 1.3 5.2
61016-S 100 54 240 1 38 225 2 3.1 11.8
62018-S 80 53 161 1+1 21 + 21 125 + 125 2 3.1 11.8
61018-S 125 61 287 1 44 272 2 3.1 11.8
62020-S 100 62 215 1+1 28 + 21 179 + 125 2 3.1 11.8
62022-S 125 73 233 1+1 28 + 28 179 + 179 2 5 21.0
62026-S 125 86 279 1+1 38 + 28 225 + 179 2 5 21.0
62030-S 160 101 294 1+1 38 + 38 225 + 225 3 5 21.0
62033-S 160 108 341 1+1 44 + 38 272 + 225 3 5 21.0
62036-S 160 114 347 1+1 44 + 44 272 + 272 3 5 21.0
62043-S 200 134 294 2+2 28 + 28 179 + 179 3 5 21.0
62051-S 250 162 355 2+2 38 + 28 225 + 179 4 5 21.0
62058-S 250 182 375 2+2 38 + 38 225 + 225 4 5 21.0
62063-S 250 195 428 2+2 44 + 38 272 + 225 4 5 21.0
62071-S 315 207 440 2+2 44 + 44 272 + 272 4 5 21.0
63076-S 315 238 447 3+3 38 + 28 225 + 179 6 5 21.0
63085-S 315 268 477 3+3 38 + 38 225 + 225 6 5 21.0
63094-S 400 281 530 2+4 44 + 38 272 + 225 6 5 21.0
63100-S 400 293 542 4+2 44 + 38 272 + 225 6 5 21.0
63102-S 400 299 548 5+1 44 + 38 272 + 225 6 5 21.0
64113-S 400 354 563 4+4 38 + 38 225 + 225 8 5 21.0
64126-S 500 373 622 3+5 44 + 38 272 + 225 8 5 21.0
Table 10

64132-S 500 385 634 5+3 44 + 38 272 + 225 8 5 21.0


64140-S 500 403 652 8 44 272 8 5 21.0

19
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

ELECTRICAL DATA Power Supply: 220V / 3Ph / 60Hz

Model Unit Characteristic Compressor Condenser Fan Motor


UCUV
MFA MCA ICF QTY RLA LRA QTY FLA LRA
61009-S 125 64 255 1 47 245 2 2.5 7.5
61011-S 160 80 350 1 60 340 2 2.5 7.5
61016-S 200 112 527 1 81 505 2 5.4 16.7
62018-S 200 117 314 1+1 47 + 47 245 + 245 2 5.4 16.7
61018-S 250 120 627 1 87 605 2 5.4 16.7
62020-S 200 133 409 1+1 60 + 47 340 + 245 2 5.4 16.7
62022-S 250 153 439 1+1 60 + 60 340 + 340 2 9 29.7
62026-S 315 179 604 1+1 81 + 60 505 + 340 2 9 29.7
62030-S 315 209 634 1+1 81 + 81 505 + 505 3 9 29.7
62033-S 315 217 734 1+1 87 + 81 605 + 505 3 9 29.7
62036-S 315 223 740 1+1 87 + 87 605 + 605 3 9 29.7
62043-S 400 282 568 2+2 60 + 60 340 + 340 3 9 29.7
62051-S 500 338 763 2+2 81 + 60 505 + 340 4 9 29.7
62058-S 500 380 805 2+2 81 + 81 505 + 505 4 9 29.7
62063-S 500 394 911 2+2 87 + 81 605 + 505 4 9 29.7
62071-S 500 406 923 2+2 87 + 87 605 + 605 4 9 29.7
63076-S 630 497 942 3+3 81 + 60 505 + 340 6 9 29.7
63085-S 800 560 1005 3+3 81 + 81 505 + 505 6 9 29.7
63094-S 800 574 1111 2+4 87 + 81 605 + 505 6 9 29.7
63100-S 800 586 1123 4+2 87 + 81 605 + 505 6 9 29.7
63102-S 800 592 1129 5+1 87 + 81 605 + 505 6 9 29.7
64113-S 1000 740 1185 4+4 81 + 81 505 + 505 8 9 29.7
64126-S 1000 760 1297 3+5 87 + 81 605 + 505 8 9 29.7
64132-S 1000 772 1309 5+3 87 + 81 605 + 505 8 9 29.7
64140-S 1000 790 1327 8 87 605 8 9 29.7
Table 11
Legend

MFA Maximum Fuse Amps (for fuse/circuit breaker sizing), PWS Part Winding Start.
omplies with NEC Article 440-22 & 430-52. RLA Rated Load Amps. (at worst operating condition) .
MCA Minimum Circuit Amps.(for wire3 sizing), complies with
NEC article 440-33. LRA Locked Rotor Amps.
ICF Maximum Instantaneous Current Flow. FLA Full Load Amps.
DOL Direct On-Line Start .
Note :
Voltage imbalance not to exceed ± 2 % of the rated voltage.

