UCUV-S Series: Air Cooled Condensing Units
UCUV-S Series: Air Cooled Condensing Units
Contents Introduction
Introduction ....................................... 2 Selection Procedure ....................... 15
Legend.............................................. 2 Typical Wiring Diagram................... 12 UNTES UCUV-S series Air cooled
Nomenclature ................................... 2 Electrical Data ........................... 18-20 condensing unit are designed for the use on
General Features.............................. 3 Dimensional Data ...................... 20-23 systems with indoor units connected to remote
Component Features ........................ 3 Loading Points ........................... 23-24
condensing units located outside either on
Control Panel .................................... 4 Location & Space Requirements .... 25
Unit Controller................................... 5 Unit Installation ............................... 26 ground or on roof level.
Optional Features ............................. 5 Typical Refrigerant Piping............... 27
Engineering Specificatio ............ 7-10 Recommended Line Sizes......... 28-29 UNTES UCUV-S units are manufactured to
Capacity Ratings ....................... 11-14 Guide Specificatio ......................... 30
meet the requirements of the gulf severe
Capacity Control Steps ................... 15
climatic conditions.
3
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
UNTES UCUV-S series, all models, are restricted to a 14FPI Refrigerant Charge
(1.8mm) fin spacing condenser coil.
Gulf dust storms and the general level of available maintenance UCUV-S Air Cooled Condensing units are shipped
in Gulf countries ensures this condenser coil design shall provide with nitrogen holding charge only. Actual charging
long life and maintenance-free operation with the least with refrigerant R-134a should be done at site.
possibility of operational blockage on the condenser. Ample
condenser surface and sensible air flow across the condenser
ensures a low temperature differential between
condensing temperature and the high Gulf ambients making Piping connections
the UCUV-S condensing unit perform efficiently and durably.
UCUV-S Air Cooled Condensing units piping connections
Condenser Fans come, as standard, terminated with sealed and soldered
copper pipe ends.
Condenser fans are propeller type, aluminium alloy
blades, directly driven by electric motors. Normal installation would require the cutting off (using roller-type
tube cutters) of the ends prior to connections being resoldered
M o t o r s a r e To t a l l y E n c l o s e d A i r O v e r (TEAO) and connected to the field supplied refrigerant pipework
six pole with class ‘F’ insulation and minimum IP55
protection. Refrigerant Pipe work
The TEAO and class ‘F’ insulation features ensure long UNTES UCUV-S series Condensing units are provided
life and are unique for UNTES. with all internal piping, using ACR grade copper
tubing, between compressor and condenser.
The motors are factory wired, using wires specially selected for Loose supplied liquid line refrigerant controls are available as
high ambients operation, to unit control panel where the motor an option for field installation (Please specify CRSP). When
contactors are located to control the operation of these motors. ordered this option, the unit should be supplied with a correctly
sized thermostatic expansion valve, liquid line solenoid valve,
The condenser fans are individually statically and dynamically liquid line sight glass/moisture indicator and filter drier having
balanced at the factory. Complete fan assembly is provided with flared or soldered ends isolatable with one shut-o f valve.
suitable acrylic coated fan guard.
Shut-off valve for the other side of the filter drier can be supplied,
if option CXFV is specified
Casing/Structure
Designed for ease of handling and low cost to install. The
UCUV-S Air cooled condensing Units are factory assembled Control Panel
and mounted on a rigid base. The unit casing used in
UCUV-S condensing units is made of zinc coated The unit mounted control panel enclosure is fabricated out of heavy
galvanized steel sheets conforming to JIS-G3302 and gauge sheet steel in phosphatized powder coated baked finish.
ASTM A653 which is phosphatized then baked after an The enclosure conforms to IP54 as per guidelines in IEC 529.
electrostatic powder coat of approximately 60 microns.
A hinged access door and key-fastener is provided for easy access
This nisha ndc oating passa 1 000h oursi n5 % s alts prayt esting and security. The panel is factory wired in accordance with NEC
at 95°F (35°C) and 95% relative humidity as per ASTM B117. 430 & 440, labelled, tagged and features 220V / 240V controls.
The entire assembly comes complete with lifting holes on • All compressors are with DOL starting.
the base frame for rigging and installation. Acess panels are
• Individual compressor & condenser fan motor contactors.
provided for easy service and maintainance
• Motor protector circuit breaker for condenser fan motors.
Options available include hot dipped galvanized base frame
and structural members aluminium/stainless steel panels are • Voltage monitoring module for protection against under
available, on request, as option. voltage, over voltage, phase loss, phase reversal and
