Professional Documents
Culture Documents
Tb18 PDF
Tb18 PDF
Natatorium Economizer
Vs. Conventional Dehumidifier
I NTRODUCTION This lower condition reduces the capacity of the system and
creates a variable, unpredictable moisture removal and cool-
This technical bulletin will review how an economizer-type ing capacity. To eliminate these issues, it is of typical design
indoor pool dehumidifier functions, and provide details on its to introduce the outside air between the evaporator and hot
control sequence. It will also outline the system's advantages gas reheat coil.
and disadvantages versus a conventional dehumidification
system. E CONOMIZER DEHUMIDIFIER
S TANDARD DEHUMIDIFIER An economizer type dehumidifier uses the same components,
but adds a mixing box between the evaporator and hot gas
A pool dehumidifier is defined as an air handler that is sized reheat coils. It also needs to add a full-sized return blower
to remove the moisture in a Natatorium at a rate equal to the prior to the evaporator. (Figure 2) This system now has the
evaporation rate of the warm pool water. To achieve this, capability to exhaust, and introduce 0 - 100% outdoor air into
mechanical refrigeration is utilized to cool the air down past the pool facility by modulating the dampers on the mixing
its dewpoint, and then use the recovered hot gas to reheat the box. Like the standard dehumidifier, the mixing box needs to
air or heat the pool water to reduce energy costs. During the be between the coils to insure proper operation in a pool facility.
summer cooling season, the system provides air conditioning
to the space. (Figure 1) An exhaust fan can easily be incorpo- The economizer type system functions as a standard dehu-
rated into this system to meet code ventilation requirements. midifier controlling the humidity, heating or cooling the
space, and providing code amounts of outdoor air. Under
The outside air is introduced into a dehumidification system certain weather conditions, the outdoor air can supply the
after the evaporator coil for several reasons. First, during the dehumidification requirements for the pool facility. When this
winter, the cold outdoor air may condense the return air at occurs, the compressors are turned off and the dehumidifier
undesirable places in the system or ductwork. Second, the acts as a modulating 100% outside air system. The actual
variability of the outdoor air will influence the design and per- amount of time that conditions are just right varies from loca-
formance of the evaporator coil. When colder outside air tion to location, but is estimated to be less than 17% of the
mixes with the return air from the poolroom, it lowers the year (a maximum of 1500 hours per year). Refer to Desert
mixed air conditions, which flows over the evaporator coil. Aire Technical Bulletin #7 for a detailed review.
O/A
E H A
R/A V G U Blw
A R X
P S/A
Blw
E H A
R/A V G U Blw
A R X
P Blw S/A
O/A
E H A
R/A V G U Blw
A R X
P S/A
O/A
Blw
E/A
Figure 3 - Select Aire Dehumidifier - Heating Mode E H A
R/A V G U Blw
A R X
P S/A
Blw
Dead
Zone
Damper % Open
Figure 5 - Mixing Box Airflow
O/A By-Pass E/A
Mode
Unoccupied 0% 100% 0%
Standard Dehumidifier with Code (typical) 20% to 30% 70% to 80% 20% to 30%
I MPACT OF BLOWERS
The differences in sizing blowers for a standard or Select-Aire Because of the high break horsepower requirements of the
dehumidifiers are significantly different than that of the econ- economizer's blower components, it increases the opera-
omizer type. The standard dehumidifier has one full-sized tional costs of the system. When the Select Aire system is
supply air blower and smaller code ventilation exhaust air compared to the economizer system at similar air volumes,
blower. The economizer requires two (2) full-sized blowers the blower energy operational costs are significantly different.
that must overcome higher internal static pressures caused Table 3 summarizes the different costs for a typical system.
by the dampers; double filtration and dead headed mixing air
plenum. Table 2 summarizes. The use of two full size blowers that must operate 24 hours
per day and overcome the higher static pressure virtually dou-
bles the blower operational costs of an economizer system.
The system would be required to exhaust the 5,000 cfm of If the economizer uses a semi-hermetic compressor, this will
cooled air (approximately at 52 F) to the outdoors, while also reduce the efficiency of the system. When a semi-her-
bringing in air that is 75 F to 95 F. Since you cannot deliver metic compressor is unloaded, it closes one of the cylinders,
the cooled air to the space, the system must be de-rated. but does not stop its motion. Therefore the BTU output per
kW input will be greatly reduced and the systems overall
As table 4 demonstrates, the efficiency of the economizer sys- moisture removal efficiency (MRE) will be reduced. A system
tem is significantly impacted by the position of the mixing using scroll compressors will stage off a complete compres-
box. This reduction in cooling capacity is normally not con- sor, thus totally removing its power requirements and there-
sidered in the payback analysis of the dehumidification systems. fore maintaining its MRE.
One of the arguments is that the economizer system can offer Another energy issue is if the when the economizer design
free cooling. Free cooling is when the outdoor air is cooler uses a full face evaporator coil (4 row) vs. a shorter 8 row coil
and dryer than the indoor air. It can provide cooling and which uses a bypass damper. The full-face coil is cheaper to
dehumidification without the use of the compressors. The install, but causes the system to operate at a higher suction
applications geographical location determines how often con- temperature to remove the same amount of moisture. When
ditions are suitable for the economizer or "free cooling" mode. a refrigerant system runs at a higher suction pressure, the
The frequency of these conditions can be predicted using a compressor must work harder and experiences a reduction in
detailed bin hour weather program. As a rule of thumb, many efficiency.