Dimensional Data 10 10
[254] A3 [254]
UCUV Models: 51008S-51010S & 61009S-61011S A1

LEGEND
1 CO NDENSER FAN
2 CO NDENSER COIL
3 CO NTRO L PANEL
4 CO MPRESSOR
A2 A4
LINE SIZES ARE BASED ON 100f EQUIVALENT LENGTH
ALL DIMENSIONS ARE IN INCHES [m m]
68
45
[1727] 1
3 [1143]

ENSIONS ARE IN INCHES [m m] 2 SUC.Ø


VENTILATION
ON BOTH SIDES
[1312]

LIQ.Ø
51.65

MODEL CONNECTØIONSIZE,
UCUV- SUC. LIQ. DETACHABLE
[305]

PLATE FOR
51008S 1 5/8 5/8
12

CABLE ENTRY
61009S [41] [16]
ACCESS
51010S 1 5/8 7/8
[178]
[100]
3.94

61011S [41] [22] 4


20 6 RIGGING HOLES
7

[152] Ø0.79 [20] 4 Nos.


45
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Dimens
Dimensional Data
UCUV Models: 51013S-52022S & 61016S-62026S

6S 10 10
[254] A3 [254]

CONNECTION SIZE, Ø A1
DIMENSIONS ONNECTION SIZE, Ø
MODEL CIRCUIT-2
CIRCUIT-1 UIT-1 CIRCUIT-2
UCUV- L W H A B
SUC.#1 LIQ.#1 SUC.#2 LIQ.#2 LIQ.#1 SUC.#2 LIQ.#2
7/8
*61016S
51013S 56
[1422]
74
[1880]
51.65
[1312]
12.72
[323] - 2 1/8 7/ 8
[54] [22] - - [22] - -
5/8 1 5/8 5/8
52015S 56 74 51.65 12 12 1 5/8 5/8 1 5/8 5/8 [16] [41] [16]
62018S [1422] [1880] [1312] [305] [305] [41] [16] [41] [16] 7/ 8 - -
*51016S
61018S
56
[1422]
76
[1930]
51.65
[1312]
12.72
[323] - 2 1/8 7/8
[54] [22] - -
[22]
7/8 1 5/8 5/8
1 5/8 7/8 1 5/8 5/8 [22] [41] [16]
52017S 56 76 51.65 12 12
62020S [1422] [1930] [1312] [305] [305] [41] [22] [41] [16] 7/8 1 5/8 7/8
[22] [41] [22]
52019S 56 84 59.65 12 12 1 5/8 7/ 8 1 5/8 7/ 8 7/8 1 5/8 7/8 A4
62022S [1422] [2134] [1515] [305] [305] [41] [22] [41] [22] A2
[22] [41] [22]
52022S 58 84 59.65 12.72 12 2 1/8 7/ 8 1 5/8 7/8
62026S [1473] [2134] [1515] [323] [305] [54] [22] [41] [22]
SSOR MODEL
* MODEL WITH ONE COMPRESSOR
DIM.12" INSTEAD OF 10" & 4" F OR O N E C O M P R ES SOR MODEL W
ALL DIMENSIONS ARE IN INCHES [mm ]
L

L
SUCTION #2
3 1 SUCTION #1
LIQUID #2
LIQUID #1
RIGGING HOLES
Ø0.79 [20] 4 Nos.
VENTILATION 2
ON BOTH SIDES
A

B
H

*
[100]

ACCESS 4
3.94

4*
[178]