phase unbalance of the incoming voltage.
• •Control circuit breaker.
• •Control circuit on/off switch.
• •Microprocessor control boards.
• •Control Relays.
• •Power and control terminal blocks.
•
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
5
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
Rotalock Valves on compressors (RVC) Ammeter & Phase Selector switch (AMPI)
For additional facilitation of maintenance of unit. To indicate running AMPS on main incomer of the unit.
Condenser Fan with polyglycoat coating (PGF) Voltmeter & Selector Switch (VSS)
For incoming line voltage.
To provide protection against corrosion for condenser fans.
6
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
ENGINEERING SPECIFICATIONS - 50 HZ
Model UCUV 51008-S 51010-S 51013-S 52015-S 51016-S 52017-S 52019-S
BTUH 86000 110000 146000 168000 176000 190000 220000
Cooling Capacity (1)
W 25205 32239 42790 49238 51583 55686 64478
BTUH 74150 97100 129550 145550 156100 164200 190350
Cooling Capacity (2)
W 21732 28458 37969 42658 45750 48124 55788
Type - Hermetic Scroll Compressor
Quantity - 1 1 1 2 1 2 2
Compressor
Oil Charge per Circuit US Gal 0.86 0.86 1.23 0.86/0.86 1.80 0.86/0.86 0.86/0.86
(A/B/C/D) Liter 3.3 3.3 4.7 3.3/3.3 6.8 3.3/3.3 3.3/3.3
Type - Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 19.4 19.4 24.4 24.4 24.4 24.4 29.3
Face Area
m² 1.8 1.8 2.3 2.3 2.3 2.3 2.7
Type - Propeller direct drive 960 RPM
Code / Qty. - 628/2 628/2 723/2 723/2 723/2 723/2 823/2
Condenser Fan
cfm 9240 8920 13240 13240 13240 13240 17880
Air Flow Rate
l/s 4361 4210 6249 6249 6249 6249 8438
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 0.37/2 0.37/2 0.75/2 0.75/2 0.75/2 0.75/2 1.5/2
Refrigerant (R - 134a) Operating lbs 9.7 14.8 18.3 9.3/9.3 18.3 11.6/8.9 11.5/11.5
Charge per Circuit (A/B/C/D) (3) kg 4.4 6.7 8.3 4.2/4.2 8.3 5.3/4.1 5.2/5.2
Number of Refrigerant Circuits - 1 1 1 2 1 2 2
lbs 809 889 1142 1169 1142 1213 1319
Unit Operating Weight
kg 367 403 518 530 518 550 598
7
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
ENGINEERING SPECIFICATIONS - 50 HZ
Model UCUV 52053-S 52060-S 53064-S 53071-S 53079-S 53084-S
BTUH 625000 695000 750000 835000 920000 980000
Cooling Capacity (1)
W 183177 203693 219812 244725 269637 287222
BTUH 549900 614050 656350 733900 811650 862000
Cooling Capacity (2)
W 161166 179968 192365 215094 237881 252638
Type - Hermetic Scroll Compressor
Quantity - 4 4 6 6 6 6
Compressor
Oil Charge per Circuit US Gal 3.0/3.0 3.6/3.6 2.1/2.1/2.1 2.5/2.5/2.5 3.0/3.0/2.5 3.6/3.0/3.0
(A/B/C/D) Liter 11.5/11.5 13.6/13.6 7.9/7.9/7.9 9.3/9.3/9.3 11.5/11.5/9.3 13.6/11.5/11.5
Type - Air cooled 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 72.0 72.0 97.5 97.5 97.5 97.5
Face Area
m² 6.7 6.7 9.1 9.1 9.1 9.1
Type - Propeller direct drive 960 RPM
Code / Qty. - 829/4 829/4 823/6 823/6 829/6 829/6
Condenser Fan
cfm 42880 40920 54900 54900 59340 59340
Air Flow Rate
l/s 20237 19312 25910 25910 28005 28005
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 1.5/4 1.5/4 1.5/6 1.5/6 1.5/6 1.5/6
Refrigerant (R - 134a) Operating Charge per lbs 31.9/31.9 35.9/35.9 28.8/28.8/28.8 28.8/28.8/28.8 35.7/35.7/35.7 35.7/35.7/35.7
Circuit (A/B/C/D) (3) kg 14.5/14.5 16.3/16.3 13.1/13.1/13.1 13.1/13.1/13.1 16.2/16.2/16.2 16.2/16.2/16.2
Number of Refrigerant Circuits - 2 2 3 3 3 3
lbs 3585 3815 6139 6533 6727 6727
Unit Operating Weight
kg 1626 1730 2784 2963 3051 3051
8 8
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
ENGINEERING SPECIFICATIONS - 60 Hz
Model UCUV 61009-S 61011-S 61016-S 62018-S 61018-S 62020-S 62022-S
BTUH 102000 132000 174000 200000 210000 226000 262000
Cooling Capacity (1)
W 29894 38687 50996 58617 61547 66237 76788
BTUH 88500 117250 154950 173400 185550 196550 229150
Cooling Capacity (2)
W 25938 34364 45413 50821 54382 57606 67160
Type - Hermetic Scroll Compressor
Quantity - 1 1 1 2 1 2 2
Compressor
Oil Charge per Circuit US Gal 0.86 0.86 1.23 0.86/0.86 1.80 0.86/0.86 0.86/0.86
(A/B/C/D) 3.3 6.8 3.3/3.3 3.3/3.3
Liter 3.3 4.7 3.3/3.3
Type - Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 19.4 19.4 24.4 24.4 24.4 24.4 29.3
Face Area
m² 1.8 1.8 2.3 2.3 2.3 2.3 2.7
Type - Propeller direct drive 1150 RPM
Code / Qty. - 628/2 628/2 723/2 723/2 723/2 723/2 823/2
Condenser Fan
cfm 11200 10820 15660 15660 15660 15660 21760
Air Flow Rate
l/s 5286 5106 7391 7391 7391 7391 10270
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 0.55/2 0.55/2 1.1/2 1.1/2 1.1/2 1.1/2 2.2/2
Refrigerant (R - 134a) Operating lbs 9.7 14.8 18.3 9.3/9.3 18.3 11.6/8.9 11.5/11.5
Charge per Circuit (A/B/C/D) (3) kg 4.4 6.7 8.3 4.2/4.2 8.3 5.3/4.0 5.2/5.2
Number of Refrigerant Circuits - 1 1 1 2 1 2 2
lbs 816 895 1142 1169 1142 1213 1319
Unit Operating Weight
kg 370 406 518 530 518 550 598
9
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
ENGINEERING SPECIFICATIONS - 60 HZ
Model UCUV 62063-S 62071-S 63076-S 63085-S 63094-S 63100-S
BTUH 740000 825000 895000 990000 1095000 1165000
Cooling Capacity (1)
W 216882 241794 262309 290152 320926 341442
BTUH 654050 731700 787200 876100 969850 1027950
Cooling Capacity (2)
W 191691 214449 230715 256770 284247 301275
Type - Hermetic Scroll Compressor
Quantity - 4 4 6 6 6 6
Compressor
Oil Charge per Circuit US Gal 3.0/3.0 3.6/3.6 2.1/2.1/2.1 2.5/2.5/2.5 3.0/3.0/2.5 3.6/3.0/3.0