[178]
DETACHABLE
7

7
PLATE FO R [101]
CABLE ENTRY [101]
A

10 * 10 *
[254] [254]
4

UCUV Models: 52025S-52036S & 62030S- 62043S


10 10
[254] [254]
A1 A3
DIMENSIONS CONNECTION SIZE,Ø
MODEL
UCUV- CIRCUIT-1 CIRCUIT-2
H A B
SUC.#1 LIQ.#1 SUC.#2 LIQ.#2
52025S 60.63 13.7 13.7 2 1/8 7/8 2 1/8 7/8 LEGEND
62030S [1540] [348] [348] [54] [22] [54] [22] 1 CONDENSER FAN
52028S 60.63 13.7 13.7 2 1/8 7/8 2 1/8 7/8 2
62033S [1540] [348] [348] [54] [22] [54] [22] CONDENSER COIL
52030S 60.63 13.7 13.7 2 1/8 7/8 2 1/8 7/8 3 CONTROL PANEL
62036S [1540] [348] [348] [54] [22] [54] [22] 4 COMPRESSOR
* 52036S 77.63 27.29 27.29 2 1/8 7/8 2 1/8 7/8
* 62043S [1972] [693] [693] [54] [22] [54] [22]
* MODEL WITH TANDEM COMPRESSOR
LINE SIZES ARE BASED ON 100f tEQUIVALEN T LENGTH
ALL DIMENSIONS ARE IN INCHES [mm]
A2 A4

76 88
[1930] [2235]
1
3

2 SUCTION#1 SUCTION #2
VENTILATION
ON BOTH SIDES LIQUID#1 LIQUID #2
H
[125]
4.92

DETACHABLE
PLATE FOR
A

CABLE ENTRY

4 4 ACCESS 4
[203]

[203]

[102] [102]
8

10 10
[254] [254]
21
21
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Dimensional Data
UCUV Models: 52043S-52060S & 62051S-62071S
10 10
[254] [254]
A1 A3
DIMENSIONS CONNECTION SIZE,Ø
MODEL CIRCUIT-1 CIRCUIT-2
UCUV- H
SUC.#1 LIQ.#1 SUC.#2 LIQ.#2
52043S 77.63 2 5/8 1 1/8 2 5/8 1 1/8 LEGEND
62051S [1972] [67] [29] [67] [29]
1 CONDENSER FAN
52048S 85.63 2 5/8 1 1/8 2 5/8 1 1/8
62058S [2175] [67] [29] [67] [29] 2 CONDENSER COIL
52053S 85.63 2 5/8 1 1/8 2 5/8 1 1/8 3 CONTROL PANEL
62063S [2175] [67] [29] [67] [29] 4 TANDEM COMPRESSOR
52060S 85.63 2 5/8 1 1/8 2 5/8 1 1/8
62071S [2175] [67] [29] [67] [29]
LINE SIZES ARE BASED ON 100f tEQUIVALENT LENGTH
ALL DIMENSIONS ARE IN INCHES[mm]
A2 A4

84 88
[2134] [2235]
1

2
FILTERED SUCTION #1 SUCTION #2
VENTILATION
ON BOTH SIDES
H

LIQUID #1 LIQUID #2
DETACHABLE
[125]
4.92

PLATE FOR
[693]

[693]
27.29

27.29
CABLE ENTRY

ACCESS
4
[203]

[203]
8

8
RIGGING HOLES 4 4
Ø.79[20]4 Nos.
[102] [102]
10 10
[254] [254]

UCUV Models: 53064S-53086S & 63102S


10 10
[254] [254]
A1 A3 A5

LEGEND
CIRCUIT-1
1 CONDENSER FAN CIRCUIT-2
2 CONDENSER COIL CIRCUIT-3
3 CONTROL PANEL
4 TANDEM COMPRESSOR

LINE SIZES ARE BASED ON 100f tEQUIVALENT LENGTH


A2 A4 A6
ALL DIMENSIONS ARE IN INCHES [m m]
88 135.6
[2235] [3445]
47 88.6 12
[1195] [2250] [305]
2 1 PARTITION
3

FILTERED
VENTILATION
ON BOTH SIDES
LIQUID Ø
1 1/8[29]x 4Nos.
105.91
[2690]

[2420]
95.28

DETACHABLE
PLATE FOR
CABLE ENTRY
[750]
29.5

4
[125]

SUCTION Ø RIGGING HOLES


4.92

2 5/8[67]x 4Nos. Ø7/8[22]x 4 Nos.