(A/B/C/D) Liter 11.5/11.5 13.6/13.6 7.9/7.9/7.9 9.3/9.3/9.3 11.5/11.5/9.3 13.6/11.5/11.5
Type - Air cooled 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins
Condenser Coil ft² 72.0 72.0 97.5 97.5 97.5 97.5
Face Area
m² 6.7 6.7 9.1 9.1 9.1 9.1
Type - Propeller direct drive 1150 RPM
Code / Qty. - 829/4 829/4 823/6 823/6 829/6 829/6
Condenser Fan
cfm 51760 49560 66840 66840 72000 72000
Air Flow Rate
l/s 24428 23390 31545 31545 33980 33980
Type - Totally enclosed, air over Class F insulation, 6-pole, IP-55
Condenser Motor
Size / Quantity kW 2.2/4 2.2/4 2.2/6 2.2/6 2.2/6 2.2/6
Refrigerant (R - 134a) Operating Charge per lbs 31.9/31.9 35.9/35.9 28.8/28.8/28.8 28.8/28.8/28.8 35.7/35.7/35.7 35.7/35.7/35.7
Circuit (A/B/C/D) (3) kg 14.5/14.5 16.3/16.3 13.1/13.1/13.1 13.1/13.1/13.1 16.2/16.2/16.2 16.2/16.2/16.2
Number of Refrigerant Circuits - 2 2 3 3 3 3
lbs 3625 3850 6139 6536 6787 6787
Unit Operating Weight
kg 1644 1746 2784 2964 3078 3078
10
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
CAPACITY RATINGS - 50 H Z
Condenser Entering Air Temperature
Model SST 95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)
UCUV Total Capacity PI* Total Capacity PI* Total Capacity PI* Total Capacity PI*
°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW
35 1.7 72.4 21.2 5.5 67.4 19.8 6.3 62.0 18.2 7.0 56.5 16.6 7.8
40 4.4 79.0 23.2 5.6 73.7 21.6 6.3 67.9 19.9 7.1 62.1 18.2 7.9
51008-S
45 7.2 85.9 25.2 5.7 80.2 23.5 6.4 74.0 21.7 7.2 68.0 19.9 7.9
50 10 93.1 27.3 5.8 86.9 25.5 6.5 80.4 23.6 7.2 74.1 21.7 7.8
35 1.7 93.1 27.3 7.4 86.7 25.4 8.3 79.5 23.3 9.3 72.3 21.2 10.3
40 4.4 102.1 29.9 7.5 95.4 28.0 8.5 87.9 25.8 9.5 80.6 23.6 10.4
51010-S
45 7.2 111.6 32.7 7.7 104.5 30.6 8.6 96.8 28.4 9.6 89.4 26.2 10.6
50 10 121.6 35.6 7.8 114.1 33.4 8.8 106.3 31.1 9.8 98.7 28.9 10.8
35 1.7 119.6 35.1 9.6 112.4 32.9 10.8 105.0 30.8 12.2 97.5 28.6 13.6
40 4.4 132.6 38.9 9.8 124.7 36.5 11.0 116.6 34.2 12.4 108.6 31.8 13.8
51013-S
45 7.2 146.5 42.9 10.1 137.9 40.4 11.4 129.1 37.8 12.7 120.4 35.3 14.1
50 10 161.4 47.3 10.4 152.0 44.6 11.7 142.5 41.8 13.1 133.1 39.0 14.4
35 1.7 142.8 41.9 11.3 132.7 38.9 12.8 121.8 35.7 14.4 111.0 32.5 15.9
40 4.4 155.8 45.7 11.5 144.9 42.5 13.0 133.3 39.1 14.5 122.1 35.8 16.0
52015-S
45 7.2 169.2 49.6 11.7 157.5 46.2 13.2 145.3 42.6 14.6 133.6 39.1 16.1
50 10 183.2 53.7 11.9 170.7 50.0 13.3 157.8 46.3 14.7 145.6 42.7 16.0
35 1.7 144.6 42.4 12.6 135.8 39.8 14.2 126.9 37.2 15.9 118.0 34.6 17.6
40 4.4 160.1 46.9 12.9 150.5 44.1 14.5 140.7 41.2 16.3 131.1 38.4 18.0
51016-S
45 7.2 176.7 51.8 13.3 166.1 48.7 14.9 155.4 45.6 16.7 144.9 42.5 18.3
50 10 194.2 56.9 13.7 182.9 53.6 15.4 171.5 50.3 17.1 160.3 47.0 18.7
35 1.7 160.3 47.0 13.7 148.4 43.5 15.4 135.7 39.8 17.1 123.7 36.2 18.8
40 4.4 175.2 51.3 14.0 162.6 47.6 15.7 149.5 43.8 17.4 137.2 40.2 19.1
52017-S
45 7.2 190.6 55.9 14.3 177.3 52.0 16.0 163.8 48.0 17.7 151.3 44.3 19.3
50 10 206.8 60.6 14.5 192.8 56.5 16.2 178.9 52.4 17.9 166.1 48.7 19.4
35 1.7 183.4 53.8 15.1 170.2 49.9 17.0 155.8 45.7 19.0 141.7 41.5 21.0
40 4.4 201.1 58.9 15.5 187.3 54.9 17.4 172.4 50.5 19.4 158.1 46.3 21.3
52019-S
45 7.2 219.6 64.4 15.8 205.0 60.1 17.8 189.8 55.6 19.7 175.5 51.4 21.6
50 10 239.0 70.0 16.2 223.8 65.6 18.1 208.3 61.1 20.2 193.7 56.8 22.0
35 1.7 206.5 60.5 17.9 192.5 56.4 20.1 177.9 52.1 22.6 163.7 48.0 24.8
40 4.4 227.4 66.7 18.4 212.5 62.3 20.7 197.1 57.8 23.1 182.3 53.4 25.3
52022-S
45 7.2 249.6 73.1 19.0 233.6 68.5 21.3 217.5 63.7 23.6 202.1 59.2 25.8
50 10 273.0 80.0 19.6 256.1 75.1 21.9 239.1 70.1 24.2 223.0 65.4 26.3
35 1.7 236.7 69.4 19.6 222.2 65.1 22.0 207.4 60.8 24.8 192.5 56.4 27.6
40 4.4 262.1 76.8 20.1 246.3 72.2 22.6 230.3 67.5 25.4 214.3 62.8 28.1
52025-S
45 7.2 289.4 84.8 20.7 272.2 79.8 23.3 254.7 74.7 26.1 237.5 69.6 28.7
50 10 318.6 93.4 21.4 299.8 87.9 24.0 280.9 82.3 26.8 262.3 76.9 29.3
35 1.7 261.3 76.6 22.6 245.3 71.9 25.5 229.0 67.1 28.6 212.7 62.4 31.7
40 4.4 289.3 84.8 23.2 271.7 79.6 26.2 254.0 74.4 29.3 236.4 69.3 32.3
52028-S
45 7.2 319.1 93.5 23.9 300.0 87.9 26.9 280.6 82.2 30.1 261.6 76.7 33.0
50 10 350.9 102.8 24.8 330.2 96.8 27.8 309.5 90.7 30.9 289.1 84.7 33.6
35 1.7 285.3 83.6 25.8 267.7 78.5 29.1 250.0 73.3 32.6 232.4 68.1 35.9
40 4.4 315.7 92.5 26.5 296.4 86.9 29.9 277.0 81.2 33.4 257.9 75.6 36.6
52030-S
45 7.2 348.0 102.0 27.3 326.8 95.8 30.8 305.6 89.6 34.2 284.9 83.5 37.3
50 10 382.1 112.0 28.3 359.6 105.4 31.7 337.0 98.8 35.1 314.9 92.3 38.0
35 1.7 361.8 106.1 31.0 334.9 98.1 34.8 306.1 89.7 38.8 278.6 81.6 42.7
40 4.4 396.5 116.2 31.9 368.2 107.9 35.7 338.7 99.3 39.6 311.0 91.2 43.3
52036-S
45 7.2 432.5 126.8 32.6 403.1 118.1 36.4 373.1 109.3 40.4 345.3 101.2 44.0
50 10 470.4 137.9 33.3 439.9 128.9 37.3 409.3 120.0 41.2 381.2 111.7 44.7
35 1.7 413.6 121.2 35.8 385.5 113.0 40.2 356.3 104.4 45.0 327.9 96.1 49.6
40 4.4 455.5 133.5 36.8 425.5 124.7 41.3 394.8 115.7 46.0 365.2 107.0 50.5
52043-S
45 7.2 499.8 146.5 37.8 467.9 137.1 42.4 435.6 127.7 47.1 404.7 118.6 51.4
50 10 546.8 160.3 39.0 512.9 150.3 43.7 479.0 140.4 48.3 446.7 130.9 52.5
Table 3
Notes :
* Power input mentioned in this page should not be used for cable or fuse selection. MC and MFA values given in the electrical data
pages (18 - 20) should be referred for the same.
Computer Print outs for matched ratings with UNTES Air Handling Units are
available.
11
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
CAPACITY RATINGS - 50 H Z
Condenser Entering Air Temperature
Model SST 95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)
UCUV Total Capacity PI* Total Capacity PI* Total Capacity PI* Total Capacity PI*
°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW
35 1.7 461.1 135.1 41.2 432.0 126.6 46.4 402.5 118.0 52.0 373.4 109.4 57.1
40 4.4 509.5 149.3 42.4 478.0 140.1 47.7 446.2 130.8 53.3 414.9 121.6 58.2
52048-S
45 7.2 561.3 164.5 44.0 527.0 154.5 49.3 492.7 144.4 54.7 459.0 134.5 59.5
50 10 616.5 180.7 45.6 579.3 169.8 51.0 542.3 158.9 56.3 506.2 148.4 60.9
35 1.7 512.8 150.3 46.9 480.6 140.9 52.9 448.1 131.3 59.2 416.1 122.0 65.0
40 4.4 566.7 166.1 48.3 531.7 155.8 54.4 496.5 145.5 60.7 462.0 135.4 66.2
52053-S
45 7.2 624.2 183.0 50.0 586.0 171.7 56.1 547.7 160.5 62.3 510.5 149.6 67.6
50 10 685.2 200.8 51.9 644.1 188.8 58.0 603.3 176.8 63.9 563.4 165.1 69.0
35 1.7 570.7 167.3 51.6 535.5 157.0 58.2 499.9 146.5 65.2 464.8 136.2 71.8
40 4.4 631.3 185.0 53.0 592.8 173.8 59.8 554.0 162.4 66.8 515.8 151.2 73.2
52060-S
45 7.2 695.9 204.0 54.7 653.6 191.6 61.5 611.2 179.2 68.5 569.9 167.0 74.6
50 10 764.2 224.0 56.6 719.1 210.8 63.5 674.1 197.6 70.2 629.8 184.6 76.0
35 1.7 621.1 182.1 53.5 579.1 169.7 60.2 535.2 156.9 67.4 492.5 144.3 74.3
40 4.4 684.1 200.5 55.0 639.2 187.4 61.8 593.1 173.8 68.9 548.6 160.8 75.6
53064-S
45 7.2 750.7 220.0 56.6 702.9 206.0 63.5 654.4 191.8 70.6 608.0 178.2 77.1
50 10 821.4 240.8 58.3 770.6 225.9 65.3 719.6 210.9 72.3 671.1 196.7 78.6
35 1.7 686.1 201.1 62.7 642.4 188.3 70.6 598.3 175.4 79.0 554.9 162.6 86.5
40 4.4 757.7 222.1 64.7 710.4 208.2 72.7 663.0 194.3 80.9 616.4 180.7 88.2
53071-S
45 7.2 834.2 244.5 67.1 782.9 229.5 75.2 731.7 214.4 83.2 681.6 199.8 90.2
50 10 915.6 268.3 69.8 860.0 252.1 77.8 804.8 235.9 85.6 751.4 220.2 92.3
35 1.7 754.0 221.0 65.7 707.3 207.3 74.0 659.9 193.4 83.1 612.9 179.6 91.8
40 4.4 834.2 244.5 67.5 783.4 229.6 76.0 732.0 214.5 85.1 681.2 199.7 93.6
53079-S
45 7.2 920.1 269.7 69.7 864.5 253.4 78.4 808.6 237.0 87.4 753.7 220.9 95.6
50 10 1011.3 296.4 72.1 951.3 278.8 80.9 891.3 261.2 89.7 832.4 244.0 97.6
35 1.7 801.8 235.0 72.0 752.1 220.4 81.2 701.8 205.7 91.1 652.0 191.1 100.3
40 4.4 886.8 259.9 74.1 832.5 244.0 83.5 777.8 228.0 93.3 724.0 212.2 102.2
53084-S
45 7.2 977.5 286.5 76.5 918.0 269.1 86.1 858.4 251.6 95.7 800.2 234.5 104.3
50 10 1073.5 314.6 79.3 1009.8 296.0 88.8 946.2 277.3 98.2 883.8 259.1 106.4
35 1.7 825.4 241.9 75.3 774.1 226.9 84.9 722.4 211.7 95.1 671.3 196.8 104.6
40 4.4 912.7 267.5 77.5 856.7 251.1 87.3 800.4 234.6 97.5 745.0 218.4 106.6
53086-S
45 7.2 1005.7 294.8 80.1 944.3 276.8 90.0 882.9 258.8 100.0 823.0 241.2 108.7
50 10 1104.1 323.6 82.9 1038.5 304.4 92.9 973.2 285.2 102.5 909.1 266.5 110.8
35 1.7 922.9 270.5 82.2 864.6 253.4 92.6 805.6 236.1 103.8 747.4 219.1 114.2
40 4.4 1019.8 298.9 84.7 956.7 280.4 95.3 893.2 261.8 106.4 830.6 243.4 116.4
54095-S
45 7.2 1123.6 329.3 87.8 1055.0 309.2 98.5 986.3 289.1 109.3 918.9 269.3 119.0
50 10 1234.1 361.7 91.1 1159.7 339.9 101.8 1085.6 318.2 112.4 1013.5 297.1 121.7
35 1.7 1013.4 297.0 88.6 950.6 278.6 99.9 886.9 260.0 112.2 823.8 241.5 123.8
40 4.4 1121.2 328.6 91.1 1052.8 308.6 102.6 983.7 288.3 114.9 915.5 268.3 126.2
54106-S
45 7.2 1236.4 362.4 94.0 1161.7 340.5 105.8 1086.6 318.5 117.9 1012.7 296.8 128.9
50 10 1358.8 398.3 97.4 1278.3 374.7 109.1 1197.6 351.0 121.0 1118.5 327.8 131.6
35 1.7 1061.2 311.0 95.0 995.4 291.7 107.1 928.8 272.2 120.1 862.9 252.9 132.3
40 4.4 1173.8 344.0 97.7 1101.9 323.0 110.1 1029.5 301.8 123.0 958.3 280.9 134.9
54111-S
45 7.2 1293.8 379.2 100.9 1215.2 356.2 113.5 1136.4 333.1 126.2 1059.2 310.5 137.6
50 10 1421.1 416.5 104.5 1336.7 391.8 117.1 1252.5 367.1 129.5 1170.0 342.9 140.3
35 1.7 1131.7 331.7 104.8 1061.3 311.1 118.3 990.4 290.3 132.3 920.5 269.8 145.2
40 4.4 1251.2 366.7 108.0 1174.2 344.1 121.6 1096.9 321.5 135.6 1021.2 299.3 148.0
54118-S
45 7.2 1378.1 403.9 111.6 1293.7 379.2 125.3 1209.4 354.5 139.0 1127.6 330.5 150.9
50 10 1512.4 443.3 115.6 1422.5 416.9 129.3 1333.1 390.7 142.5 1245.3 365.0 153.6
Table 3 ends
Notes :
* Power input mentioned in this page should not be used for cable or fuse selection. MC and MFA values given in the electrical data
pages (18 - 20) should be referred for the same.
Computer Print outs for matched ratings with UNTES Air Handling Units are
available.
12
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
CAPACITY RATINGS - 60 H Z
Condenser Entering Air Temperature
Model SST 95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)
UCUV Total Capacity PI* Total Capacity PI* Total Capacity PI* Total Capacity PI*
°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW
35 1.7 86.2 25.3 6.9 79.6 23.3 7.7 72.8 21.3 8.6 66.0 19.3 9.5
40 4.4 94.4 27.7 7.0 87.7 25.7 7.9 80.6 23.6 8.8 73.7 21.6 9.7
61009-S
45 7.2 102.3 30.0 7.2 95.6 28.0 8.1 88.5 25.9 9.0 81.8 24.0 9.9
50 10 109.7 32.2 7.4 103.2 30.3 8.3 96.4 28.3 9.2 90.0 26.4 10.0
35 1.7 111.7 32.7 9.3 104.5 30.6 10.4 96.6 28.3 11.5 88.8 26.0 12.7
40 4.4 122.4 35.9 9.5 114.7 33.6 10.6 106.5 31.2 11.8 98.6 28.9 12.9
61011-S
45 7.2 133.7 39.2 9.8 125.6 36.8 10.9 117.0 34.3 12.0 108.8 31.9 13.1
50 10 145.5 42.6 10.1 136.9 40.1 11.2 128.0 37.5 12.3 119.6 35.1 13.4
35 1.7 142.8 41.9 12.2 134.4 39.4 13.6 125.9 36.9 15.2 117.4 34.4 16.8