22
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Dimensional Data
UCUV Models: 54095S- 54118S & 64140S
10 20 10
[254] [508] [254]
A1 A3 A5 A7

LEGEND
1 CONDENSER FAN CIRCUIT-1
CIRCUIT-2
2 CONDENSER COIL
CIRCUIT-3
3 CONTROL PANEL CIRCUIT-4
4 TANDEM COMPRESSOR

LINE SIZES ARE BASED ON 100f tEQUIVALENT LENGTH


ALL DIMENSIONS ARE IN INCHES [m m]
A2 A4 A6 A8
88 177.2
[2235] 88.6 [4500] 88.6 12
[2250] [2250] [305]
PARTITION 2 1 PARTITION 3

FILTERED
LIQUID Ø VENTILATION
1 1/8[29]x 4Nos. ON BOTH SIDES
106.91
[2715]

[2420]
95.28

DETACHABLE
PLATE FOR
CABLE ENTRY
[750]
29.5

4
SUCTION Ø RIGGING HOLES
[150]
5.91

2 5/8[67]x 4Nos. Ø7/8[22]x 4 Nos.

LOADING POINTS - 50Hz LOADING POINTS - 60Hz


LOADING POINTS TOTAL LOADING POINTS TOTAL
UCUV UNIT UCUV UNIT
A1 A2 A3 A4 WEIGHT A1 A2 A3 A4 WEIGHT
Ib. 194 203 194 218 809 Ib. 196 203 196 221 816
51008-S 61009-S
Kg. 88 92 88 99 367 Kg. 89 92 89 100 370
Ib. 214 223 214 238 889 Ib. 218 223 216 238 895
51010-S 61011-S
Kg. 97 101 97 108 403 Kg. 99 101 98 108 406
Ib. 265 306 265 306 1142 Ib. 265 306 265 306 1142
51013-S 61016-S
Kg. 120 139 120 139 518 Kg. 120 139 120 139 518
Ib. 254 331 254 331 1169 Ib. 254 331 254 331 1169
52015-S 62018-S
Kg. 115 150 115 150 530 Kg. 115 150 115 150 530
Ib. 265 306 265 306 1142 Ib. 265 306 265 306 1142
51016-S 61018-S
Kg. 120 139 120 139 518 Kg. 120 139 120 139 518
Ib. 265 353 256 340 1213 Ib. 265 353 256 340 1213
52017-S 62020-S
Kg. 120 160 116 154 550 Kg. 120 160 116 154 550
Ib. 284 375 284 375 1319 Ib. 284 375 284 375 1319
52019-S 62022-S
Kg. 129 170 129 170 598 Kg. 129 170 129 170 598
Ib. 326 445 298 395 1464 Ib. 326 445 298 395 1464
52022-S 62026-S
Kg. 148 202 135 179 664 Kg. 148 202 135 179 664
Ib. 366 366 516 516 1764 Ib. 366 366 516 516 1764
52025-S 62030-S
Kg. 166 166 234 234 800 Kg. 166 166 234 234 800
Ib. 366 366 516 516 1764 Ib. 366 366 516 516 1764
52028-S 62033-S
Kg. 166 166 234 234 800 Kg. 166 166 234 234 800
Ib. 366 366 516 516 1764 Ib. 366 366 516 516 1764
52030-S 62036-S
Kg. 166 166 234 234 800 Kg. 166 166 234 234 800
Ib. 406 395 637 624 2062 Ib. 415 404 642 631 2090
52036-S 62043-S
Kg. 184 179 289 283 935 Kg. 188 183 291 286 948
Ib. 706 706 933 933 3277 Ib. 706 706 933 933 3277
52043-S 62051-S
Kg. 320 320 423 423 1486 Kg. 320 320 423 423 1486
Ib. 761 761 1032 1032 3585 Ib. 761 761 1032 1032 3585
52048-S 62058-S
Kg. 345 345 468 468 1626 Kg. 345 345 468 468 1626
Ib. 761 761 1032 1032 3585 Ib. 772 772 1041 1041 3625
52053-S 62063-S
Kg. 345 345 468 468 1626 Kg. 350 350 472 472 1644
Ib. 800 800 1107 1107 3815 Ib. 809 809 1116 1116 3850
52060-S 62071-S
Kg. 363 363 502 502 1730 Kg. 367 367 506 506 1746
Table 12 Table 13