40 4.4 158.1 46.3 12.5 148.9 43.6 14.0 139.6 40.9 15.6 130.4 38.2 17.2
61016-S
45 7.2 174.5 51.1 12.9 164.5 48.2 14.4 154.4 45.3 16.0 144.4 42.3 17.5
50 10 192.0 56.3 13.3 181.2 53.1 14.8 170.3 49.9 16.4 159.5 46.8 17.9
35 1.7 169.2 49.6 14.1 156.0 45.7 15.8 142.5 41.8 17.6 129.1 37.8 19.3
40 4.4 185.3 54.3 14.5 171.7 50.3 16.3 157.7 46.2 18.1 144.3 42.3 19.8
62018-S
45 7.2 201.0 58.9 14.9 187.3 54.9 16.7 173.3 50.8 18.5 160.3 47.0 20.2
50 10 215.7 63.2 15.3 202.4 59.3 17.1 189.1 55.4 18.9 176.9 51.8 20.5
35 1.7 171.9 50.4 15.9 161.7 47.4 17.8 151.5 44.4 19.8 141.3 41.4 21.7
40 4.4 190.2 55.7 16.3 178.9 52.4 18.3 167.7 49.1 20.3 156.5 45.9 22.2
61018-S
45 7.2 209.6 61.4 16.9 197.2 57.8 18.9 184.7 54.1 20.9 172.6 50.6 22.6
50 10 230.2 67.5 17.5 216.8 63.5 19.5 203.4 59.6 21.4 190.4 55.8 23.1
35 1.7 190.4 55.8 17.2 176.2 51.6 19.2 161.7 47.4 21.2 147.9 43.3 23.1
40 4.4 208.3 61.0 17.7 193.5 56.7 19.7 178.6 52.4 21.7 164.8 48.3 23.6
62020-S
45 7.2 226.5 66.4 18.2 211.3 61.9 20.3 196.3 57.5 22.3 182.7 53.5 24.0
50 10 244.8 71.8 18.8 229.5 67.3 20.8 214.5 62.9 22.8 201.5 59.0 24.4
35 1.7 219.5 64.3 19.1 204.6 60.0 21.4 188.9 55.4 23.7 173.8 50.9 26.0
40 4.4 240.3 70.4 19.7 224.6 65.8 21.9 208.3 61.1 24.2 193.0 56.6 26.4
62022-S
45 7.2 262.1 76.8 20.3 245.6 72.0 22.5 228.7 67.0 24.8 213.1 62.5 26.8
50 10 284.9 83.5 20.9 267.5 78.4 23.1 250.0 73.3 25.4 234.2 68.6 27.3
35 1.7 246.5 72.3 22.7 230.6 67.6 25.4 214.3 62.8 28.2 198.6 58.2 30.8
40 4.4 271.1 79.5 23.5 254.1 74.5 26.1 236.9 69.4 28.8 220.4 64.6 31.3
62026-S
45 7.2 297.2 87.1 24.2 279.0 81.8 26.9 260.8 76.4 29.6 243.6 71.4 31.9
50 10 324.7 95.2 25.0 305.3 89.5 27.7 286.1 83.9 30.4 268.3 78.6 32.6
35 1.7 282.4 82.8 24.9 265.6 77.8 27.9 248.6 72.9 31.1 231.7 67.9 34.2
40 4.4 312.4 91.6 25.6 294.1 86.2 28.6 275.6 80.8 31.8 257.2 75.4 34.9
62030-S
45 7.2 344.5 101.0 26.4 324.6 95.1 29.5 304.5 89.3 32.7 284.7 83.5 35.6
50 10 378.7 111.0 27.2 357.1 104.7 30.4 335.5 98.3 33.5 314.2 92.1 36.4
35 1.7 311.1 91.2 28.7 292.5 85.7 32.1 273.8 80.3 35.7 255.3 74.8 39.1
40 4.4 344.0 100.8 29.5 323.7 94.9 33.0 303.2 88.9 36.6 283.0 82.9 39.9
62033-S
45 7.2 379.1 111.1 30.5 356.8 104.6 34.0 334.4 98.0 37.6 312.5 91.6 40.8
50 10 416.3 122.0 31.6 392.1 114.9 35.1 368.1 107.9 38.6 344.7 101.0 41.7
35 1.7 339.1 99.4 32.6 318.7 93.4 36.5 298.3 87.4 40.5 278.1 81.5 44.2
40 4.4 374.7 109.8 33.6 352.3 103.2 37.6 329.9 96.7 41.6 307.9 90.2 45.1
62036-S
45 7.2 412.4 120.9 34.8 387.7 113.6 38.8 363.0 106.4 42.7 339.3 99.4 46.1
50 10 452.3 132.6 36.2 425.7 124.8 40.1 399.4 117.1 43.9 374.0 109.6 47.0
35 1.7 432.4 126.7 39.3 402.1 117.9 43.8 370.9 108.7 48.5 341.7 100.1 52.8
40 4.4 472.9 138.6 40.5 441.2 129.3 44.9 409.1 119.9 49.5 379.5 111.2 53.7
62043-S
45 7.2 515.6 151.1 41.7 482.3 141.4 46.2 449.2 131.7 50.6 419.3 122.9 54.6
50 10 559.9 164.1 43.0 525.0 153.9 47.5 491.0 143.9 51.9 461.0 135.1 55.5
35 1.7 493.8 144.7 45.4 461.9 135.4 50.7 429.3 125.8 56.2 397.9 116.6 61.4
40 4.4 543.1 159.2 46.8 509.0 149.2 52.1 474.6 139.1 57.6 441.6 129.4 62.6
62051-S
45 7.2 595.4 174.5 48.3 558.9 163.8 53.7 522.5 153.1 59.0 488.0 143.0 63.8
50 10 650.5 190.7 49.9 611.6 179.3 55.3 573.2 168.0 60.6 537.4 157.5 65.0
Notes : Table 4
* Power input mentioned in this page should not be used for cable or fuse selection. MC and MFA values given in the electrical data
pages ( 18-20 ) should be referred for the same.
Computer Print outs for matched ratings with UNTES Air Handling Units are
available.
13
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
CAPACITY RATINGS - 60 Hz
Condenser Entering Air Temperature
Model SST 95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)
UCUV Total Capacity PI* Total Capacity PI* Total Capacity PI* Total Capacity PI*
°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW
35 1.7 549.9 161.2 52.3 516.3 151.3 58.5 482.7 141.5 64.9 449.4 131.7 70.8
40 4.4 607.1 177.9 54.1 570.6 167.2 60.3 534.1 156.5 66.6 498.1 146.0 72.2
62058-S
45 7.2 668.1 195.8 55.9 628.5 184.2 62.2 589.1 172.7 68.4 550.6 161.4 73.8
50 10 732.8 214.8 58.0 690.1 202.3 64.3 647.7 189.8 70.3 606.7 177.8 75.3
35 1.7 609.5 178.6 59.6 572.4 167.8 66.6 535.3 156.9 73.8 498.6 146.1 80.2
40 4.4 672.8 197.2 61.6 632.3 185.3 68.7 591.8 173.4 75.8 552.1 161.8 81.9
62063-S
45 7.2 740.1 216.9 63.8 695.6 203.9 71.0 651.6 191.0 77.8 609.0 178.5 83.6
50 10 811.2 237.8 66.3 763.4 223.8 73.4 716.3 209.9 80.0 670.9 196.6 85.4
35 1.7 680.0 199.3 64.9 639.3 187.4 72.6 598.4 175.4 80.7 557.9 163.5 88.0
40 4.4 751.5 220.3 66.9 706.7 207.1 74.8 661.8 194.0 82.8 617.7 181.1 89.9
62071-S
45 7.2 827.4 242.5 69.2 777.9 228.0 77.2 728.5 213.5 85.1 680.9 199.6 91.8
50 10 907.7 266.0 71.9 854.4 250.4 79.8 801.6 234.9 87.4 750.6 220.0 93.8
35 1.7 741.7 217.4 67.9 693.9 203.4 75.8 645.1 189.1 84.2 597.8 175.2 92.0
40 4.4 815.9 239.1 70.0 764.7 224.1 78.0 713.0 209.0 86.2 663.4 194.4 93.7
63076-S
45 7.2 894.6 262.2 72.2 839.9 246.2 80.3 785.1 230.1 88.3 733.3 214.9 95.5
50 10 977.5 286.5 74.6 919.1 269.4 82.7 861.4 252.5 90.7 807.5 236.7 97.4
35 1.7 817.1 239.5 79.9 766.8 224.8 89.2 716.5 210.0 98.7 666.9 195.5 107.3
40 4.4 901.4 264.2 82.6 846.9 248.2 92.0 792.4 232.3 101.3 738.9 216.6 109.5
63085-S
45 7.2 991.3 290.6 85.6 932.2 273.2 95.1 873.5 256.0 104.2 816.3 239.3 111.9