23
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

LOADING POINTS - 50Hz


LOADING POINTS TOTAL
UCUV UNIT
A1 A2 A3 A4 A5 A6 A7 A8 WEIGHT

53064-S Ib. 781 1019 1200 1019 942 1180 - - 6139


Kg. 354 462 544 462 427 535 - - 2784
53071-S Ib. 805 1094 1316 1094 968 1257 - - 6533
Kg. 365 496 597 496 439 570 - - 2963
53079-S Ib. 838 1127 1349 1127 999 1288 - - 6727
Kg. 380 511 612 511 453 584 - - 3051
53084-S Ib. 838 1127 1349 1127 999 1288 - - 6727
Kg. 380 511 612 511 453 584 - - 3051
53086-S Ib. 838 1127 1349 1127 999 1288 - - 6727
Kg. 380 511 612 511 453 584 - - 3051
54095-S Ib. 1111 882 875 1116 1111 882 1036 1279 8293
Kg. 504 400 397 506 504 400 470 580 3761
54106-S Ib. 1144 913 908 1149 1144 913 1069 1310 8551
Kg. 519 414 412 521 519 414 485 594 3878
54111-S Ib. 1144 913 908 1149 1144 913 1069 1310 8551
Kg. 519 414 412 521 519 414 485 594 3878
54118-S Ib. 1144 913 908 1149 1144 913 1069 1310 8551
Kg. 519 414 412 521 519 414 485 594 3878
Table 14

LOADING POINTS - 60Hz


LOADING POINTS TOTAL
UCUV UNIT
A1 A2 A3 A4 A5 A6 A7 A8 WEIGHT

63076-S Ib. 781 1019 1200 1019 942 1180 - - 6139


Kg. 354 462 544 462 427 535 - - 2784
63085-S Ib. 805 1094 1316 1094 968 1257 - - 6533
Kg. 365 496 597 496 439 570 - - 2963
63094-S Ib. 849 1136 1358 1136 1010 1299 - - 6787
Kg. 385 515 616 515 458 589 - - 3078
63100-S Ib. 849 1136 1358 1136 1010 1299 - - 6787
Kg. 385 515 616 515 458 589 - - 3078
63102-S Ib. 849 1136 1358 1136 1010 1299 - - 6787
Kg. 385 515 616 515 458 589 - - 3078
64113-S Ib. 1122 891 884 1125 1122 891 1047 1288 8370
Kg. 509 404 401 510 509 404 475 584 3796
64126-S Ib. 1153 924 917 1158 1153 924 1080 1321 8630
Kg. 523 419 416 525 523 419 490 599 3914
64132-S Ib. 1153 924 917 1158 1153 924 1080 1321 8630
Kg. 523 419 416 525 523 419 490 599 3914
64140-S Ib. 1153 924 917 1158 1153 924 1080 1321 8630
Kg. 523 419 416 525 523 419 490 599 3914
Table 15

24
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Location and Space Requirements UCUV A B C


51008-S 61009-S
Due to the vertical air flow discharge condenser design, it is 42
recommended that certain precautions are to be taken before 51010-S 61011-S
installation. There should be no obstruction on the air flow. 51013-S 61016-S
40 60
52015-S 62018-S
Orient the unit so that prevailing winds blow parallel to the unit length 51016-S 61018-S 50
thus minimizing the effects on condensing pressure. If it is not practical 52017-S 62020-S
to orient the unit in this manner, a wind deflecting shield should be
52019-S 62022-S
considered.
52022-S 62026-S 56
It is also necessary to provide adequate clearance on all sides of the unit 52025-S 62030-S 48 72
for service access and satisfactory performance. This will prevent excessive 52028-S 62033-S
66
condensing temperatures and enhance system performance and operating 52030-S 62036-S
economy. 52036-S 62043-S
64 96
52043-S 62051-S
A flat concrete foundation or floor which can support the weight of the
52048-S 62058-S
equipment must be provided as the unit must be level for proper operation 78
and functioning of controls. 52053-S 62063-S 72 108
52060-S 62071-S
Under certain critical conditions it is recommended that vibration isolators 53064-S 63076-S
of rubber-in-shear or spring type be installed under the base. 53071-S 63085-S
53079-S 63094-S
The isolators must be designed for the operating weight of the unit. For
53084-S 63100-S
operating load points refer to Loading Points Data (page No.23 & 24).
53086-S 63102-S 84 46 90
Correct selection of types of isolators depends upon application and
structure. 54095-S 64113-S
54106-S 64126-S
54111-S 64132-S
54118-S 64140-S
Table 16

SINGLE UNIT INSTALLATION

SPACING FOR AIR FLOW SPACING FOR SERVICE AND ACCESS

*
A

B
A
A

*
A

UCUV-51008S to 52060S UCUV-53064S to 54118S


UCUV-61009S to 62071S UCUV-63076S to 64140S

* SPACING FOR AIRFLOW & SERVICE


25
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

MULTIPLE UNIT INSTALLATION

SPACING FOR AIR FLOW SPACING FOR SERVICE AND ACCESS

B
B
*

A
A

*
C

C
A

B
*
A
UCUV-51008S to 52060S
UCUV-61009S to 62071S

UCUV-53064S to 54118S
UCUV-63076S to 64140S

* SPACING FOR AIRFLOW & SERVICE

26
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Typical Refrigeration Piping


1

Legend 2
3
AIR

1. Expansion Valve 4
FLOW

5
2. Sight Glass AHU

3. Solenoid Valve
4. Filter Drier
5. Shut Off Valve
CONDENSING
UNIT
6

6. Liquid Line
7. Suction Line
1

2 7
7
3

Single Circuit Unit Shown. For Dual


AIR
FLOW
4

circuit units, piping of second circuit is


5

AHU CONDENSING

similar. UNIT

DOTTED IN CASE OF
LEGEND
DOUBLE SUCTION RISER
1 EXPANSION VALVE
2 SIGHT GLASS
3 SOLENOID VALVE
4 FILTER DRIER
5 SHUT OFF VALVE
6 LIQUID LINE
7 SUCTION LINE

Refrigerant Piping
Correct design and size of refrigerant piping is necessary c. Pressure drop due to vertical lift of liquid line for R-134a 1°F
for proper operation. The refrigerant piping generally should (0.55°C) sub cooling must be allowed for each 5.5 ft (1.7m)
be designed to accomplish the following: vertical rise in order to avoid flash gas forming due to the weight
of the column of liquid refrigerant.
a. To ensure proper refrigerant feed to the evaporator.
b. To provide practical refrigerant line sizes without excessive UNTES UCUV-S Series units are designed with a sub cooling
pressure drop. circuit enough to sub cool the liquid 12°F (6.6 °C), which gives the
c. To maintain uniform return of lubricating oil to the liquid maximum 66 ft. (20m) lift without additional sub cooling.
compressor. Liquid suction heat exchanger can be used for additional sub
cooling in order to avoid flash gas forming.
d. To prevent refrigerant from entering the compressor and
causing compressor damage due to "slugging".

Field Expansion Valve Selection Matching DX Coil Selection


For single circuit UCUV-S Series, the DX coil selection
The following recommendations should be taken into in a UKS or other air handler from UNTES should be
consideration when selecting expansion valves in field. based on total capacity. For dual circuit UCUV-S
Series, extra care should be exercised and correspondingly
1. Expansion valves should be installed as close to the
split, by face area or number of rows to correspond
evaporator as possible, mounted directly to the distributor.
and match the capacity split available in the dual circuited
UCUV-S Series selected. For optimum matching the
2. The following possible sources of pressure drop to be
DX coil should be ordered from UNTES as well.
considered:
UNTES provides correct no. of feeds and circuits and
a. Friction losses through refrigerant lines.
properly sized distribution to ensure the correct split on the
DX coil is made available to match the particular
b. Pressure drop across valves and controls.
selected UCUV-S Series model.

27
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Recommended Refrigerant Line Sizes - 50 Hz

Liquid Line, Inches Suction Line, Inches


Model
Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 1 Circuit 2 Circuit 3 Circuit 4
UCUV
25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft
51008-S 5/8 5/8 5/8 5/8 - - - 1 3/8 1 3/8 1 5/8 1 5/8 - - -
51010-S 5/8 5/8 5/8 7/8 - - - 1 3/8 1 3/8 1 5/8 1 5/8 - - -
51013-S 5/8 7/8 7/8 7/8 - - - 1 3/8 1 5/8 1 5/8 2 1/8 - - -
52015-S 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - -
51016-S 5/8 7/8 7/8 7/8 - - - 1 5/8 1 5/8 2 1/8 2 1/8 - - -
52017-S 5/8 5/8 5/8 5/8 5/8 5/8 5/8 7/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - -
52019-S 5/8 5/8 5/8 7/8 5/8 5/8 5/8 7/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - -
52022-S 5/8 7/8 7/8 7/8 5/8 5/8 5/8 7/8 - - - - - - - - 1 3/8 1 5/8 1 5/8 2 1/8 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - -
52025-S 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 3/8 1 5/8 1 5/8 2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 - - - - - - - -
52028-S 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 3/8 1 5/8 1 5/8 2 1/8 1 5/8 1 5/8 2 1/8 2 1/8 - - - - - - - -
52030-S 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 1 5/8 2 1/8 2 1/8 1 5/8 1 5/8 2 1/8 2 1/8 - - - - - - - -
52036-S 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - -
52043-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8 2 5/8 - - - - - - - -
52048-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - -
52053-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - -
52060-S 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - - - - - -
53064-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - 1 5/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8 2 5/8 - - - -
53071-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - -
53079-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - -
53084-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -
53086-S 7/8 7/8 7/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -
54095-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8
54106-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8
54111-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 1 1/8 1 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8
54118-S 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8
Table 17