50 10 1086.6 318.5 88.8 1022.8 299.8 98.3 959.8 281.3 107.1 899.2 263.6 114.1
35 1.7 899.6 263.7 83.1 845.6 247.9 93.0 791.3 231.9 103.4 737.4 216.1 113.3
40 4.4 994.4 291.5 85.6 935.4 274.2 95.7 876.1 256.8 106.1 817.6 239.6 115.6
63094-S
45 7.2 1095.6 321.1 88.4 1031.0 302.2 98.7 966.4 283.3 109.0 903.2 264.7 118.1
50 10 1202.8 352.6 91.6 1133.1 332.1 101.9 1063.6 311.7 112.0 996.1 291.9 120.6
35 1.7 955.5 280.1 91.0 898.0 263.2 101.8 840.4 246.3 113.0 783.2 229.5 123.3
40 4.4 1055.7 309.4 93.8 992.7 291.0 104.9 929.5 272.4 116.0 867.5 254.3 126.0
63100-S
45 7.2 1162.3 340.7 97.1 1093.0 320.4 108.2 1023.9 300.1 119.2 956.9 280.5 128.6
50 10 1275.1 373.7 100.8 1200.4 351.8 111.8 1126.4 330.1 122.4 1054.8 309.2 131.4
35 1.7 983.1 288.1 95.0 923.8 270.8 106.3 864.5 253.4 117.9 805.6 236.1 128.4
40 4.4 1085.9 318.3 98.1 1020.8 299.2 109.5 955.8 280.1 121.0 892.0 261.4 131.2
63102-S
45 7.2 1195.1 350.3 101.5 1123.3 329.2 113.1 1052.0 308.3 124.3 983.3 288.2 133.9
50 10 1310.5 384.1 105.5 1233.3 361.5 116.9 1157.1 339.1 127.8 1083.6 317.6 136.8
35 1.7 1098.3 321.9 104.9 1031.2 302.3 117.3 963.9 282.5 130.1 897.4 263.0 141.8
40 4.4 1212.4 355.4 108.4 1139.5 334.0 120.9 1066.5 312.6 133.5 994.7 291.5 144.7
64113-S
45 7.2 1334.1 391.0 112.2 1255.1 367.9 124.8 1176.3 344.8 137.2 1099.3 322.2 147.8
50 10 1463.3 428.9 116.3 1377.8 403.8 129.0 1293.2 379.0 141.0 1211.4 355.0 150.8
35 1.7 1208.9 354.3 112.0 1136.3 333.1 125.4 1063.4 311.7 139.5 990.9 290.4 152.7
40 4.4 1336.2 391.6 115.5 1256.9 368.4 129.1 1177.2 345.0 143.1 1098.5 322.0 155.9
64126-S
45 7.2 1472.0 431.4 119.3 1385.2 406.0 133.1 1298.3 380.5 147.0 1213.4 355.6 159.2
50 10 1616.0 473.6 123.6 1522.2 446.1 137.5 1428.8 418.8 151.0 1338.0 392.2 162.6
35 1.7 1264.8 370.7 119.9 1188.7 348.4 134.2 1112.4 326.0 149.1 1036.7 303.8 162.8
40 4.4 1397.5 409.6 123.7 1314.1 385.2 138.3 1230.6 360.7 153.0 1148.4 336.6 166.2
64132-S
45 7.2 1538.8 451.0 128.0 1447.1 424.1 142.7 1355.7 397.4 157.2 1267.0 371.4 169.7
50 10 1688.3 494.8 132.8 1589.5 465.9 147.4 1491.5 437.2 161.5 1396.7 409.4 173.3
35 1.7 1347.1 394.8 132.1 1265.9 371.0 147.8 1184.5 347.2 163.7 1103.8 323.5 178.0
40 4.4 1487.6 436.0 136.5 1398.2 409.8 152.4 1308.9 383.6 168.2 1221.6 358.1 181.9
64140-S
45 7.2 1636.4 479.6 141.4 1537.6 450.7 157.4 1439.7 422.0 172.7 1345.8 394.4 185.6
50 10 1793.8 525.8 147.1 1687.7 494.7 162.8 1583.1 464.0 177.5 1482.7 434.6 189.6
Table 4 ends
Notes :
* Power input mentioned in this page should not be used for cable or fuse selection. MC and MFA values given in the electrical data
pages ( 18-20) should be referred for the same.
Computer Print outs for matched ratings with UNTES Air Handling Units are
available.
1). Cooling capacity at 95°F (35°C) ambient temperature according to AHRI-365.
2). Cooling capacity at Gulf conditions : 115°F (46.1°C) condenser entering air temperature & 45°F (7.2°C) SST.
3). Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil.
4). Condensing units are shipped with nitrogen holding charge only.
14
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
Example
Altitude Correction Factors
The following information should be determined:
1. Required total capacity = 455 MBh (126 kW) The unit ratings are based on sea level. Above sea level
2. Saturated suction temperature = 50°F (10°C) apply the following correction factors:
3. Condenser entering air temperature = 115°F (46°C)
4. Power Supply (V/PH/Hz) = 380/3/50 Altitude Capacity Power
feet meter Multiplier Multiplier
Enter capacity ratings from Table 3 at 115°F (46°C) 0 0 1 1
condenser entering air temperature and select model
2000 610 0.99 1.01
UCUV 52043-S having a cooling capacity of 479MBh (140.4 kW)
at 50°F (10°C) saturated suction temperature, compressor 4000 1219 0.98 1.02
motor power input is 48.3 kW. For further details refer to 6000 1829 0.97 1.03
physical data and specifications sheets.Capacity ratings are 8000 2438 0.96 1.04
based on sea level operation. Above sea level, apply the 10000 3048 0.95 1.05
following corrections method. Table 6
15
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
Field Connections
UCUV-S series self-contained heavy duty air cooled condensing units are designed for minimum field interaction.
Power hook-ups for AHU starter and fan interlock and control wiring of room unit as per Electrical hook-up diagram is all that is
required to electrically connect any model of UCUV-S series .
Every UCUV-S series condensing unit requires, at most, field installed fused disconnect switches or circuit breakers, and room unit.
Refer below for a schematic representation of required field electrical hook-ups for a standard UCUV-S series condensing unit.
All field wiring must be done in accordance with applicable local and national codes.
For maximum recommended fuse sizes and minimum circuit amps for cable sizing, see Page 18 - 20 of this bulletin.
3 PHASE,
3 WIRE SYSTEM
440V/3PH/50HZ CIRCUIT BREAKER
220V/3PH/60HZ OR FUSED CIRCUIT BREAKER
460V/3PH/60HZ DISCONNECT SWITCH OR FUSED
(NOT BY UNTES) DISCONNECT SWITCH
(NOT BY UNTES)
3 PHASE,
4 WIRE SYSTEM
380-415V/3PH/50HZ
L1
L2
380V/3PH/60HZ
L3
N
GROUND 3 PHASE,
4 WIRE SYSTEM
E
380-415V/3PH/50HZ
L1 380V/3PH/60HZ
L2
CUSTOMER SUPPLIED
EFM STARTER INTERLOCK TO AHU AND INSTALLED
AHU STARTER BOX
(BY OTHERS) FIELD ACCESSORY
(CONTACTOR, OVERLOAD
RELAY & ON/OFF CONTROL etc.)