UNTES UCUV-S Series Condensing Units are designed for satisfactory operation with single suction line.
1. Suction Line sizing selection recommendation in Table 17 is based on 2ºF temperature drop.
2. Double suction risers, for applications with systems having large variations in capacity , are recommended to ensure proper
oil low up and return to compressor.
3. Liquid line sizing selection recommendation in table 17 & 18 is based on 2ºF temperature drop.
4. Recommended line sizes in Table 17 are for guidance only. For detailed proper pip. For detailed proper piping, consult
recognized piping like ASHRAE Guide and Data Book for assistance.
5. Equivalent suction and liquid line lengths are shown in table 17 & 18.

UNTES is not responsible for faulty or improper design or sizing of refrigerant lines. The above recommendations do
not incorporate necesarry slopes. etc. that may be required on horizontal risers, etc.

28
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a

Recommended Refrigerant Line Sizes - 60 Hz

Liquid Line, Inches Suction Line, Inches


Model
Circuit 1 Circuit 2 Circuit 3 Circuit 4 Circuit 1 Circuit 2 Circuit 3 Circuit 4
UCUV
25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft
61009-S 5/8 5/8 5/8 5/8 - - - 1 3/8 1 3/8 1 5/8 1 5/8 - - -
61011-S 5/8 5/8 7/8 7/8 - - - 1 3/8 1 5/8 1 5/8 1 5/8 - - -
61016-S 5/8 7/8 7/8 7/8 - - - 1 5/8 1 5/8 2 1/8 2 1/8 - - -
62018-S 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - -
61018-S 5/8 7/8 7/8 7/8 - - - 1 5/8 2 1/8 2 1/8 2 1/8 - - -
62020-S 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -
62022-S 5/8 5/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 3/8 1 5/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -
62026-S 5/8 7/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 5/8 1 5/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -
62030-S 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 1 5/8 2 1/8 2 1/8 1 5/8 1 5/8 2 1/8 2 1/8 - - - - - - - -
62033-S 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 1 5/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - -
62036-S 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - -
62043-S 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - -
62051-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - -
62058-S 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - - - - - -
62063-S 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - - - - - -
62071-S 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -
63076-S 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - -
63085-S 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -
63094-S 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -
63100-S 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - -
63102-S 7/8 7/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - -
64113-S 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8
64126-S 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8
64132-S 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8
64140-S 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8
Table 18

UNTES UCUV-S Series Condensing Units are designed for satisfactory operation with single suction line.
1. Suction Line sizing selection recommendation in Table 18 is based on 2ºF temperature drop.
2. Double suction risers, for applications with systems having large variations in capacity , are recommended to ensure proper
oil low up and return to compressor.
3. Liquid line sizing selection recommendation in table 18 is based on 2ºF temperature drop.
4. Recommended line sizes in Table 18 are for guidance only. For detailed proper pi. For detailed proper piping, consult
recognized piping like ASHRAE Guide and Data Book for assistance.

5. Equivalent suction and liquid line lengths are shown in table 17 &18.

UNTES is not responsible for faulty or improper design or sizing of refrigerant lines. The above recommendations do
not incorporate necesarry slopes. etc. that may be required on horizontal risers, etc.

29
Headquarter & Factory
İstanbul Yolu 37. Km K.Kazan – ANKARA
Tel : +90 (312) 818 63 00 (pbx) - Fax : +90 (312) 818 61 50

Export Office
53. Cadde 1450. Sokak Ulusoy Plaza No:9 / 50 Çukurambar - ANKARA
Tel: +90 (312) 287 91 00 (pbx) - Fax : +90(312) 284 91 00

www.untes.com
export@untes.com.tr

UCUV-S_EN_01.10.2018_V2

You might also like