DOL/STAR DELTA
FAN INTERLOCK FROM AHU
ROOM UNIT
(LOOSESUPPLY) U
V M
W 3~
+ -
E
CE+ CE-
CE-
2 CORE UNSCREENED TWISTED PAIR CABLE
AS PER KNX SPECIFICATION (BY OTHERS) LINE VOLTAGE
FIELD WIRING
AU MR
ACUV-S A-SERIES
SERIES
CONTROL PANEL LOW VOLTAGE
FIELD WIRING
REFER ACTUAL WIRING DIAGRAM
FURNISHED WITH THE UNIT FOR
EXACT IDENTIFICATION OF WIRE NUMBERS.
**AAUMR
CUV - S ASERIES
SERIES UNITS RATED FOR 440V/3PH/50HZ, 460V/3PH/60HZ, OR POWER SUPPLIES WITH OUT NEUTRAL
REQUIRE SEPARATE SOURCE OF CONTROL POWER SUPPLY THRU FIELD SUPPLIED & INSTALLED 15A/220V FUSED
CONTROL DISCONNECT SWITCH OR ORDER WITH FACTORY BUILT IN OPTION ' CXT '.
16
17
**L1
POWERSUPPLY
L2
L3
N
F
C1 C2
MPM1 * MPM2 I> I> I> I> I> I> I> I> I> I> I> I>
L2 L2
L1 L3
* L1 L3
T2 T1 M1 M2 S1 S2 T2 T1 M1 M2 S1 S2 C3 C4 C5 C6 VMM
CM1 CM2
A BC
NC Com NO
MCB1 CFM1 CFM2 CFM3 CFM4 PROVIDE OVERCURRENT, EARTH FAULT PROTECTION, SHORT CIRCUITAND
** DISCONNECT MEANS AS REQUIRED BYLOCAL & NATIONAL ELECTRIC CODE.
CR1 CR2
LPS-1
LPS-2
TWISTED PAIR CABLE
AS PER KNXSPECIFICATON
RUN/STOP
(BY OTHERS)
FAN INTERLOCK
L E GEN D
DISC. PRESSURE-1
DISC. PRESSURE-2
MCB2
TFR TRANSFORMER VMM VOLTAGEMONITORINGMODULE
CS CONTROL SWITCH MPM MOTOR PROTECTOR MODULE
C CONTACTOR MPCB MOTOR PROTECTORCIRCUT BREAKER
CCH CRANK CASE HEATER OL OVERLOADRELAY
MCB MINIATURECIRCUITBREAKER LSV LIQUID LINESOLENOID VALVE
CFM CONDENSERFANMOTOR EFM EVAPORATOR FANMOTOR
CM COMPRESSORMOTOR CR CONTROL RELAY
24~_ RS485 PB LPS LOW PRESSURESWITCH
FIELD WIRING
HPS HIGH PRESSURESWITCH
B-
M
M
M
M
M
M
M
X1
X2
X3
X4
X5
X6
X7
X8
B1
B2
B3
A+
D1
D2
DG
CE-
REF
CE+
5V=
5V=
DU1
DU2
T1
T2
T3
T4
T5
T6
T7
24V=
24V=
MATCHING AHU FOR
CR5
INFO
EFMSTARTER
MICROPROCESSSOR
OK INTERLOCK
TFR
CONTROLLER
24V
220~ 240V
ESC
C1 C2 CR3 CR4
T8
T9
24~_
G0
Q12
Q11
Q14
Q22
Q21
Q24
Q33
Q34
Q43
Q44
Q53
Q54
Q64
Q73
Q74
Q84
C
D01
D02
DL1
DN
DL2
T10
T11
T12
T13
T-IP
T-HI
LSV-1 LSV-2
CCH1
CCH2
(BY OTHERS)
HPS-1
HPS-2
FAN INTERLOCK
COMP.-1
LSV-1
COMP.-2
LSV-2
CFM1
CFM2
CFM3
CFM4
EFM
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
Table 7
54111-S 500 376 620 5+3 44 + 38 272 + 225 8 3.9 17.2
54118-S 500 394 638 8 44 272 8 3.9 17.2
18
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
Table 9
64132-S 630 462 770 5+3 56 + 42 353 + 280 8 5.3 17.5
64140-S 630 504 812 8 56 353 8 5.3 17.5
19
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
MFA Maximum Fuse Amps (for fuse/circuit breaker sizing), PWS Part Winding Start.
omplies with NEC Article 440-22 & 430-52. RLA Rated Load Amps. (at worst operating condition) .
MCA Minimum Circuit Amps.(for wire3 sizing), complies with
NEC article 440-33. LRA Locked Rotor Amps.
ICF Maximum Instantaneous Current Flow. FLA Full Load Amps.
DOL Direct On-Line Start .
Note :
Voltage imbalance not to exceed ± 2 % of the rated voltage.
Dimensional Data 10 10
[254] A3 [254]
UCUV Models: 51008S-51010S & 61009S-61011S A1
LEGEND
1 CO NDENSER FAN
2 CO NDENSER COIL
3 CO NTRO L PANEL
4 CO MPRESSOR
A2 A4
LINE SIZES ARE BASED ON 100f EQUIVALENT LENGTH
ALL DIMENSIONS ARE IN INCHES [m m]
68
45
[1727] 1
3 [1143]
LIQ.Ø
51.65
MODEL CONNECTØIONSIZE,
UCUV- SUC. LIQ. DETACHABLE
[305]
PLATE FOR
51008S 1 5/8 5/8
12
CABLE ENTRY
61009S [41] [16]
ACCESS
51010S 1 5/8 7/8
[178]
[100]
3.94
Dimens
Dimensional Data
UCUV Models: 51013S-52022S & 61016S-62026S
6S 10 10
[254] A3 [254]
CONNECTION SIZE, Ø A1
DIMENSIONS ONNECTION SIZE, Ø
MODEL CIRCUIT-2
CIRCUIT-1 UIT-1 CIRCUIT-2
UCUV- L W H A B
SUC.#1 LIQ.#1 SUC.#2 LIQ.#2 LIQ.#1 SUC.#2 LIQ.#2
7/8
*61016S
51013S 56
[1422]
74
[1880]
51.65
[1312]
12.72
[323] - 2 1/8 7/ 8
[54] [22] - - [22] - -
5/8 1 5/8 5/8
52015S 56 74 51.65 12 12 1 5/8 5/8 1 5/8 5/8 [16] [41] [16]
62018S [1422] [1880] [1312] [305] [305] [41] [16] [41] [16] 7/ 8 - -
*51016S
61018S
56
[1422]
76
[1930]
51.65
[1312]
12.72
[323] - 2 1/8 7/8
[54] [22] - -
[22]
7/8 1 5/8 5/8
1 5/8 7/8 1 5/8 5/8 [22] [41] [16]
52017S 56 76 51.65 12 12
62020S [1422] [1930] [1312] [305] [305] [41] [22] [41] [16] 7/8 1 5/8 7/8
[22] [41] [22]
52019S 56 84 59.65 12 12 1 5/8 7/ 8 1 5/8 7/ 8 7/8 1 5/8 7/8 A4
62022S [1422] [2134] [1515] [305] [305] [41] [22] [41] [22] A2
[22] [41] [22]
52022S 58 84 59.65 12.72 12 2 1/8 7/ 8 1 5/8 7/8
62026S [1473] [2134] [1515] [323] [305] [54] [22] [41] [22]
SSOR MODEL
* MODEL WITH ONE COMPRESSOR
DIM.12" INSTEAD OF 10" & 4" F OR O N E C O M P R ES SOR MODEL W
ALL DIMENSIONS ARE IN INCHES [mm ]
L
L
SUCTION #2
3 1 SUCTION #1
LIQUID #2
LIQUID #1
RIGGING HOLES
Ø0.79 [20] 4 Nos.
VENTILATION 2
ON BOTH SIDES
A
B
H
*
[100]
ACCESS 4
3.94
4*
[178]
[178]
DETACHABLE
7
7
PLATE FO R [101]
CABLE ENTRY [101]
A
10 * 10 *
[254] [254]
4
76 88
[1930] [2235]
1
3
2 SUCTION#1 SUCTION #2
VENTILATION
ON BOTH SIDES LIQUID#1 LIQUID #2
H
[125]
4.92
DETACHABLE
PLATE FOR
A
CABLE ENTRY
4 4 ACCESS 4
[203]
[203]
[102] [102]
8
10 10
[254] [254]
21
21
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
Dimensional Data
UCUV Models: 52043S-52060S & 62051S-62071S
10 10
[254] [254]
A1 A3
DIMENSIONS CONNECTION SIZE,Ø
MODEL CIRCUIT-1 CIRCUIT-2
UCUV- H
SUC.#1 LIQ.#1 SUC.#2 LIQ.#2
52043S 77.63 2 5/8 1 1/8 2 5/8 1 1/8 LEGEND
62051S [1972] [67] [29] [67] [29]
1 CONDENSER FAN
52048S 85.63 2 5/8 1 1/8 2 5/8 1 1/8
62058S [2175] [67] [29] [67] [29] 2 CONDENSER COIL
52053S 85.63 2 5/8 1 1/8 2 5/8 1 1/8 3 CONTROL PANEL
62063S [2175] [67] [29] [67] [29] 4 TANDEM COMPRESSOR
52060S 85.63 2 5/8 1 1/8 2 5/8 1 1/8
62071S [2175] [67] [29] [67] [29]
LINE SIZES ARE BASED ON 100f tEQUIVALENT LENGTH
ALL DIMENSIONS ARE IN INCHES[mm]
A2 A4
84 88
[2134] [2235]
1
2
FILTERED SUCTION #1 SUCTION #2
VENTILATION
ON BOTH SIDES
H
LIQUID #1 LIQUID #2
DETACHABLE
[125]
4.92
PLATE FOR
[693]
[693]
27.29
27.29
CABLE ENTRY
ACCESS
4
[203]
[203]
8
8
RIGGING HOLES 4 4
Ø.79[20]4 Nos.
[102] [102]
10 10
[254] [254]
LEGEND
CIRCUIT-1
1 CONDENSER FAN CIRCUIT-2
2 CONDENSER COIL CIRCUIT-3
3 CONTROL PANEL
4 TANDEM COMPRESSOR
FILTERED
VENTILATION
ON BOTH SIDES
LIQUID Ø
1 1/8[29]x 4Nos.
105.91
[2690]
[2420]
95.28
DETACHABLE
PLATE FOR
CABLE ENTRY
[750]
29.5
4
[125]
22
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
Dimensional Data
UCUV Models: 54095S- 54118S & 64140S
10 20 10
[254] [508] [254]
A1 A3 A5 A7
LEGEND
1 CONDENSER FAN CIRCUIT-1
CIRCUIT-2
2 CONDENSER COIL
CIRCUIT-3
3 CONTROL PANEL CIRCUIT-4
4 TANDEM COMPRESSOR
FILTERED
LIQUID Ø VENTILATION
1 1/8[29]x 4Nos. ON BOTH SIDES
106.91
[2715]
[2420]
95.28
DETACHABLE
PLATE FOR
CABLE ENTRY
[750]
29.5
4
SUCTION Ø RIGGING HOLES
[150]
5.91
23
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
24
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
*
A
B
A
A
*
A
B
B
*
A
A
*
C
C
A
B
*
A
UCUV-51008S to 52060S
UCUV-61009S to 62071S
UCUV-53064S to 54118S
UCUV-63076S to 64140S
26
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
Legend 2
3
AIR
1. Expansion Valve 4
FLOW
5
2. Sight Glass AHU
3. Solenoid Valve
4. Filter Drier
5. Shut Off Valve
CONDENSING
UNIT
6
6. Liquid Line
7. Suction Line
1
2 7
7
3
AHU CONDENSING
similar. UNIT
DOTTED IN CASE OF
LEGEND
DOUBLE SUCTION RISER
1 EXPANSION VALVE
2 SIGHT GLASS
3 SOLENOID VALVE
4 FILTER DRIER
5 SHUT OFF VALVE
6 LIQUID LINE
7 SUCTION LINE
Refrigerant Piping
Correct design and size of refrigerant piping is necessary c. Pressure drop due to vertical lift of liquid line for R-134a 1°F
for proper operation. The refrigerant piping generally should (0.55°C) sub cooling must be allowed for each 5.5 ft (1.7m)
be designed to accomplish the following: vertical rise in order to avoid flash gas forming due to the weight
of the column of liquid refrigerant.
a. To ensure proper refrigerant feed to the evaporator.
b. To provide practical refrigerant line sizes without excessive UNTES UCUV-S Series units are designed with a sub cooling
pressure drop. circuit enough to sub cool the liquid 12°F (6.6 °C), which gives the
c. To maintain uniform return of lubricating oil to the liquid maximum 66 ft. (20m) lift without additional sub cooling.
compressor. Liquid suction heat exchanger can be used for additional sub
cooling in order to avoid flash gas forming.
d. To prevent refrigerant from entering the compressor and
causing compressor damage due to "slugging".
27
Rooftop Packaged Air Conditioners
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
UNTES UCUV-S Series Condensing Units are designed for satisfactory operation with single suction line.
1. Suction Line sizing selection recommendation in Table 17 is based on 2ºF temperature drop.
2. Double suction risers, for applications with systems having large variations in capacity , are recommended to ensure proper
oil low up and return to compressor.
3. Liquid line sizing selection recommendation in table 17 & 18 is based on 2ºF temperature drop.
4. Recommended line sizes in Table 17 are for guidance only. For detailed proper pip. For detailed proper piping, consult
recognized piping like ASHRAE Guide and Data Book for assistance.
5. Equivalent suction and liquid line lengths are shown in table 17 & 18.
UNTES is not responsible for faulty or improper design or sizing of refrigerant lines. The above recommendations do
not incorporate necesarry slopes. etc. that may be required on horizontal risers, etc.
28
ÜNTES Air Cooled Condensing Units UCUV-S Series - R-134a
UNTES UCUV-S Series Condensing Units are designed for satisfactory operation with single suction line.
1. Suction Line sizing selection recommendation in Table 18 is based on 2ºF temperature drop.
2. Double suction risers, for applications with systems having large variations in capacity , are recommended to ensure proper
oil low up and return to compressor.
3. Liquid line sizing selection recommendation in table 18 is based on 2ºF temperature drop.
4. Recommended line sizes in Table 18 are for guidance only. For detailed proper pi. For detailed proper piping, consult
recognized piping like ASHRAE Guide and Data Book for assistance.
5. Equivalent suction and liquid line lengths are shown in table 17 &18.
UNTES is not responsible for faulty or improper design or sizing of refrigerant lines. The above recommendations do
not incorporate necesarry slopes. etc. that may be required on horizontal risers, etc.
29